background image

6 of 23

WX-501-0552 • 01.22

Fault State

The Click 111 receives datagrams from the connected SmartSensor, and it’s looking for datagrams containing 

detection data that’s intended for one of its output channels. If a bus does not receive such a datagram for ten 

seconds, it will go into a fault state. (The fault timeout can be changed using Click Supervisor software, as will be 

discussed later.) Each data bus can go into a fault state independently. The state of the output channels, when 

they are in fault, can be configured as either a call or a no call.

If either of the buses go into a fault state then the master fault will be asserted. The card has one master fault 

indicator (the blue LED on the faceplate of the device) and an associated output on the back connector. You can 

disable failsafe for the whole card if you desire.

Configuration

The Click 111 can be configured in three ways: DIP switches, the front panel menu, and Click Supervisor.

These three different configuration methods can configure different sets of options; some of these parameters 

can be set using multiple configuration methods, and some of them can only be set using one particular method. 

The table below lists how each parameter may be accessed and configured.

DIP Switch

Front Panel Menu

Click Supervisor

Baud Rate

Yes

Yes

Yes

Base Channel

Yes

Yes

Yes

Channel Allocation

Yes

Yes

Yes

Data Enable

Yes

Yes

Yes

Channel Output Polarity

Yes

Yes

Yes

Fault Output Polarity

Yes

Yes

Yes

Fault Enable

Yes

Yes

Yes

Fault State

Yes

Yes

Yes

Autobaud

No

Yes

No

Reset to Defaults

No

Yes

Yes

Description

No

No

Yes

Location

No

No

Yes

Device ID

No

No

Yes

Fault Detect Time

No

No

Yes

To use this configuration 

feature:

Hardware Configuration 

Mode

Software Configuration 

Mode

Software Configuration 

Mode

The final row on the table refers to configuration modes. The DIP switches can be used to choose between 

Hardware and Software modes. If the switches are set to Hardware mode, the DIP switches will be used to 

change configuration options. If the switches are set to Software mode, the front panel menu and Click Supervisor 

will be used to change configuration options. This will be discussed in greater detail in the DIP Switches section 

below.

Note. 

Any setting which has been configured via the DIP switches will be read-only in Click Supervisor and the 

front panel menu.

Содержание Click 111

Страница 1: ...thers 9600 5 6 7 8 1 2 3 4 0 0 0 0 SW 0 0 0 1 1 0 0 1 0 3 0 0 1 1 5 0 1 0 0 7 0 1 0 1 9 0 1 1 0 11 0 1 1 1 13 1 0 0 0 15 5 6 7 8 1 2 3 4 1 0 0 1 17 1 0 1 0 19 1 0 1 1 21 1 1 0 0 23 1 1 0 1 25 1 1 1 0...

Страница 2: ...of the device as follows Yellow RD Lights up when the Click 111 is receiving data on any port Green TD Lights up when the device is transmitting data on any port Blue MF This LED indicates whether the...

Страница 3: ...put channels will be covered later So as long as one of these options suits your needs for output channels using a single Click 111 as outlined below will work just fine 1 If you re using hardware con...

Страница 4: ...vered in the DIP Switches section 2 Insert two cards into the rack 3 Connect a patch cable from one of the RJ 11 jacks labeled Bus 1 on the faceplate of the first Click 111 to the surge protector Clic...

Страница 5: ...onnection A6 No connection A7 Fault Status Out A8 No connection A9 DC common A10 No connection A11 DC common A12 Channel 5 normally open A13 No connection A14 DC common A15 Channel 9 normally open A16...

Страница 6: ...ing multiple configuration methods and some of them can only be set using one particular method The table below lists how each parameter may be accessed and configured DIP Switch Front Panel Menu Clic...

Страница 7: ...to choose between Hardware Software modes If Software mode is selected the parameter must be configured using the front panel menu or Click Supervisor If Hardware mode is selected the parameter can b...

Страница 8: ...he front panel menu will be able to display the current setting but not change it If all switches are off down Software mode is selected and only Click Supervisor and the front panel menu will be able...

Страница 9: ...the current setting but not change it If all switches are off down Software mode is selected and only Click Supervisor and the front panel menu will be able to both display and change the current set...

Страница 10: ...know a bus will not be receiving any data for instance if you re only using one sensor with your Click 111 If a bus is disabled from receiving data then its associated channels will not go into a faul...

Страница 11: ...e front panel menu will be able to both display and change the current setting Warning If you don t have switch 1 on flipped up to set it to Hardware mode anything you set on switches 2 and 3 will be...

Страница 12: ...bank will be referred to as Level 2 and is used in configuring the menu options Mode Menu RD TD MF PWR 1 2 3 4 Detection 1 4 5 8 9 12 13 16 Note The multicolored LEDs also function as activity status...

Страница 13: ...hes As shown above the menu options are displayed on the Level 1 LEDs and the configuration parameters are displayed on the Level 2 LEDs If a configuration parameter has been set using the DIP switche...

Страница 14: ...bled Bus 1 Data Enabled Bus 2 Data Disabled Bus 1 Data Disabled Bus 2 Data Enabled Bus 1 2 Data Enabled Default LED off Cancel and exit menu LED on See the Navigating through the Menu and the Menu Ope...

Страница 15: ...ud rate for bus 1 Level 2 LEDs 9600 bps default 19200 bps 38400 bps 57600 bps LED off Cancel and exit menu LED on Navigating through the Menu and the Menu Operation Example sections for how to configu...

Страница 16: ...ey are set to Hardware the front panel menu will be able to display but not change these settings Channel Allocation The next parameter on the front panel menu label is channel allocation To select th...

Страница 17: ...an also be changed using the DIP switches or Click Supervisor This parameter lets you choose the polarity of the calls placed by the Click 111 A call can be indicated by either high voltage or low vol...

Страница 18: ...d red LEDs come on solid Note This parameter can also be changed using the DIP switches or Click Supervisor This parameter lets you choose whether the device will go into a fault state at all If fault...

Страница 19: ...the Navigating through the Menu and the Menu Operation Example sections for how to view this parameter After the Click 111 has reset to factory defaults it will check the DIP switches if any of them a...

Страница 20: ...ation about your device The tab has the following parameters see the figure and table below Note This parameter can only be configured using Click Supervisor Setting Description Module Allows you to e...

Страница 21: ...e and table below Note These parameters can also be configured using the DIP switches or the front panel menu if in the DIP switches they are set to Hardware mode the parameters will appear grayed out...

Страница 22: ...is low or high when the output is asserted Chan Out Polarity Lets you choose the polarity of the output channels whether the voltage is low or high when there is a call on that channel Fault Enable Le...

Страница 23: ...ve your settings return to the Select Driver screen and more The Save menu allows you to save your settings Select Save to File to save your settings to a file Selecting this will open a directory box...

Отзывы: