System limitations

 

 

•  Only one Hot-Cool module BT-HCM02 RF per System – 1 output only 

for humidity drier 

 

•  4 hydraulic circuits per System

 

•  Only zones containing only electrical heaters can do heating when the 

System is in cooling mode

 

•  Mix different modes of heating in the same room is not recommended 

as the regulations embedded in each receiver are not synchronized

 

•  With a Central Unit BT-CT02 RF, it is highly recommended to use devic

-

es paired in hydraulic circuit directly on the BT-CT02 RF. Output usage 
of BT-M6Z02 RF and BT-HCM02 RF is only possible on small System 
(Only 1 BT-M6Z02 RF and 1 BT-HCM02 RF)

BT-CT02 RF software update

 

On www.wattswater.eu homepage, you can find files allowing updating the 

software of the Central Unit BT-CT02 RF. The procedure should be performed while 
the BT-CT02 RF is plugged to the 230V wall support.
 

•  Unzip in a microSD  the 3 files (wifi.ini, wifi.hex, update.bin) 

 

•  Insert the microSD

 

•  Press on Update Firmware in the installation menu

 

•  Wait the end of the software Update procedure and wait at least 1mn 

before removing the microSD

Configuration of the remote control 

of the central

   

Except the installation configuration, all the functions of the Central Unit are 

available on:

 

•  The web site www.wattswater.eu

 

•  On Watts Vision application available on Apple store (iOS)

 

•  On Watts Vision application available on Play store (Android)

The remote control configuration should be performed in 3 steps after configuration 
of you heating and cooling system.

 

1 Connect the central to a wifi router. Menu Installation/wifi. The connec

-

tion can be manual or automatic. When the wifi connection succeeds, 

the wifi menu displays 1/2 status and a green flag.

 

2 From the web site or the application, create an account with your email 

and a password

 

3 Link your central to your account. In the application, request the send

-

ing of a pairing code on your mail box. Enter the code in the wifi menu.

 

4 After a few minutes, your central should be displayed in the application. 

The wifi menu of the central should display 2/2 status.

More detailed explanation available on BT-CT02 RF dedicated user guide.

  

Devices configuration

: go in the zone, select the information menu, 

select the receiver and the hydraulic type, then the hydraulic circuit 

(refer to HYDRAULIC SYSTEM PAIRING chapter on Central Unit 

user guide). 

 

3  Option: Pair the BT-WR02 RF receiver to the BT-M6Z02 RF as a 

slave link. 

Zone 2

   4  Option: Pair a thermostat in each virtual room created in the BT-

CT02 RF containing a radiator

 

5  Pair each BT-TH02 RF in each virtual room created in the BT-CT02 

RF by selecting the hydraulic circuit. We can pair several BT-TH02 
RF in the same room

  

Devices configuration

: go in the zone, select the information 

menu, select the receiver and the hydraulic type, then the hydraulic 

circuit (refer to HYDRAULIC SYSTEM PAIRING chapter on Central 
Unit user guide). 

Main Circuit

 

6  Pair the BT-WR02 HC RF receiver to the BT-CT02 RF as a hydraulic 

circuit then select the hydraulic circuit.

Zone 3

  7  Pair thermostat in virtual room in the Central Unit BT-CT02 RF

 

8  Pair each receiver in each virtual room of the Central Unit BT-CT02 

RF by selecting the electrical device.

 

 

 

 

33 

 

For a correct installation, refer to dedicated user guides of each product, then: 

 

WIRING CONNECTION:

  

Connect BT-M6Z02 RF to the actuators (eg. 22C – 22CX series)  

Connect the circulating pump to the connecting box BT-M6Z02 RF 

(*) 

Connect the receivers BT-WR HC02 RF to the heating relay of the boiler

 

Connect the receivers BT-WR 02 RF (or BT-FR02 RF) to electrical heaters and to the 
pump (if needed – option)

 

 

VIRTUAL – RF CONNECTION: 

Zone 1  

1. 

Pair each thermostat to each zone of the BT-M6Z02 RF. One thermostat can drive several zones. 

2. 

Pair in master mode each BT-M6Z02 RF to the Central Unit BT-CT02 RF. Name the virtual rooms 
in the BT-CT02 RF and select the hydraulic circuit 

 

Devices configuration: 

go in the zone, select the information menu, select the receiver and the 

hydraulic type,  then the hydraulic circuit (refer to HYDRAULIC SYSTEM PAIRING chapter on 
Central Unit user guide).

  

3. 

Option: Pair the BT-WR02 RF receiver to the BT-M6Z02 RF as a slave link.  

Zone 2  

4. 

Option: Pair a thermostat in each virtual room created in the BT-CT02 RF containing a radiator 

5. 

Pair each BT-TH02 RF in each virtual room created in the BT-CT02 RF by selecting the hydraulic 
circuit. We can pair several BT-TH02 RF in the same room 

Devices configuration: 

go in the zone, select the information menu, select the receiver and the 

hydraulic type,  then the hydraulic circuit (refer to HYDRAULIC SYSTEM PAIRING chapter on 
Central Unit user guide).

  

Main Circuit

 

6. 

Pair the BT-WR02 HC RF receiver to the BT-CT02 RF as a hydraulic circuit then select the hydraulic 
circuit. 

Zone 3 

7.

 

Pair thermostat in virtual room in the Central Unit BT-CT02 RF 

8. 

Pair each receiver in each virtual room of the Central Unit BT-CT02 RF by selecting the electrical 
device.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Option 

*

 

DIP SWITCH #1  

Configuration : 
OFF = LOCAL 

*   DIP SWITCH #1  Configuration : OFF = LOCAL

BT-WR02 HC RF

BT-WR02 HC RF

BT-WR02 HC RF

Содержание Vision BT-A02 RF

Страница 1: ...WattsIndustries com Description and application guide...

Страница 2: ...1 Hydraulic Systems with Central Unit 6 3 1 1 A thermostat mono zone managing a boiler or a heat pump 6 3 1 2 Water floor heating mono zone managing hydraulic circuit and a boiler 8 3 1 3 Hydraulic r...

Страница 3: ...Name Descriptive Applications Possible pairing BT S6Z02 RF 6 zones extension module for Hydraulic heating and cooling BT A02RF BT M6Z02 RF Water floor heating and cooling BT D02 RF BT DP02 RF BT HCM0...

Страница 4: ...eat pump VIRTUAL RF CONNECTION Create a virtual room on Central Unit BT CT02 RF Pair as Heating Device the thermostat to the Central Unit BT CT02 RF Pair in heating mode the receiver BT WR02 HC RF to...

Страница 5: ...e several receivers in the same zone We can create several zones in the Central Unit It is possible to link each receiver to a specific hydraulic circuit managing its pump by the Central Unit BT CT02...

Страница 6: ...draulic circuit Devices configuration go in the zone select the information menu select the receiver and the hydraulic type then the hydraulic circuit refer to HYDRAULIC SYSTEM PAIRING chapter on Cent...

Страница 7: ...vices configuration go in the zone select the information menu select the receiver and the hydraulic type then the hydraulic circuit refer to HYDRAULIC SYSTEM PAIRING chapter on Central Unit user guid...

Страница 8: ...triggering it on off and managing relative humidity In this case it is necessary to install at least 1 thermostat BT D02 RF with Humidity Sensor and locate it in a central area of the installation WI...

Страница 9: ...lation refer to dedicated user guides of each product then WIRING CONNECTION Connect the receiver BT WR02 HC RF to the heating relay of boiler or heat pump VIRTUAL RF CONNECTION Pair the thermostat to...

Страница 10: ...F to the heating relay of the boiler VIRTUAL RF CONNECTION 1 Pair each thermostat to each zone of the BT M6Z02 RF One thermostat can drive several zones BT D02 RF UP TO SIX BT M6Z02 RF 21 For a correc...

Страница 11: ...nect the actuators eg 22C 22CX series to the c Connect the circulating pumps to the related connect Connect both connecting boxes BT M6Z02 RF to the h VIRTUAL RF CONNECTION 1 2 Pair each thermostat to...

Страница 12: ...ative humidity In this case it is necessary to install at least 1 thermostat BT D02 RF with Humidity Sensor and locate it in a central area of the installation Note one humidity drier per System refer...

Страница 13: ...ing device in each virtual room in the Central Unit BT CT02 RF 2 3 4 Pair each receiver in each virtual room of the Central Unit BT CT02 RF as a Heating device and select electrical heating mode in th...

Страница 14: ...l device VIRTUAL RF CONNECTION 1 Pair the thermostat to the receiver 2 3 4 In case of several receivers e linked to the same thermostat make again the operation above for each receiver 29 For a correc...

Страница 15: ...hermostat can drive several zones 2 Pair in master mode each BT M6Z02 RF to the BT CT02 RF Name the virtual rooms in the BT CT02 RF and select the hydraulic circuit Devices configuration go in the zon...

Страница 16: ...mostats BT D02 RF or BT A02 RF BT DP02 RF BT D02 RH RF BT DP02 RH RF Central Unit BT CT02 RF Receivers BT WR02 HC RF to control the boiler Receivers BT WR02 RF or BT FR02 RF to control the pumps if ne...

Страница 17: ...4 Option Pair a thermostat in each virtual room created in the BT CT02 RF containing a radiator 5 Pair each BT TH02 RF in each virtual room created in the BT CT02 RF by selecting the hydraulic circuit...

Страница 18: ...private server Wifi central unit and Rooms do not appear in the application 1 Check Wifi connection on the central Status 2 2 is required application 2 Check that you have the last sofware on the cen...

Страница 19: ...assono MB Italia Tel 39 039 49 86 1 Fax 39 039 49 86 222 Sede legale Frazione Gardolo Via Vienna 3 38121 Trento TN Italia Cod Fisc 00743720153 Partita IVA n IT 01742290214 Societ unipersonale del grup...

Отзывы: