Problem

Test Steps

Next

1

The LV switch does 

not control the relay 

or group.

Is it terminated correctly in the panel? 

See pages 4 & 8.

No – Correct terminations
Yes – Go to next step

Is the 12VDC indicating LED on the C8 

motherboard solid Green?

No – Cycle power to panel; recheck
Yes – Go to next step

Does the board mounted override 

pushbutton control the relay or group?

No – Call tech support
Yes – Go to next step

Disconnect input terminals. 

Does jumping the Red to White input 

terminals turn the relay on and does 

Black to White turn it off?

No – Call tech support
Yes - Verify the LV wiring is not 

shorted and that the switch is 

operating correctly

If using a Group switch, have the relays 

been assigned to the particular group 

using the GS card?

No – Make the necessary 

assignments (refer to page 9)
Yes – Go to next step

2

When I try to turn 

the relay off it goes 

off for a second then 

comes back on.

Is this relay scheduled using the “AS 

Manual ON/Auto OFF” or the “AS 

Automatic ON/OFF” scenarios.

No – Go to next Step
Yes – The relay can only be 

overridden OFF during unoccupied 

periods

Remove any LV switching that is landed 

at the relay input and attempt to turn 

relay ON using the board override 

buttons.

No change in status - Go to next 

step
Relay functions normally - Verify 

the LV wiring is not shorted 

and that the switch is operating 

correctly

Move LV relay connection to a different 

point on the RD board and attempt to 

override the relay on.

No change in status - relay needs 

to be replaced - call tech support
Relay functions properly – circuit 

board needs to be replaced - call 

tech support

3

When I try to turn 

the relay on it comes 

on for a second then 

comes back off.

Remove any LV switching that is landed 

at the relay input and attempt to turn 

relay ON using the board override 

buttons.

No change in status - Go to next 

step
Relay functions normally – Verify 

the LV wiring is not shorted 

and that the switch is operating 

correctly

Move LV relay connection to a different 

point on the RD board and attempt to 

override the relay on.

No change in status - relay needs 

to be replaced - call tech support
Relay functions properly – circuit 

board needs to be replaced - call 

tech support

TROUBLESHOOTING

10

Visit our web site for FAQs: www .wattstopper .com

Содержание LP Series

Страница 1: ...y 240VAC P115 347 Power Supply 115 or 347VAC Load Ratings 120VAC 50 60Hz 20A Tungsten or Ballast 277 347VAC 50 60Hz 20A Ballast 250VAC 1HP Accessory Power Ouput 800mA 24VDC VAC ACR Environmental Maximum Ambient Temperature 60 C Maximum Humidity 5 to 90 RH non condensing UL cUL Listed for receptacle rated circuit control Installation Wiring Reference ...

Страница 2: ...steps 9 CONTENTS SPECIFICATIONS 1 INTRODUCTION 3 Welcome to the LP Series Lighting Control Panels 3 System Wiring Overview 4 INSTALLATION 5 Mount the Enclosure 5 Install Interior 6 CONNECT THE LP8 POWER SUPPLY 7 Power Up and Test Relays 7 Confirm Nominal Operation 7 LOW VOLTAGE WIRING 8 Hardwire Low Voltage Switches Optional 8 Install and Wire Exterior Photocell Optional 9 Using Low Voltage Sensor...

Страница 3: ...2 contactors A secure outer cover protects the user from the high voltage area A separate interior enclosure protects the low voltage wiring and components while allowing easy user access to the time clock scheduling controls Most functions are the same for the LP24 as for the LP8 References to LP8 features functions programming and wiring also apply to the LP24 unless specified otherwise If you h...

Страница 4: ...24VR 24VAC WHITE RELAY PILOT Manual override switch for relays Factory installed jumper provides 24V rectified power to pilot contacts A different voltage 5 24V can be connected to the YELCOM terminal from other equipment looking to monitor relay state pilot contacts For standard use 3 18 Line Neutral To relay as rquired For standard use 2 18 For pilot use 3 18 Light fixture Light fixture Light fi...

Страница 5: ...urdy flat horizontal surface 2 Remove the outer cover by removing the cover screws Set it aside 3 Open the interior door containing the clock keypad and display window by pulling up the two black plastic self retained pop fasteners on the left side 4 Remove the panel interior assembly a Remove the washer and nut that attaches the transformer mounting assembly to the back of the enclosure b Remove ...

Страница 6: ...ltage wiring compartments Install Interior Do not reinstall the interior until after the exterior enclosure has been securely mounted to the wall and the conduit wiring holes have been drilled or knocked out 1 Place the interior in the enclosure 2 Align the interior with the studs provided in the enclosure 3 Hold the interior in place while you pull up on the black self retaining pop fasteners to ...

Страница 7: ...e voltage terminations of each relay 4 Apply power to the relays 5 Being careful not to touch any line voltage wiring toggle each relay on off again and confirm that each relay con trols the appropriate load Confirm Nominal Operation With power applied to the LP8 panel there should be two 2 green LED indicators glowing on the power supply card in the lower left corner of the panel And there should...

Страница 8: ...sensor wiring R B Y W 2 WIRE MAINTAINED CONTACT R to B JUMPER B to W JUMPER 2 WIRE MOMENTARY PUSH BUTTON STANDARD 3 WIRE MOMENTARY STANDARD 3 WIRE MAINTAINED R B Y W RED WHITE RED WHITE BLACK WHITE RED BLACK WHITE RED R B Y W R B Y W R B Y W OCCUPANCY SENSOR or INDOOR PHOTOCELL BLACK BLUE RED Blue Black Red White 24VDC 24VR 24VAC COMMON CONTROL 24VDC R B Y W COMBINATION OF 2 WIRE MOMENTARY PUSHBUT...

Страница 9: ...ing card press and hold the Group push button for several seconds The red group LED and the LEDs for relays currently controlled by that input will begin to flash 2 On each Relay Driver card select the relays to be controlled If a relay was previously Smartwired to the group input selected the LED flashes otherwise the LED is off Press the associated Relay Control Button to add delete that relay t...

Страница 10: ... can only be overridden OFF during unoccupied periods Remove any LV switching that is landed at the relay input and attempt to turn relay ON using the board override buttons No change in status Go to next step Relay functions normally Verify the LV wiring is not shorted and that the switch is operating correctly Move LV relay connection to a different point on the RD board and attempt to override ...

Страница 11: ...o next step Is Daylight Savings set up correctly for the panel s location No make the necessary changes and test again Yes Call tech support 6 I go to enter my on and off times and I get the You are attempting to enter a ON OPEN time that happens after the OFF Close time Please correct before moving on Error message Are you entering ON OFF times using the 24 hour format No Using the 24 hour format...

Страница 12: ...A2 Low voltage exterior photocell AS 100 Automatic control switch 120 277VAC 50 60Hz LVS 1 Standard momentary toggle switch RS2 3x Two button low voltage momentary switch L1S Single button low voltage architectural design toggle switch LxS Multi button low voltage architectural design toggle switch DCC2 Low voltage momentary switch Miro Decorator style with LED Multiple options available such as c...

Отзывы: