background image

14

15

TnT RCD

User Manual

Wavecom

TnT RCD

User Manual

Wavecom

RCD Trip Time Testing: 

This test is designed to trip RCD devices at a fixed current and to determine the trip time of the RCD device. 

During an RCD Trip Time test, the TnT RCD injects a true fault current value using a real-time compensation 

calculation of the actual voltage at the time of test, delivering a true and accurate trip current. The TnT RCD will 

measure the time the RCD takes to trip in milliseconds, and display it on the screen. This function is factory set 

to 30mA for fast testing, but the user can set the current to x0.5, x1.0 or x5.0 using the RCD Multiplier.

For example:  

30mA * 0.5 =15mA

30mA * 1.0 = 30mA - This also is effective on any set test current of the RCD tester from 5mA to 500mA output.

30mA * 5.0 = 150mA

These tests should result in no-trip, trip & fast trip times respectively.

To enter the RCD menu from Main Menu B, press the F3 button. Then, to set up a Trip Time Test, press F1. Before 

performing an RCD Trip Time Test, the TnT RCD should be configured to ensure an accurate result. 

RCD Test Options:

To adjust the Trip Time test options, press F3 . This allows the user to set the trip current level, 5mA to 500mA. 

The RCD type can also be select here depending whether the unit is a Type I or Type II RCD. From the options 

menu, press F2 to change the current level and F3 to change the RCD type. 

Adjusting the current level:

The TnT RCD displays and maintains the last set trip current value. If the user wishes to change the value of the 

trip current the following steps enable the changes. Press F2 from the options menu to display test current.

F1 - Raises the trip current in 1mA increments to 500mA. Hold the button and the value will scroll faster the longer it is 

pressed. Once 500mA limit is reached the value will then loop over and start again from 0mA

F2 - Decreases the trip current in 5mA increments. Hold the button and the value will scroll faster the longer it is pressed. 

Once 0mA limit is reached the value will then loop over and start again from 500mA.

Enter - Sets the selected current for the next trip time test. The TnT RCD will then return to the current trip time test 

screen.

Changing RCD Type:

Depending on the RCD, the RCD type needs to be selected from the options menu. These options change the 

pass / fail values when performing RCD tests. Please make sure that you have the correct RCD type selected. 

 

F1 - Sets RCD Type to Type 1

F2 - Sets RCD Type to Type 2

You will be promoted to enable or disable Portable RCD (PRCD) testing - unless you are testing a switchboard 

RCD, turn PRCD on.

Conducting the Trip Time Test

1.  Complete a Visual Inspection.  For details refer to the First Test section.  If the device passed the Visual 

Inspection, continue with the following instructions, if not, refer to the First Test section. 

2.  Navigate to Main Menu B, and press F3 to enter the RCD Menu, then press F1 to select Time Test

3.  Press F3 to enter the Time Test options menu, to ensure your TnT RCD has the correct settings for the type 

of RCD (cont...) 

4.  (cont...) Once your TnT RCD is set up correctly, select either the 0° (Positive) or the 180° (Negative) Phase to 

test. Both phases should be tested, and after the first test, you can select ‘Retest’ to test the other phase.

5.  When ready, press F3 to begin the test - the RCD will trip, and the time will be recorded in milliseconds.

6.  TnT RCD testers will switch to battery power (if charged) and stay on, but will need to be Mains Powered 

again to conduct further RCD tests.

7.  You can now retest the other phase of the RCD, or simply print your tag and record your results.

RCD Ramp Testing

 

This test is designed to trip RCD devices using a ramping up current value, to determine the trip current of the 

RCD device.  This useful test allows the user to determine circuit leakage load/pre-loading of RCD circuit.  This 

can assist in determining nuisance tripping issues (RCD is too sensitive) or determining RCD performance if 

suspected faulty or inconsistent in performance.  The TnT RCD has a nominal leakage current of 2mA, which 

should be added to the result of test.  

E.g. if RCD tripped at 22mA, add 2mA  to get a value of 24mA trip current.

To enter the RCD menu from Main Menu B, press the F3 button. Then, to set up a Ramp Test, press F2. Before 

performing an RCD Ramp Test, the TnT RCD should be configured to ensure an accurate result. 

Changing RCD Type:

Depending on the RCD, the RCD type needs to be selected from the options menu. These options change the 

pass / fail values when performing RCD tests. Please make sure that you have the correct RCD type selected. 

 

F1 - Sets RCD Type to Type 1

F2 - Sets RCD Type to Type 2

You will be promoted to enable or disable Portable RCD (PRCD) testing - unless you are testing a switchboard 

RCD, turn PRCD on.

Conducting the Ramp Test

1.  Complete a Visual Inspection.  For details refer to the First Test section.  If the device passed the Visual 

Inspection, continue with the following instructions, if not, refer to the First Test section. 

2.  Navigate to Main Menu B, and press F3 to enter the RCD Menu, then press F2 to select Ramp Test

3.  Press F2 to select your RCD Type, and turn Portable RCD testing on or off

4.  Press F3 to begin the test - the TnT RCD will increase the current to the RCD until it trips, displaying the 

current on screen.

5.  TnT RCD testers will switch to battery power (if charged) and stay on, but will need to be Mains Powered 

again to conduct further RCD tests.

6.  You can now print your tag and record your results.

Содержание TnT RCD

Страница 1: ...Wavecom User Manual Certificate of Warranty and Product Support Information TnT RCD Portable Appliance Tester ...

Страница 2: ... Tester should be calibrated every 12 months A correctly calibrated tester is essential for ensuring testing accuracy is maintained and for complying with the AS NZS 3760 2010 To book your tester in for calibration go to https www wavecom com au calibration_services php Then send your tester to your nearest calibration service centre For Western Australian customers Wavecom WA Calibrations Unit 2 ...

Страница 3: ...t 19 Leakage Test 20 Earth Continuity Test 20 Integrated Tests 20 No Connection No Test 21 Wavecom Tags 22 Tester Serial WinPATS Coupon Code Purchase Information Rear Cover TnT RCD Portable Appliance Tester IEC Test Lead 500mm Orange USB A to USB B Interface Cable Earth Lead with Alligator Clips 1800mm Black IEC Power Cable 10A units IEC 20 10 Power Cable with Circuit Breaker 20A Units 24 Month Co...

Страница 4: ...ents please contact your dangerous goods adviser and or review the IATA website www iata org publications dgr Pages index aspx This is not intended to constitute legal advice and you should obtain your own professional advice Please contact Wavecom Instruments Pty Ltd for more information Competent Person To ensure that all electrical equipment or devices are inspected tested and tagged correctly ...

Страница 5: ... red and A N is green there is a fault with the Mains Supply You may also see more than one or all of these turn red For more information see Mains Supply Test Page 25 Battery LEDs The battery LED indicators display how much charge is remaining in your TnT RCD Use the table below for reference 100 Battery is fully charged 80 60 40 20 LED 2 will be flashing 0 LED 1 will be flashing TnT RCD Testing ...

Страница 6: ...s a FAIL Tag with a DANGER tag and remove the device from service TnT RCD Testing Menu Main Menu B Use the Enter button to switch between Menu A and Menu B All tests on Menu B require a Mains Power source Power Test Menu B F1 The Power Test is for the purposes of monitoring and performance of equipment The Power Test feature is for single phase appliances only The Power Test allows the user to tur...

Страница 7: ... IEC socket of the TnT RCD then clamp it onto earthed metal on the appliance 5 If testing an RCD plug the IEC 550 Orange Cable into the IEC socket of the TnT RCD then plug it into a socket on your RCD and turn that switch on 6 Navigate to Main Menu B then press F2 to enter the Leakage Test Menu cont 7 Press a function key to start the test F1 Earth Leakage limit set to MAX then 5mA fail F2 Double ...

Страница 8: ...Inspection For details refer to the First Test section If the device passed the Visual Inspection continue with the following instructions if not refer to the First Test section 2 Navigate to Main Menu B and press F3 to enter the RCD Menu then press F1 to select Time Test 3 Press F3 to enter the Time Test options menu to ensure your TnT RCD has the correct settings for the type of RCD cont 4 cont ...

Страница 9: ...plied to the equipment times the current drawn by the equipment Both Watt and VA ratings have a use and purpose The Watt rating determines the actual power purchased from the utility company and the heat loading generated by the equipment Disclaimer Meter Mode is to be used for quick simple indicative electrical parameter measurements Providing reasonably accurate readings without the need to carr...

Страница 10: ...ween the exposed conductive material metal and the TnT RCD appliance tester This is done by means of connecting the earth lead with the crocodile clip probe attached to a GOOD earth point paint coatings will not provide effective connections and the appliance plugged into the TnT RCD appliance testers test socket The Maximum allowable limit is less than 1 0Ω Class 2 Double Insulated Construction D...

Страница 11: ...d this The Supply Mains Test checks the polarity and connectivity of the mains supply by LED s This test is also a part of all the testing functions of this unit If the central N E light is on red and you need to conduct load leakage tests DO NOT CONTINUE If you are carrying out standard Insulation and Earth Bond tests it is generally safe to continue This light will glow if a voltage difference l...

Страница 12: ...but the most extreme environments Part no WCM TM TAGS B BLK BUR GN O R Y Super Heavy Duty TA Tags 100 Tags Suitable for all industrial and outdoor sites Part no WCM TA TAGS B BLK BUR GN O R Y Optional Accessories 500mm Metal Braid for Earthing Appliances Part No TnT ES 500 3 Phase Adaptor 20A 32A 5pin 5pin Part No WCM 3PH MADP HBC Fuse Part No WCM HBC10AM205 Isolation Transformer for RCD testing P...

Страница 13: ...asino Street Welshpool WA 6106 P 08 9353 1943 F 08 9353 4319 E saleswa wavecom com au Wavecom VIC Mark Kennedy M 0430 299 164 P 03 9897 4711 F 08 8243 3501 E service wavecom com au Sold By Date of Purchase Purchase Information Tester Serial Number The TnT RCD is proudly designed and manufactured in Australia by Wavecom ...

Отзывы: