3.1.5 Water floor heating and cooling (multi zones).

 Equipments:

 

  • 2 Connecting boxes BT-M6Z02 RF

 

  • 2 (or more) Thermostats BT-D02 RF (or BT-A02 RF, BT-DP02 RF, 

 

     BT-D02 RH RF) **

 

  • 1 Connecting box BT-HCM02 RF to drive the heating or cooling mode

 

  • 1 Central Unit BT-CT02 RF

 

For a correct installation, refer to dedicated user guides of each product, then:

WIRING CONNECTION:

•  Connect the actuators (eg. 22C – 22CX series) to the connecting box BT-M6Z02 RF
•  Connect the circulating pumps to the related connecting box BT-M6Z02 RF (*)
•  Connect the Hot/Cool Module to the load (eg. A/C system) and to the heating relay 

of the boiler

VIRTUAL – RF CONNECTION:

1-2  Pair each thermostat to each zone of the BT-M6Z02 RF. 

 

  One thermostat can drive several zones. 

  3  Pair the BT-HCM02 RF to the BT-M6Z02 RF.
    Note – Only one Hot/Cool module BT-HCM02 RF per System (**).
  4  Pair in master mode each BT-M6Z02 RF to the Central Unit BT-CT02 RF. 
    Name the virtual rooms in the BT-CT02 RF and select the hydraulic circuit.

1

st

 floor

Ground floor

**) In application with humidity drier (for system limitation ref. to pag. 33) connect it to the output of Hot/Cool 

module for triggering it on/off and managing relative humidity (%). In this case it is necessary to install at 

least 1 thermostat BT-D02 RF with Humidity Sensor and locate it in a central area of the installation.

* )  In this application each BT-M6Z02 RF is connected to a circulating pump. 

DIP SWITCH #1 Configuration: 

OFF = LOCAL

. In case of an installation with more than one BT-M6Z02 RF connecting box and only 1 

circulating pump, 

DIP SWITCH #1 Configuration: ON = GLOBAL

 on the BT-M6Z02 RF that drives the 

circulating pump (= BT-M6Z02 Master).

 

 

 

 

17 

 

 

WIRING CONNECTION:

  

Connect the actuators (eg. 22C – 22CX series) to the connecting box BT-M6Z02 RF 

Connect the circulating pumps to the related connecting box BT-M6Z02 RF 

(*)

 

Connect the Hot/Cool Module to the load (eg. A/C system) and to the heating relay 
boiler 

 
VIRTUAL – RF CONNECTION: 

1-2 

Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive 
several zones.  

3

  

Pair the BT-HCM02 RF to the BT-M6Z02 RF. 
NOTE – Only one Hot/Cool module BT-HCM02 RF per System 

(**)

4

  

Pair in master mode each BT-M6Z02 RF to the Central Unit BT-CT02 RF.  
Name the virtual rooms in the BT-CT02 RF and select the hydraulic circuit. 

  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 

*

  In this application each BT-M6Z02 RF is 

connected to a circulating pump. 

DIP SWITCH #1 Configuration: OFF = LOCAL. 

 
In case of an installation with more than one 
BT-M6Z02 RF connecting box and only 1 
circulating pump,  

DIP SWITCH #1 Configuration: ON = GLOBAL 

on the BT-M6Z02 RF that drives the circulating 
pump (= BT-M6Z02 Master).

 

**

 In application with humidity drier (for system limitation ref. to pag. 34) connect it to the output of Hot/Cool module for 

triggering it on/off and managing relative humidity (%). In this case it is necessary to install at least 1 thermostat BT-D02 RF 
with Humidity Sensor and locate it in a central area of the installation. 

  

     

 

 

 

 

 

 

 

 

 

 

 

17 

 

 

WIRING CONNECTION:

  

Connect the actuators (eg. 22C – 22CX series) to the connecting box BT-M6Z02 RF 

Connect the circulating pumps to the related connecting box BT-M6Z02 RF 

(*)

 

Connect the Hot/Cool Module to the load (eg. A/C system) and to the heating relay 
boiler 

 
VIRTUAL – RF CONNECTION: 

1-2 

Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive 
several zones.  

3

  

Pair the BT-HCM02 RF to the BT-M6Z02 RF. 
NOTE – Only one Hot/Cool module BT-HCM02 RF per System 

(**)

4

  

Pair in master mode each BT-M6Z02 RF to the Central Unit BT-CT02 RF.  
Name the virtual rooms in the BT-CT02 RF and select the hydraulic circuit. 

  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 

*

  In this application each BT-M6Z02 RF is 

connected to a circulating pump. 

DIP SWITCH #1 Configuration: OFF = LOCAL. 

 
In case of an installation with more than one 
BT-M6Z02 RF connecting box and only 1 
circulating pump,  

DIP SWITCH #1 Configuration: ON = GLOBAL 

on the BT-M6Z02 RF that drives the circulating 
pump (= BT-M6Z02 Master).

 

**

 In application with humidity drier (for system limitation ref. to pag. 34) connect it to the output of Hot/Cool module for 

triggering it on/off and managing relative humidity (%). In this case it is necessary to install at least 1 thermostat BT-D02 RF 
with Humidity Sensor and locate it in a central area of the installation. 

  

     

 

 

 

 

 

 

 

 

 

 

 

17 

 

 

WIRING CONNECTION:

  

Connect the actuators (eg. 22C – 22CX series) to the connecting box BT-M6Z02 RF 

Connect the circulating pumps to the related connecting box BT-M6Z02 RF 

(*)

 

Connect the Hot/Cool Module to the load (eg. A/C system) and to the heating relay 
boiler 

 
VIRTUAL – RF CONNECTION: 

1-2 

Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive 
several zones.  

3

  

Pair the BT-HCM02 RF to the BT-M6Z02 RF. 
NOTE – Only one Hot/Cool module BT-HCM02 RF per System 

(**)

4

  

Pair in master mode each BT-M6Z02 RF to the Central Unit BT-CT02 RF.  
Name the virtual rooms in the BT-CT02 RF and select the hydraulic circuit. 

  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 

*

  In this application each BT-M6Z02 RF is 

connected to a circulating pump. 

DIP SWITCH #1 Configuration: OFF = LOCAL. 

 
In case of an installation with more than one 
BT-M6Z02 RF connecting box and only 1 
circulating pump,  

DIP SWITCH #1 Configuration: ON = GLOBAL 

on the BT-M6Z02 RF that drives the circulating 
pump (= BT-M6Z02 Master).

 

**

 In application with humidity drier (for system limitation ref. to pag. 34) connect it to the output of Hot/Cool module for 

triggering it on/off and managing relative humidity (%). In this case it is necessary to install at least 1 thermostat BT-D02 RF 
with Humidity Sensor and locate it in a central area of the installation. 

  

     

 

 

 

 

 

 

 

 

 

 

 

17 

 

 

WIRING CONNECTION:

  

Connect the actuators (eg. 22C – 22CX series) to the connecting box BT-M6Z02 RF 

Connect the circulating pumps to the related connecting box BT-M6Z02 RF 

(*)

 

Connect the Hot/Cool Module to the load (eg. A/C system) and to the heating relay 
boiler 

 
VIRTUAL – RF CONNECTION: 

1-2 

Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive 
several zones.  

3

  

Pair the BT-HCM02 RF to the BT-M6Z02 RF. 
NOTE – Only one Hot/Cool module BT-HCM02 RF per System 

(**)

4

  

Pair in master mode each BT-M6Z02 RF to the Central Unit BT-CT02 RF.  
Name the virtual rooms in the BT-CT02 RF and select the hydraulic circuit. 

  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 

*

  In this application each BT-M6Z02 RF is 

connected to a circulating pump. 

DIP SWITCH #1 Configuration: OFF = LOCAL. 

 
In case of an installation with more than one 
BT-M6Z02 RF connecting box and only 1 
circulating pump,  

DIP SWITCH #1 Configuration: ON = GLOBAL 

on the BT-M6Z02 RF that drives the circulating 
pump (= BT-M6Z02 Master).

 

**

 In application with humidity drier (for system limitation ref. to pag. 34) connect it to the output of Hot/Cool module for 

triggering it on/off and managing relative humidity (%). In this case it is necessary to install at least 1 thermostat BT-D02 RF 
with Humidity Sensor and locate it in a central area of the installation. 

  

     

 

 

 

 

 

 

 

BT-D02 RF

BT-D02 RF

UP TO SIX

BT-M6Z02 RF

BT-HCM02 RT

BT-CT02 RF

BT-M6Z02 RF

UP TO SIX

BT-M6Z02 RF

Содержание Vision BT-A02 RF

Страница 1: ...WattsIndustries com Description and application guide...

Страница 2: ...1 Hydraulic Systems with Central Unit 6 3 1 1 A thermostat mono zone managing a boiler or a heat pump 6 3 1 2 Water floor heating mono zone managing hydraulic circuit and a boiler 8 3 1 3 Hydraulic r...

Страница 3: ...Name Descriptive Applications Possible pairing BT S6Z02 RF 6 zones extension module for Hydraulic heating and cooling BT A02RF BT M6Z02 RF Water floor heating and cooling BT D02 RF BT DP02 RF BT HCM0...

Страница 4: ...eat pump VIRTUAL RF CONNECTION Create a virtual room on Central Unit BT CT02 RF Pair as Heating Device the thermostat to the Central Unit BT CT02 RF Pair in heating mode the receiver BT WR02 HC RF to...

Страница 5: ...e several receivers in the same zone We can create several zones in the Central Unit It is possible to link each receiver to a specific hydraulic circuit managing its pump by the Central Unit BT CT02...

Страница 6: ...draulic circuit Devices configuration go in the zone select the information menu select the receiver and the hydraulic type then the hydraulic circuit refer to HYDRAULIC SYSTEM PAIRING chapter on Cent...

Страница 7: ...vices configuration go in the zone select the information menu select the receiver and the hydraulic type then the hydraulic circuit refer to HYDRAULIC SYSTEM PAIRING chapter on Central Unit user guid...

Страница 8: ...triggering it on off and managing relative humidity In this case it is necessary to install at least 1 thermostat BT D02 RF with Humidity Sensor and locate it in a central area of the installation WI...

Страница 9: ...lation refer to dedicated user guides of each product then WIRING CONNECTION Connect the receiver BT WR02 HC RF to the heating relay of boiler or heat pump VIRTUAL RF CONNECTION Pair the thermostat to...

Страница 10: ...F to the heating relay of the boiler VIRTUAL RF CONNECTION 1 Pair each thermostat to each zone of the BT M6Z02 RF One thermostat can drive several zones BT D02 RF UP TO SIX BT M6Z02 RF 21 For a correc...

Страница 11: ...nect the actuators eg 22C 22CX series to the c Connect the circulating pumps to the related connect Connect both connecting boxes BT M6Z02 RF to the h VIRTUAL RF CONNECTION 1 2 Pair each thermostat to...

Страница 12: ...ative humidity In this case it is necessary to install at least 1 thermostat BT D02 RF with Humidity Sensor and locate it in a central area of the installation Note one humidity drier per System refer...

Страница 13: ...ing device in each virtual room in the Central Unit BT CT02 RF 2 3 4 Pair each receiver in each virtual room of the Central Unit BT CT02 RF as a Heating device and select electrical heating mode in th...

Страница 14: ...l device VIRTUAL RF CONNECTION 1 Pair the thermostat to the receiver 2 3 4 In case of several receivers e linked to the same thermostat make again the operation above for each receiver 29 For a correc...

Страница 15: ...hermostat can drive several zones 2 Pair in master mode each BT M6Z02 RF to the BT CT02 RF Name the virtual rooms in the BT CT02 RF and select the hydraulic circuit Devices configuration go in the zon...

Страница 16: ...mostats BT D02 RF or BT A02 RF BT DP02 RF BT D02 RH RF BT DP02 RH RF Central Unit BT CT02 RF Receivers BT WR02 HC RF to control the boiler Receivers BT WR02 RF or BT FR02 RF to control the pumps if ne...

Страница 17: ...4 Option Pair a thermostat in each virtual room created in the BT CT02 RF containing a radiator 5 Pair each BT TH02 RF in each virtual room created in the BT CT02 RF by selecting the hydraulic circuit...

Страница 18: ...private server Wifi central unit and Rooms do not appear in the application 1 Check Wifi connection on the central Status 2 2 is required application 2 Check that you have the last sofware on the cen...

Страница 19: ...assono MB Italia Tel 39 039 49 86 1 Fax 39 039 49 86 222 Sede legale Frazione Gardolo Via Vienna 3 38121 Trento TN Italia Cod Fisc 00743720153 Partita IVA n IT 01742290214 Societ unipersonale del grup...

Отзывы: