14
BACnet Menu
Description
Range
Default
Access
DEVICE ID
Select the BACnet device number identification .
0 to 4194302
1
Installer
ADDRESS
Set the BACnet MS/TP MAC address .
0 to 127
60
Installer
BAUD RATE
Select the BACnet-MSTP data communication rate .
Higher data rates may restrict cable length and may
require terminating resistors at the end of the RS-485
data bus .
2400, 9600,
19k2, 38k4,
57k6, 76k8,
115k
76800
Installer
Sensors Menu
Description
Range
Default
Access
SNOW/ICE
Select if a Snow/Ice Sensor 090 “In-slab” or a
Snow Sensor 095 “Aerial” is installed .
In-Slab
Aerial
In-Slab
Installer
OUTDOOR
Current outdoor air temperature . Select if the outdoor
air temperature is measured by the outdoor local
sensor or provided by the BAS .
Local
BAS
BAS
Installer
SLAB
Current slab sensor temperature . The slab sensor is only
available when the Aerial Snow Sensor 095 is installed .
On, Off
On
Installer