The WiFi Thermostat 562 operates a first stage baseboard/radiator and a second stage 

fan coil for heating, and an air conditioner for cooling.

C
R

AWAY

W

Rh1

W1

Rh2

W2

Rc
Y1

G

C
R

AWAY

S1
S2

SEN

COM

C
R

W

G

Y

X
X

C

Vlv

Air

Handling

Unit

Terminals

V2

B1

WiFi Thermostat 562

S1

S2

ZVC1

Legend

B1 = Boiler

BP = Boiler Pump

C1 = Air Conditioner

F1 = Fan Coil

PS = System Pump

S1 = Optional Floor Sensor 079

S2 = Optional Indoor Sensor 084

T1 = WiFi Thermostat 562

V1 = Radiant Zone Valve

V2 = Fan Coil Zone Valve

ZVC1 = Zone Valve Control 304V, 306V

C1

F1

B1

T1

S1

V1

V2

ZVC1

BP

PS

C
R

AWAY

S1
S2

J1 J2 J3

RELAY

POWER

JUMPER

ON

OFF

SEN

COM

Rh1

Rh2
W2

W1

Rc

J1

R

Y1
G

R

J2

J3

R

Thermostat

jumpers:

J1 = On

J2 = Off

J3 = Off

Application 562-4

Mechanical

Electrical

Содержание tekmar 562

Страница 1: ...tions IOM T 562 Installation Operation and Maintenance WiFi Thermostat 562 WARNING Please read carefully before proceeding with installation Your failure to follow any attached instructions or operating parameters may lead to the product s failure Keep this Manual for future reference Works with the Watts Home Mobile App ...

Страница 2: ...pplication 562 4 9 Sequence of Operation 10 Heating Operation 10 Cooling Operation 10 User Interface 11 User Settings 12 Away 12 Schedule 12 Display 13 Time 14 Fan 14 WiFi 15 WiFi and Connectivity Troubleshooting 16 Installer Settings 17 Setup 17 Setup Toolbox 17 Setup Temp 18 Setup Sensors 19 Setup Alerts 19 Setup Relays 20 Error Messages 21 Technical Data 22 Limited Warranty and Product Return P...

Страница 3: ...in minor or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read Manual and all product labels BEFORE using the equipment Do not use unless you know the safe and proper operation of this equipment Keep this Manual available for easy access by all users Replacement Manuals are available at tekmarControls com...

Страница 4: ...ond 32 122 F 0 50 C No draft direct sun or other cause for inaccurate temperature readings Away from equipment appliances or other sources of electrical interference Easy access for wiring viewing and adjusting the display screen Approximately 5 feet 1 5 m off the finished floor The maximum length of wire is 500 feet 150 m Strip wire to 3 8 10 mm for all terminal connections Use standard 8 conduct...

Страница 5: ...l Stud Thermostat Front Thermostat Base C R AWAY S1 S2 J1 J2 J3 RELAY POWER JUMPER ON OFF SEN COM Rh1 Rh2 W2 W1 Rc J1 R Y1 G R J2 J3 R C R AWAY S1 S2 J1 J2 J3 RELAY POWER JUMPER ON OFF SEN COM Rh1 Rh2 W2 W1 Rc J1 R Y1 G R J2 J3 R The thermostat includes three relay power jumper connectors located below the wiring hole Set Jumper J1 to On to connect power R to the Rh1 terminal Set Jumper J2 to On t...

Страница 6: ...rmostat 562 C1 WiFi Thermostat 562 F1 T1 The WiFi Thermostat 562 operates a one or two stage furnace for heating and an air conditioner for cooling Furnace Terminals C R AWAY S1 S2 J1 J2 J3 RELAY POWER JUMPER ON OFF SEN COM Rh1 Rh2 W2 W1 Rc J1 R Y1 G R J2 J3 R Thermostat jumpers J1 On J2 On J3 On Application 562 1 Mechanical Electrical ...

Страница 7: ... and an air conditioner for cooling C1 WiFi Thermostat 562 F1 B1 T1 S1 S1 S2 S2 V1 ZVC1 ZVC1 BP PS F1 Furnace PS System Pump T1 WiFi Thermostat 562 V1 Zone Valve S1 Optional Floor Sensor 079 S2 Optional Indoor Sensor 084 ZVC1 Zone Valve Control 304V 306V Furnace Terminals C R AWAY S1 S2 J1 J2 J3 RELAY POWER JUMPER ON OFF SEN COM Rh1 Rh2 W2 W1 Rc J1 R Y1 G R J2 J3 R Thermostat jumpers J1 On J2 Off ...

Страница 8: ...iFi Thermostat 562 S1 S2 ZVC1 Legend B1 Boiler BP Boiler Pump C1 Air Conditioner F1 Fan Coil PS System Pump S1 Optional Floor Sensor 079 S2 Optional Indoor Sensor 084 T1 WiFi Thermostat 562 V1 Radiant Zone Valve V2 Fan Coil Zone Valve ZVC1 Zone Valve Control 304V 306V C1 F1 B1 T1 S1 S2 V1 V2 ZVC1 BP PS C R AWAY S1 S2 J1 J2 J3 RELAY POWER JUMPER ON OFF SEN COM Rh1 Rh2 W2 W1 Rc J1 R Y1 G R J2 J3 R T...

Страница 9: ...B1 WiFi Thermostat 562 S1 S2 ZVC1 Legend B1 Boiler BP Boiler Pump C1 Air Conditioner F1 Fan Coil PS System Pump S1 Optional Floor Sensor 079 S2 Optional Indoor Sensor 084 T1 WiFi Thermostat 562 V1 Radiant Zone Valve V2 Fan Coil Zone Valve ZVC1 Zone Valve Control 304V 306V C1 F1 B1 T1 S1 V1 V2 ZVC1 BP PS C R AWAY S1 S2 J1 J2 J3 RELAY POWER JUMPER ON OFF SEN COM Rh1 Rh2 W2 W1 Rc J1 R Y1 G R J2 J3 R ...

Страница 10: ...bination of air and floor temperature control leave the internal air sensor on in the setup menu A floor minimum can be used to prevent a fast drop in temperature caused by receding solar exposure This operation is recommended for areas heated by afternoon sun through largewindows Whenthesunsets itcantakealongtimeforthefloorstogetwarmagain This maycausetheroomtocoolofftoomuchintheearlyevening Aflo...

Страница 11: ... temperature to the current schedule event Go to settings Swipe to view Weather Outdoor temperature Floor temperature Heat To setting Cool To setting Go to schedule After 60 seconds of inactivity the thermostat home screen displays only the time and the temperature Save Cancel Mode Heat Cool Auto Heat Cool Off Temperature Adjustment Hold Until 5 00 PM Save to Schedule 70 Heat To 75 Cool To MENU SE...

Страница 12: ...ll devices linked to that location through the app Save Info Home Away At Home Away Heating temperature Go to the next group of program days Current group of program days Early Start anticipates the time required to heat or cool a room and starts early Set to On to follow the schedule Set to Off to use the same temperature all of the time Creates a new schedule Cooling temperature New Schedule Ear...

Страница 13: ...rs 0 hrs Sat 0 hrs 0 hrs Fri 0 hrs 0 hrs View each day s run time for both heating and cooling Toggle between Daily and Monthly Usage Energy Use Setting Range Default BRIGHTNESS ACTIVE Select the brightness when touching the screen 30 to 100 100 BRIGHTNESS INACTIVE Select the brightness when not in use Off 30 to 100 50 BACKGROUND Select the background color White Blue Black Latte Espresso Blue LAN...

Страница 14: ...net the time can be set automatically The time and date can be manually set by highlighting a field and then using the or buttons Choose from the time options listed below Incorrectly setting the time and date manually may prevent the thermostat from communicating to the mobile app Automatic time source is recommended when using an Internet connection The fan is normally off when set to auto but t...

Страница 15: ...pt the Terms of Use as amended from time to time and available at Watts com terms of use If you do not accept these terms this product can still be used without WiFi features Tutorial DISAGREE AGREE Before first using WiFi features of this product you must accept the Terms of Use available at https www watts com terms of use by pressing AGREE below Ifyoudonotaccepttheseterms this product can still...

Страница 16: ...ualorInternetService Provider ISP for assistance with router setup with these configurations The router must provide a 2 4 GHz signal The thermostat is not compatible with 5 GHz networks The router is using WPA2 Personal security The router has DHCP enabled with enough available addresses for all Internet devices The router firewall is not blocking the outbound UDP or TCP ports 53 123 443 8883 The...

Страница 17: ...ct between user and installer access levels User access level restricts access in the Setup Menu User Installer Installer STATUS The current status of warm weather shut down cold weather shut down and each of the relays WWSD CWSD W1 W2 Y1 G1 N A SOFTWARE VERSION Display the software version J1255A N A LOAD DEFAULTS All settings are returned to factory defaults Yes No No CALIBRATE TOUCHSCREEN Recal...

Страница 18: ...ngisshutoff Off 40 to 95 F Off 4 5 to 35 0 C Off Screen Page 3 FLOOR MIN WAKE Select the floor temperature while in the wake schedule Applies when there is both a floor and an air sensor Off 40 to 95 F Off 4 5 to 35 0 C Off FLOOR MIN LEAVE Select the floor temperature while in the leave schedule Applies when there is both a floor and an air sensor Off 40 to 95 F Off 4 5 to 35 0 C Off FLOOR MIN RET...

Страница 19: ... the fan exceeds this run time Off 200 to 2000 hours Off Setting Range Default SENSOR 1 Select the type of sensor connected to S1 and Com wiring terminals Off Room Floor Off SENSOR 2 Select the type of sensor connected to S2 and Com wiring terminals Off Room Floor Outdoor Off INTERNAL ROOM SENSOR Select if the internal room temperature sensor is on or off Only available when Sensor 1 or 2 is set t...

Страница 20: ...es 1 minute Y MIN RUN TIME Select the minimum time the cooling compressor must run before shutting off This helps prevent compressor failure 0 30 to 10 00 minutes 2 00 minutes Y MIN OFF TIME Select the minimum time the cooling compressor must be off before turning back on This helps prevent compressor failure 0 30 to 10 00 minutes 5 00 minutes Screen Page 2 FAN RELAY Select which relays require fa...

Страница 21: ... 2 FAULT Due to an open or short circuit the thermostat is unable to read the sensor wired to S2 and Com The thermostat stops normal operation if sensor 2 is the only active room or floor sensor or if a floor maximum temperature has been set Check the auxiliary sensor wire for short circuits according to the sensor installa tion manual It may be necessary to replace the auxiliary sensor Once the e...

Страница 22: ...e White PVC plastic NEMA Type 1 Approvals Meets Class B ICES FCC Part 15 Ambient conditions Indoor use only 32 to 122 F 0 to 50 C RH 90 non condensing Power supply 15 to 30 V ac dc 2 VA standby Class 2 Relays 30V ac dc 2 A Class 2 circuits Sensor NTC thermistor 10 kΩ 77 F 25 C 0 2 C ß 3892 Included None Optional tekmar type 070 072 073 076 077 079 084 Communications WiFi 802 11n 2 4 GHz WPA2 encry...

Страница 23: ... _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Страница 24: ...about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser s sole responsibility and obligation Pur chaser shall indemnify and hold tekmar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser...