18 

 

Intermittent flame failure occurs during 

a “call for heat” 

 

If the oil primary control stops sensing a flame after the flame has been proven and the trial for ignition timer has expired, 
the oil primary control enters a limited recycle mode where it will de-energize the burner for one minute, while the LED 
light will flash for 2 seconds on, and 2 seconds off. After one minute the oil primary control resumes the call for heat, and 
enters 

another “trial for ignition” period. If a flame is proven during the trial for ignition, and lost after the trial for ignition 

timer expires the control will go into another recycle mode countdown. If no flame is proven during the trial for ignition 
period the control will go into a lockout condition. If the control tries three recycle modes where flame is proven, and then 
subsequently lost the control will go into a hard lockout condition de-energizing the burner. If normal ignition does not 
occur see 

GENERAL TROUBLESHOOTING GUIDE

 on page 7.

 

SEQUENCE OF OPERATION: BURNER WITH R7284P CONTROL 

 

BURNER OPERATION 

On every call for heat the oil primary control performs an internal safety check which takes five seconds to complete. 
During these five seconds, the oil p

rimary control verifies that the cad cell is outputting a “no flame” resistance value. After 

the check, the oil primary control will simultaneously energize the burner blower motor, solenoid valve (if equipped), and 
ignition device. The oil primary control will then enter the 15 second trial for ignition period; once flame is established the 
oil primary control will continue to monitor the flame by using the cad cell, and it will de-energize the ignitor after 10 
seconds. The oil primary control allows burner operation to continue until the thermostat control

’s “call for heat” is 

satisfied. Once the thermostat is satisfied the burner will be de-energized. If flame is not detected during the trial for 
ignition, the oil primary control will go into a “lock-out” condition. If this occurs, proceed to the section titled SAFETY 
LOCK-OUT TIME. 

 

SAFETY LOCK-OUT TIME 

 

Ignition fai

lure occurs during the first “trial for ignition” period 

 
The cad cell monitors the combustion chamber for flame during the burner’s trial for ignition period. If no flame is detected 
the oil primary control will go into a lockout condition. When the control goes into lockout it will de-energize the burner, 
and the control’s screen will display “lockout mode”. Before attempting to start the burner again the control must be reset. 
Press and hold the “i” button for three seconds to reset the control. If normal ignition does not occur see 

GENERAL 

TROUBLESHOOTING GUIDE

 on page 7. 

 

 

 
Intermittent f

lame failure occurs during a “call for heat” 

 
If the oil primary control stops sensing a flame after the flame has been proven and the trial for ignition timer has expired, 
the oil primary control enters a limited recycle mode where it will de-energize the burner for one minute while displaying 
“recycle” on the display screen. After one minute the oil primary control resumes the call for heat, and enters another “trial 
for ignition” period. If a flame is proven during the trial for ignition, and lost after the trial for ignition timer expires the oil 
primary control will go into another recycle mode countdown. If no flame is proven during the trial for ignition period the oil 
primary control will go into a lockout condition. If the oil primary control tries three recycle modes where flame is proven, 
and then subsequently lost the control will go into a hard lockout condition de-energizing the burner. If normal ignition 
does not occur see 

GENERAL TROUBLESHOOTING GUIDE

 on page 7. 

 
 
 
 

 

 Do not keep pressing the reset button and restarting the burner more than once with the burner not 

lighting this could cause oil buildup in the firing chamber. This will cause smoking and possible detonation that could 
damage the equipment if the burner does light. 

Содержание EH

Страница 1: ...l ASTM D 396 Kerosene Diesel ASTM D975 18 JP8 Dimensions Standard Height 12 1 2 Width 15 1 2 Depth 8 1 4 Center Line of Tube to Floor 8 1 16 Mounting Rigid Flange Adjustable Flange or Pedestal Mount R...

Страница 2: ...R S NAME CONTRACTOR NAME CONTRACTOR ADDRESS CONTRACTOR PHONE NUMBER CONTRACTOR LICENSE DATE OF INSTALLATION COMMENTS ABOUT INSTALLATION START UP THESE INSTRUCTIONS SHOULD BE AFFIXED TO THE BURNER OR A...

Страница 3: ...s situation which if not avoided may result in minor or moderate bodily injury Indicates a situation that may result in equipment related damage This is the safety alert symbol It is used to alert you...

Страница 4: ...ecialized equipment Allow only qualified burner service persons to adjust the burner Special instruments and training are required Read the burner manual before using CARBON MONOXIDE POISONING Early s...

Страница 5: ...T CONTROL 19 OPERATIONAL CHECK OF BURNER 19 START SYSTEM 19 CHECK SAFETY FEATURES 19 GENERAL INSTALLATION INFORMATION 20 COMBUSTION CHAMBER 20 FUEL PUMPS 20 FUEL LINES 20 FUEL TANKS 21 ELECTRICAL WIRI...

Страница 6: ...n the problem listed in order from most likely to least likely and the solution to correct each root cause that may be affecting burner performance The solution listed for each root cause will referen...

Страница 7: ...acing gap to small Clean and position electrode tips according to Figure 14 or Figure 15 on pages 26 27 Plugged fuel filter Replace as needed Misadjusted burner air bands Re adjust air bands for clean...

Страница 8: ...trol observe burner sequence of operations If burner remains on standby see Burner does not light Honeywell controls remains on standby on page 10 Oil gun depth spaced too far ahead causing electrodes...

Страница 9: ...urner past call for heat Applicable only if burner comes with oil primary control Identify control model Replace Control and wire accordingly to Figure 3 or Figure 4 on page 16 Faulty fuel pump shut o...

Страница 10: ...roper sequence of operations If burner does not light go to step 5 5 Jumper oil primary T T terminals Burner starts Trouble in thermostat or limit circuit Check wiring connections Burner does not star...

Страница 11: ...limit circuit Burner starts but doesn t stay running Disconnect line voltage and open thermostat or limit switch Check all wiring connections If burner does not stay running go to step 6 6 Check that...

Страница 12: ...e voltage and close line switch Start burner Burner locks out Go to step 9 Burner keeps running until call for heat is satisfied System is okay 9 Check Control Cad cell Remove cad cell wires from conn...

Страница 13: ...13 Figure 1 Burner Components Models EHASR EHA and EH...

Страница 14: ...Control 15 second Honeywell R7284G 101343 SER 101343 SER 101343 SER 18A 1 Cast Iron 3 9 16 No Vane 13003 230V Control 15 second Honeywell R8184G 100490 001 18B 1 Stainless SR 1A 14157 120V Control 15...

Страница 15: ...12988 002 21913 SER 2 Stamped Stabilizer Support Kit 21923 001 21923 001 21923 001 Cast Stabilizer Support Kit 21408 SER 21408 SER 21408 SER 3 Stem Insulator Kit 13286 13286 13286 4 Cad Cell Mount 130...

Страница 16: ...gure 3 Wiring Diagram for 120V Honeywell R7284G 230V Honeywell R8184G Controls Figure 4 Wiring Diagram for 120V Honeywell R7284P Control REMOVE JUMPER TO USE THERMOSTAT TERMINALS REMOVE JUMPER TO USE...

Страница 17: ...l be de energized If flame is not detected during the trial for ignition the oil primary control will go into a lock out condition If this occurs proceed to the section titled SAFETY LOCK OUT TIME SAF...

Страница 18: ...zed If flame is not detected during the trial for ignition the oil primary control will go into a lock out condition If this occurs proceed to the section titled SAFETY LOCK OUT TIME SAFETY LOCK OUT T...

Страница 19: ...light and operate until call for heat is satisfied CHECK SAFETY FEATURES Simulate flame failure Follow starting procedures to turn on burner Close hand valve on supply line stopping fuel delivery to t...

Страница 20: ...so the face of the air cone on the burner is set a inch behind the inside front wall of the chamber see Figure 20 on page 30 FUEL PUMPS Model EHASR EHA and EH oil burners are provided with single sta...

Страница 21: ...y control and no voltage should be connected to it For boilers it may be necessary to leave the T T terminal jumped as the aquastat may be providing the voltage to the burner and controlling when volt...

Страница 22: ...the use of an 80 degree solid nozzle is a good starting point Always use the proper nozzle size spray cone type and spray angle the appliance manufacturer recommends Should this information not be av...

Страница 23: ...ASR Oil Line Assembly Fitting 2 Loosen and disconnect the brass nut of the copper oil line assembly from the oil gun assembly fitting and rotate the oil line out of the way Figure 8 Figure 8 EH EHASR...

Страница 24: ...s will allow the igniter device assembly to swing open to the left For now leave the plate in the closed position Figure 9 Figure 9 EH EHASR Ignitor mounting plate screw removal 4 Using a 9 16 inch wr...

Страница 25: ...oil gun to the right out of the housing slot and the slot plate cover Figure 11 Figure 11 EH EHASR Oil Gun Removal 6 While rotating the oil line fitting adapter up at a 45 degree angle gently lift bu...

Страница 26: ...up Figure 13 Figure 13 EH EHASR Oil Gun Nozzle Installation Flamelock and electrodes removed for clarity 8 Identify which burner model you have then measure and verify that the electrode spacing is p...

Страница 27: ...mbly in burner to verify that the position has not shifted SETTING GUN DEPTH For the oil burner to function properly the distance between the nozzle and the air cone needs to be maintained as shown in...

Страница 28: ...pth Adjustment 3 Once in the required position per Figure 16 and Figure 17 retighten the hex lock nut and slot cover screw move and align arrow decal with slot plate cover Close the ignition transform...

Страница 29: ...in such a manner that all controls will be readily accessible for inspection cleaning adjustment and repairs INSTALLATION OF MOUNTING FLANGE Position the mounting flange on the furnace wall adjusting...

Страница 30: ...ING BURNER Be sure that the electrical breaker to the appliance is in the OFF position set the thermostat to a temperature substantially above room temperature and ensure the oil tank is filled all va...

Страница 31: ...or the location of the bleeder valve on the pump Figure 22 Fuel Pump Bleeder Valve Location Note If the pump is set up in two pipe operation with the by pass plug installed bleeding the pump is not ne...

Страница 32: ...e most common cause CO2 readings must be taken ahead of draft control if used The CO2 measured in the stack should be at least 10 12 for oil rates 1 00 gal hr or below and at least above 10 for oil ra...

Страница 33: ...oper nozzle Electrode Settings This is very important for reliable ignition of the oil check these once a year in accordance with the instructions provided in this manual Replace electrodes if worn ex...

Страница 34: ...73 0 7 5 70 0 68 5 10 5 85 5 84 0 82 5 81 0 79 5 78 0 76 5 75 0 73 8 72 0 70 5 69 0 67 5 10 85 0 83 5 82 0 80 5 78 8 77 3 75 8 74 3 72 8 71 0 69 5 68 0 66 3 9 5 84 5 83 0 81 5 79 8 78 0 76 5 75 0 73...

Страница 35: ...1 11 5 1 35 12 11 x 11 11 5 1 50 13 11 x 12 12 5 1 65 14 12 x 13 13 5 1 75 14 12 x 13 13 5 2 00 15 13 x 14 13 1 2 5 1 2 2 50 17 14 x 16 14 5 1 2 3 00 15 1 2 x 15 1 2 17 1 2 13 x 18 1 2 14 7 3 50 17 3...

Страница 36: ...36 REFERENCE FIGURES Figure 25 Pump Feature Identification Figure 26 Blower Wheel Spacing...

Страница 37: ...36 31 16 27 24 18 1 2 O D Copper Tubing 0 100 100 100 100 2 100 100 100 100 4 100 100 100 100 6 100 100 100 100 8 100 100 100 100 10 100 100 100 100 12 83 70 100 100 14 41 35 100 100 16 100 100 18 76...

Страница 38: ...to the centerline of fuel pump is H 7 ft inch copper tubing is being installed and the oil pump max flow rate is rated at 3 gal hr according to the label Q 3 gal hr the maximum total line length L wou...

Страница 39: ...nts to those who purchase its Oil Burner Models for resale or for incorporation into a product of resale that its burner is free from defects in material and workmanship under normal use and service f...

Страница 40: ...40 NOTES...

Отзывы: