OCCUPANCY LOGIC
The DT-355 has 6 logic configurations for
occupancy triggers, set with DIP switches 1,
2 & 3. Determine the appropriate Occupancy
Logic Option using the Trigger matrix, then set
the DIP switches accordingly.
Initial Occupancy:
The method that activates a
change from “Standby” (area unoccupied and
loads are off) to “Occupied” (area occupied and
loads are on).
• Both
requires motion detection by the PIR
and the Ultrasonic.
• Either
requires motion detection by only one
technology.
• PIR
requires motion detection by the PIR.
• Ultra
requires motion detection by the
Ultrasonic.
Maintain Occupancy:
The method indicating
that the area is still occupied and the lights
should remain on.
Re-trigger:
After the time delay elapses and
the lights turn off, detection by the selected
technology within the number of seconds
indicated turns the lights back on.
Logic Configuration Chart
8
Minimum
Max./SmartSet
PIR Sensitivity
5 sec/SmartSet
10 min.
10 minutes
15 min.
15 minutes
20 minutes
30 min.
5 minutes
4 5 6
Time Delay
= walk-through mode
LEDs
Disabled
Enabled
7
= ON
– = OFF
Standard
Option 2
Option 3
Option 1
1 2 3
Option 4
Option 5
Logic
Switch#
Occupancy
Standard
Option 2
Option 3
Option 1
Trigger
Option 4
Option 5
Initial
Occupancy
Maintain Occupancy Re-trigger (seconds duration)
O
ccupancy Logic
Both
Both Both Both(5)
Either(n/a)
Either
Either
Either
Either
Either(n/a)
Either(n/a)
PIR
PIR
PIR
PIR
(5)
Ultra(5)
Ultra Ultra
= Factory Setting
Visit our website for FAQs: www.wattstopper.com