TROUBLESHOOTING
Load will not turn ON:
• LED does not fl ash:
- Check the sensitivity for proper confi guration.
- Check all wire connections. Verify the ground wire is tightly secured.
• LED does fl ash:
- Press the ON/OFF button. If load does not turn ON, check all wire
connections and verify the load wire is tightly secured.
- Check the light level trimpot. Turn it fully clockwise
• If load still does not turn ON, call 800.879.8585 for technical support.
Load will not turn OFF:
• The time delay can be set for 30 seconds
(Walk Test), 5, 10, 15, 20, 25, or 30 minutes.
Ensure that the time delay is set to the
desired delay and that there is no movement
within the sensor’s view for that time period.
• To quickly test the unit for proper operation,
turn the time delay to minimum (fully
counterclockwise) and move out of the
sensor’s view. Load should turn OFF after 30
seconds.
• If load still does not turn OFF, call
800. 879.8585 for technical support.
Sensing motion outside desired area:
• Opaque adhesive tape is included with the sensor and can be used to limit
the detection areas. See Masking the Lens.
• Adjust sensitivity counterclockwise to reduce excessive sensitivity.
Call 800.879.8585 for Technical Support