22
NO
NO IGNITION ARC ESTABLISHED
1. RESET CONTROL: -MOTOR STARTS – COMPLETES 30 SECOND PREPURGE CYCLE, 8 SECOND SAFE START CHECK SERIES.
-GAS VALVE OPENS, REGULATING ADEQUATE GAS PRESSURE.
-NO FLAME ESTABLISHED – PRIMARY CONTROL LOCKS OUT AFTER 4 SECOND HONEYWELL SERIES TRIAL FOR IGNIITION PERIODS.
IN ORDER FOR THE FOLLOWING FUNCTIONAL TEST TO BE MADE, THE CONTROL MUST BE RESET AND THE
TESTS MONITORED DURING THE 4 SECOND HONEYWELL SERIES TRIAL FOR IGNITION THAT OCCURS AT THE
END OF THE 30 SECOND PREPURGE CYCLE, AND THE 8 SECOND SAFE START CHECK.
2. CHECK FOR 120VAC BETWEEN TWO LEADS OF IGNITION TRANSFORMER.
CHECK ELECTRICAL WIRING AND CONNECTIONS PER
WIRING DIAGRAM FIG. 11.
CHECK THE FLAME SENSING CIRCUIT FOR:
1.
GROUNDED FLAMEROD
2.
DAMAGE TO FLAMEROD LEAD INSULATION
3.
CHECK FLAME ROD FOR DEPOSITS.
REFER TO TECHNICAL INFORMATION, PAGE 34.
NOTE:MAKE SURE THE FLAMEROD CIRCUIT AND/OR
PRIMARY CONTROL IS MOISTURE FREE.
OK
OK
REPLACE PRIMARY IGNITION CONTROL.
3. CHECK ELECTRICAL WIRING AND CONNECTIONS PER FIG. 11.
OK
OK
4. CHECK HIGH VOLTAGE LEAD AND CONNECTION TO IGNITION ELECTRODE ROD.
OK
5. INSPECT IGNITION ELECTRODE FOR CRACKED INSULATOR AND CORRECT GAP FIG 1.
OK
6. REPLACE IGNITION TRANSFORMER
Содержание EHG
Страница 16: ...16 EHG POWER GAS BURNER WITH HONEYWELL S89F GAS PRIMARY AND GAS TRAIN ASSEMBLY Figure 11...
Страница 17: ...17 EHG POWER GAS BURNER WITH HONEYWELL S89F GAS PRIMARY AND GAS TRAIN ASSEMBLY CONTINUED Figure 11 continued...
Страница 35: ...35 Cover Manifold Orifice Assembly Figure 27...
Страница 36: ...36 Burner Exploded and Assembled Views 64021 003 Figure 28...
Страница 38: ...38 Control Box Assembly 63479 004 or 63479 005 Figure 29...
Страница 39: ...39 Control Box Assembly 63479 004 or 63479 005 Figure 29 Continued...
Страница 41: ...41 Gas Train Assembly with Regulator 63527 001 Figure 31...
Страница 44: ...44 Flange 20614 Figure 33...
Страница 47: ...47 NOTES...