INSTALLATION MANUAL

7

TROUBLESHOOTING CHART (CONT’D)

Symptoms

Possible Cause(s)

Suggested Remedies

Pump will not  
start or run 
 
 
 
 
 
 

1. Water level too low
2. Blown fuse or tripped circuit breaker 

3. Low supply voltage
4. Motor
5. Switch
6. Inlet clogged
7. Switch obstruction

1. Water must be at the appropriate level to activate switch 
2. If blown, determine cause and then either replace with proper 

sized fuse or reset breaker

3. Contact an electrician
4. Replace pump
5. Replace switch
6. Remove debris
7. Remove obstruction to verify free motion of switch

Pump starts and 
stops too often

1. Back-flow of water from discharge 

pipe

2. Switch
3. Check valve not functioning properly 

or leaking

1. Install check valve 

2. Replace switch
3. Remove and examine check valve for prop er in stal la tion and free 

operation. Replace check valve if necessary.

Pump shuts off 
and turns on 
independently 
of switch (trips 
thermal overload 
protection)

1. Switch
2. Switch obstruction
3. Obstruction in discharge pipe
4. Low supply voltage

1. Replace tether switch
2. Remove obstruction to verify free motion of switch
3. Remove obstruction in discharge piping
4. Contact an electrician.

Pump operates 
noisily or vibrates 
excessively

1.  Worn bearings
2.  Impeller broken
3.  Piping attachments to building 

structure too rigid or too loose

1.  Replace pump
2.  Replace pump
3.  Install rubber coupling (available at local hardware stores) to isolate 

pump vibration from discharge plumbing

Pump will not 
shut off

1. Switch
2.  Switch obstructions
3.  Restricted discharge (obstruction in 

piping)

4.  Excessive inflow or pump not 

properly sized for application

1.  Replace switch
2.  Remove obstruction to verify free motion of switch
3.  Remove obstruction from discharge piping

4.  Recheck all sizing calculations to determine proper pump size

Pump operates 
but delivers little 
or no water

1.  Low supply voltage
2.  Inlet clogged
3.  Broken impeller
4.  Pump not properly sized for 

application

5.  Check valve stuck closed or 

installed backwards

6.  Shut off valve closed

1.  Contact an electrician
2.  Remove debris
3.  Replace pump
4.  Recheck all sizing calculations to determine proper pump size

5.  Remove and examine check valve for proper installation and free 

operation

6.  Open valve

Содержание T50SW

Страница 1: ...l DISCHARGE 2 in NPT T50SW F50SW 3 in NPT supplied 2 in Adapter 200SW 100SW 75SW Sewage Pump www blueangelpumps com PERFORMANCE Model HP Discharge Head 5 ft 10 ft 15 ft 20 ft T50SW 1 2 Gal hr 7680 660...

Страница 2: ...ment mise la terre FOR ADDED SAFETY the receptacle must be protected with a ground fault circuit interrupter GFCI All wiring must be performed by a qualified licensed electrician and comply with the N...

Страница 3: ...ACHEMINEMENT D EAU DESTIN E LA CONSOMMATION Ne pas utiliser la pompe pour transporter de l eau qui sera utilis e comme de l eau potable destin e la consommation La pompe doit tre utilis e uniquement...

Страница 4: ...PUMP SHOULD BE USED when risk of property damage from high water levels exists UNE ALARME AUTONOME DE NIVEAU D EAU LEV OU UNE POMPE DE SAUVEGARDE DOIVENT TRE UTILIS ES en cas de risque de d g ts mat...

Страница 5: ...discharge pipe size below that which is provided on the pump 7 If optional control device or float is used follow mounting instruction supplied with device or float 8 A union should be installed above...

Страница 6: ...n of switch 3 Remove obstruction in discharge piping 4 Contact an electrician TROUBLESHOOTING WARNINGS ALWAYS DISCONNECT THE PUMP FROM POWER SUPPLY before installing servicing or making any adjustment...

Страница 7: ...Replace tether switch 2 Remove obstruction to verify free motion of switch 3 Remove obstruction in discharge piping 4 Contact an electrician Pump operates noisily or vibrates excessively 1 Worn bearin...

Страница 8: ...p Check in on your sewage pump and reset the GFCI if necessary Ensure the pump itself is standing upright Vibrations during operation can cause it to fall or tilt onto one side This can jam the float...

Страница 9: ...t cover Products which have been damaged as a result of accident abuse misuse neglect improper installation improper maintenance or failure to operate in accordance with Blue Angel Pumps written instr...

Страница 10: ...__________ _____________________________________________________________________________________________ _____________________________________________________________________________________________ _...

Страница 11: ...__________ _____________________________________________________________________________________________ _____________________________________________________________________________________________ _...

Страница 12: ...12 www blueangelpumps com...

Отзывы: