Status / Error message

Possible cause 

Correction 

A50

 

Fan inverter

Internal fan fault.

Please contact your authorised Webasto Marine dealer.

A51

 

PFC module inverter

Module fault. Excess current C1, C2: connections short-circuited.

A53

 

STO inverter

Internal module fault “Safe Torque Off”. No contact between "Safe  Torque Off" connection and pc-board.

A54

 

STO inverter

No display on screen; compressor  and sea water pump not running. 

Fuse faulty or break/short-circuit in this electrical circuit. 

Pc-board damaged by high voltage (RT1 blown). 

Sea water pump(s) start up direct- ly after the control is switched on.

Wiring of pump 1 (sea water) and pump 2 (cold water) interchanged. 

Please contact your authorised Webasto Marine dealer. 

Compressor keeps cutting in and  out.

Shortage of cold water. 

No or insufficient cooling or heat- ing capacity.

Poor air or water flow, soiled or circulation blocked. 

Secure adequate air or water flow   (see A01 and/or A02). 

Refrigerant shortage. 

Please contact your authorised Webasto Marine dealer.

Oil block. 

Refrigerant circuit blocked. (Filter or expansion valve). 

Compressor fault. 

Incorrect room/ambient tempera- ture or water temperature dis- played.

Temperature sensor positioned incorrectly, subject to interference or  display values falsified. 

Check whether the sensor is subject to direct fault sources such as  direct sunlight or devices radiating heat. Please contact your author

-

ised Webasto Marine dealer.

Compressor not running.

The target temperature of the cold water is reached. No correction  necessary:  0°C (cooling mode), 49°C (heating mode).

The system starts up on reaching a defined cold water temperature.  Cut-in temperature::  4°... 8°C (cooling mode), 41°... 45°C (heating mode).

Compressor defective or break/short-circuit in compressor wiring.

Please contact your authorised Webasto Marine dealer.

Compressor 2: Compressor overload or overload protection element  on top of compressor defective.

Incorrect compressor settings.

Содержание BlueCool V50 M

Страница 1: ...Water Marine Air Conditioning Systems BlueCool V Series EN Valid for BlueCool V50 M as of change index C 2017 Typ V50 M WBCL1203001C Valid for BlueCool V77 T V64 T as of change index B 2017 Typ V64 T...

Страница 2: ...undings Highlight Explanation 3 3 Requirements for the fol lowing necessary action X X Necessary action 1 4 Warranty and liability Webasto shall not assume liability for defects or damage that are the...

Страница 3: ...touch sensitivity of the screen is optimised to direct contact with the fingers The screen may not respond to touch if gloves are worn Tapping outside the touch sen sitive area at the edge of the scre...

Страница 4: ...reen provide infor mation on the system status The symbols are explained in the table Symbol Meaning 1 On Off 2 Temperature 3 Fan 4 Settings 6 Notification 7 Increase values 8 Decrease values 9 AUTO A...

Страница 5: ...n the set setpoint temperature and the room temperature measured by the cabin temperature sensor Note The system only cools under the following conditions cabin tem perature 15 C Setpoint tem perature...

Страница 6: ...c changeover between cooling and heating 9 System settings The operating logic is explained based on the Timer function The explanation also applies to other setting levels or functions Fig 6 1 3 Time...

Страница 7: ...1 6 Standby Sets the BlueCool MyTouch display to standby mode The available functions are Webasto Logo Shows the Webasto logo Customer logo Shows an individual file that can be loa ded onto BlueCool M...

Страница 8: ...our authorised Webasto Marine dealer A01 Low pressure compressor 1 Incorrect pressure sensor measurement Please contact your authorised Webasto Marine dealer Compressor switches off in heating mode se...

Страница 9: ...Please contact your authorised Webasto Marine dealer A10 Cold water temperature sensor Cold water temperature sensor defective or break short circuit in electrical circuit A15 Cold water flow The flo...

Страница 10: ...mpressor temperature sensor Compressor temperature sensor defective or break short circuit in electrical circuit A27 Data communication in verter No data communication between inverter and pc board A2...

Страница 11: ...s at too high a load A39 Cable bridge inverter Compressor 1 switched off because the input is not bypassed open Cable not connected Function of external relay 24V voltage not applied A40 Compressor 1...

Страница 12: ...ulation blocked Secure adequate air or water flow see A01 and or A02 Refrigerant shortage Please contact your authorised Webasto Marine dealer Oil block Refrigerant circuit blocked Filter or expansion...

Страница 13: ...n the Webasto service centre leaflet or the website of the respective Webasto representative of your country Ident No WBCL010825E 08 18 Errors and omissions excepted Webasto Thermo Comfort SE 2017 Web...

Отзывы: