5
Depress the two snaps
on the bottom of the
enclosure to release the
front cover.
Secure enclosure using four #6 or #8
wood screws.
Install the front cover by
hooking the top catches
and pivoting the cover
into place.
Installing the Enclosure
Installation Using Mount Holes and Screws
Mounting Screw
Snap the enclosure onto
35mm DIN rail using the
hooks and snaps on the
back of the enclosure.
Location of DIN rail hooks
and snaps on the back of
the enclosure.
Latch top hooks of
enclosure onto DIN rail.
Then rotate enclosure
down engaging bottom
snaps.
Enclosure mounted on
DIN rail (back view).
Low-Voltage Wiring
Pull two conductor 18 AWG cable, up to 500 feet
(150 m) long, for the following equipment:
• Outdoor temperature sensor (Optional)
Pull four solid conductor 18 AWG cable, up to 500 feet
(150 m) long, for the following equipment:
• Snow Sensor 095
Pull five solid conductor 18 AWG cable, up to 435 feet
(132 m) long, for the following equipment:
• Snow / Ice Sensor 090
Rough-In Wiring
To prevent the risk of personal injury and/or death, make sure power is not
applied to the interface until it is fully installed and ready for final testing . All work
must be done with power to the circuit being worked on turned off .
Please be aware local codes may require this interface to be installed or
connected by an electrician .
DIN Rail Mounting