Application 306V–1

Mechanical

 ---------------------------------------------------------------------------------------------

Electrical

 -----------------------------------------------------------------------------------------------

B1 = Boiler

PS = System Pump

T1 = WiFi Thermostat 561 or 562

T2 to T4 = Thermostat 518 or 519

T5 = Generic Digital Power-Stealing Thermostat

T6 = Generic Bi-Metallic Strip Thermostat

V1 to V6 = 2-Wire Zone Valves

N

B1

PS

306V

V1

V2

V3

V4

V5

V6

DIP Switches

Master

T-stat 1 Priority = Off

Exercising = On

Post Purge = On

Mod Boiler = depends on boiler

System Pump During Priority = On

System Pump With Member Calls = Off

Zone Valve End Switches = Off

Included 510 Ω resistor must 

be installed when using power 

stealing thermostats 

(e.g. Thermostat T5)

Away

C R Rh W

Away

C R Rh W

Away

C R Rh W

Away

C R Rh W

R W

R W

MOD

X X

tN4

T1

T2

T3

T4

T5

T6

A

DHW

C R W

BOILER

T-STAT 1

T-STAT 2

T-STAT 3

-

+

tN4

A C R W

tN4

A C R W

T-STAT 4

tN4

A C R W

T-STAT 5

tN4

A C R W

T-STAT 6

EXPANSION

tN4

A C R W

tN4

A B C D E

FUSE 2 FUSE 1

END

SWITCH

MOTOR

POWER

PRIORITY

SYS PUMP

ROOM

RESPONSE

ZONE 1

70 80

90

60

50

100

MOD MAX %

END

SWITCH

MOTOR

ZONE 2

END

SWITCH

MOTOR

ZONE 3

END

SWITCH

MOTOR

ZONE 4

END

SWITCH

MOTOR

ZONE 5

END

SWITCH

MOTOR

ZONE 6

MASTER

MEMBER

OFF

OFF

OFF

T-STAT 1 PRIORITY : ON

EXERCISING : ON

POST PURGE : ON

MOD BOILER : 0-10V

SYSTEM PUMP DURING PRIORITY: ON

SYSTEM PUMP WITH MEMBER CALL: ON

ZONE VALVE END SWITCHES: ON

RESERVED

120 VAC

POWER

PUMP

PUMP 1

SYSTEM

PRIORITY

L

N

L

N

L

N

OFF

OFF

OFF

4-20 mA

B1

T1

T2

T3

T4

T5

T6

PS

V1

V2

V3

V4

V5

V6

L N

The Zone Valve Control 306V operates six heating zones. When the thermostat calls for heat, the zone valve opens, the system 

pump is turned on and the boiler is fired.

Legend

Содержание tekmar 306V

Страница 1: ...p to six thermostats and operates zone valves to provide heating to a zoned hydronic heating system The 306V operates a system pump whenever a zone valve opens Zone 1 can operate either a zone valve or a circulator to provide heat to an indirect domestic hot water tank with optional priority over zones 2 through 6 The 306V includes optional exercising to prevent circulator seizure when not in use ...

Страница 2: ...ided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read manual and all product labels BEFORE using the equipment Do not use unless you know the safe and proper operation of this equipment Keep this manual available for easy access by all users Replacement manuals are available at ...

Страница 3: ...ntrol to a different circuit from that to which the receiver is connected Cet appareil numérique de la classe B respecte toutes les exi gences du Règlement sur le matériel brouilleur du Canada Radio Frequency Interference Location Keep the control dry Avoid potential leakage onto the control Maintain relative humidity less than 90 in a non condensing environment Avoid exposure to extreme temperatu...

Страница 4: ...tN4 T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 tN4 A C R W tN4 A C R W T STAT 4 tN4 A C R W T STAT 5 tN4 A C R W T STAT 6 EXPANSION tN4 A C R W tN4 A B C D E FUSE 2 FUSE 1 END SWITCH MOTOR POWER PRIORITY SYSPUMP ROOM RESPONSE ZONE 1 70 80 90 60 50 100 MOD MAX END SWITCH MOTOR ZONE 2 END SWITCH MOTOR ZONE 3 END SWITCH MOTOR ZONE 4 END SWITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6...

Страница 5: ...1 70 80 90 60 50 100 MOD MAX END SWITCH MOTOR ZONE 2 END SWITCH MOTOR ZONE 3 END SWITCH MOTOR ZONE 4 END SWITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6 MASTER MEMBER OFF OFF OFF T STAT1PRIORITY ON EXERCISING ON POSTPURGE ON MODBOILER 0 10V SYSTEMPUMPDURINGPRIORITY ON SYSTEMPUMPWITHMEMBERCALL ON ZONEVALVEENDSWITCHES ON RESERVED 120 VAC POWER PUMP PUMP 1 SYSTEM PRIORITY L N L N L N OFF OFF OFF 4 20mA 1...

Страница 6: ...END SWITCH MOTOR ZONE 6 MASTER MEMBER OFF OFF OFF T STAT1PRIORITY ON EXERCISING ON POSTPURGE ON MODBOILER 0 10V SYSTEMPUMPDURINGPRIORITY ON SYSTEMPUMPWITHMEMBERCALL ON ZONEVALVEENDSWITCHES ON RESERVED 120 VAC POWER PUMP PUMP 1 SYSTEM PRIORITY L N L N L N OFF OFF OFF 4 20mA B1 PS L L N N P1 V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 A1 T1 T6 T7 T8 T9 T10 T11 T2 T3 T4 T5 L N Power L N System Pump L N L N Po...

Страница 7: ...ch if a pump is installed and the Zone Valve End Switches DIP switch is set on Exercising DIP Switch ON Each circulator pump is energized for 30 seconds every 72 hours OFF Circulator pump exercising disabled Post Purge DIP Switch ON After thermostat 1 stops calling for heat the zone 1 priority pump and zone valve remain on for 2 minutes to purge heat from the boiler to the zone OFF Post purge disa...

Страница 8: ...pansion bus from the master to the member controls Terminal Description A tN4 Away signal connecting tekmar thermostats B RoomResponseTM signal from member controls C Power common D Demandsignal 0Vdc demand 2Vdc nodemand E Priority signal 0 Vdc priority 2 Vdc no priority Setting the Max Mod Dial Boiler Make Model Required Adapter Supplied by boiler manufacturer 0 10 V dc 4 20 mA DIP Switch Mod Max...

Страница 9: ...tpoint Source Change Energy Management setting Central Heat Modulation Source to 4 20 mA Change Energy Management setting Central Heat 4 20 mA Setup 4 mA Water Temperature to 80 F 26 5 C 9 10 22 23 5 6 16 17 2 U 1 X X T T 1 2 9 10 No changes to the boiler are required Aerco AM Series Bosch Greenstar Buderus GB142 and GB162 Burnham Alpine Camus Modulating MicoFlame Heat Transfer Products Elite IBC ...

Страница 10: ...ameter to ACTIVE Set BMS Type to SETPOINT Enter boiler password Set Parameter Setpoint source to 4 20mA Enter boiler password Set Parameter Setpoint source to 4 20mA Lochinvar Knight Lochinvar FTXL NTI Trinity LX Riverside HeatStation NTI Trinity Fire Tube 306V 306V 306V 306V 306V Sensor I O 24Vac I O X X W R 1 2 37 38 X X W R 21 22 35 36 X X CH1 R 3 5 11 12 X X CH1 R 3 5 4 5 8 EMS 9 Laars Mascot ...

Страница 11: ...x to 180 F Set Local Priority 2 Volts For Min to 2 V Set Local Priority 2 Volts For Max to 10 V Install the OpenTherm Module as per the boiler manufac turer s instructions Raypak MVB or XTherm Raypak XFyre or XPakFT 306V 306V J2 J1 X X 13 14 17 18 X X T T 8 9 9 10 Viessmann OpenTherm Module Viessmann Extension Module EA1 Plug 0 10V Weil McLain Evergreen P15 306V 306V 306V 1 4 1 2 5 6 Viessmann Vit...

Страница 12: ...bligation Purchaser shall indemnify and hold tekmar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to any such representations or war ranties by Purchaser to its customers The pass through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar accident fire Act...

Отзывы: