background image

Installation & 

Operation Manual

SunStat® Pro II

Programmable Thermostat

Model 500775 (-BB, -HB, -SB, -WB)

Local building or electrical codes may require modifications to the information 

provided. You are required to consult the local building and electrical codes 

prior to installation. If this information is not consistent with local building or 

electrical codes, the local codes should be followed.

Items included

Unpack the thermostat control and make sure everything is in good condition. 

Do not use a damaged control or part. The package comes with these items:
(1) Thermostat
(1) Thermostat Floor Sensor
(5) Wire Nuts (Marettes®)
(2) Mounting Screws
(1) Screwdriver

Tools and supplies needed

•  No. 2 Phillips screwdriver
•  Hole saw (if installing in an existing wall)
•  Wire strippers, wire cutters, and other electrical tools
•  Electrical wall box (plastic or metal)*

As with any electrical product, care should be taken to guard 

against the potential risk of fire, electric shock, and injury to 

persons. The following must be observed:

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use 

information can result in death, serious personal 

injury, property damage, or damage to the 

equipment.
Keep this Manual for future reference.

Installation must be performed by qualified personnel, in accordance with 

local codes and standards. A licensed electrician is recommended.

*A single-gang extra-deep box allows sufficient space to connect 1 or 2 

heating mats or cables. For 3 heating mats or cables, a 4-inch square extra-

deep electrical box with a single-gang “mud ring” is necessary. Alternately, 

a junction box may be installed to connect multiple heating mats or cables, 

then run power supply wire from the junction box to the control electrical 

box. See the Installation Instructions provided with the floor heating system 

for more details.

•  Wire all circuits as Class 1, Electric Light and Power Circuits.
•  Wire all circuits with insulation rated 600V minimum.
•  Mount this control only to a grounded metallic box or a nonmetallic box.
•  Use power supply wires suitable for at least 90°C.
•  High voltage – disconnect power supply before servicing.
•  The GFCI (ground-fault circuit interrupter) in this thermostat control does not 

protect against shock if both bare conductors are touched at the same time.

•  Do not exceed 15 amps on this thermostat control. Doing so will cause risk 

of fire hazard and damage.

•  Make sure the house power supply voltage matches the voltage rating of 

the floor heating system. Do not apply 240 VAC to a 120 VAC rated system. 

Connecting the wrong voltage may cause overheating and damage to the 

system, the control, floor coverings, etc.

To prevent the risk of personal injury and/or death, make  sure 

power is not applied to the product until it is fully installed and 

ready for final testing. All work must be done with power turned 

off to the circuit being worked on.

House Wiring

Pull power supply wiring to the control location. Consider the following:

•  Leave about 6 to 8 inches (15 to 20 cm) of wire for connections later.
•  This wiring should be size 12 or 14 AWG following appropriate local code 

requirements.

•  A qualified person should run a dedicated circuit from the main circuit 

breaker panel to the control location. If a dedicated circuit is not possible, it 

is acceptable to tap into an existing circuit. However, there must be enough 

capacity to handle the load (amps) of the floor heating system being installed 

and any possible appliance, such as a hair dryer or vacuum cleaner.

•  Avoid circuits that have ballasted lighting, motors, exhaust fans, or hot tub 

pumps due to possible interference.

•  The circuit breaker should be rated 20 amps for total circuit loads up to 15 amps. 

A 15 amp circuit breaker may be used for total circuit loads up to 12 amps.

•  A GFCI (ground-fault circuit interrupter) or AFCI (arc-fault circuit interrupter) 

type circuit breaker may be used if desired, but is not necessary.

The SunStat Pro II model 500775 is designed to operate either a 120 VAC or 

240 VAC resistance floor heating system. It comes with an easy setup wizard, a 

typical Program Schedule ready to go, and a GFCI inside to meet safety needs.

Installation

Locating the Control

Find a suitable location for the control.  Consider the following:
•  It is designed for indoor dry location only.
•  It may be placed on an insulated or uninsulated wall, preferably an interior 

wall to avoid overheating from outside sun heat.

•  Keep it away from all water sources such as sinks, showers, and bathtubs 

as well as heat sources such as hot-water piping, heat ducting, wall-mount 

lighting, and direct sunlight.

•  Locate it at a suitable height, normally about 4-1/2’ to 5’ (1.4 m to 1.5 m) 

from the floor.

Mounting the Electrical Box

•  When mounting on an existing wall, cut the opening for the electrical box for 

the control. To make it easier to pull the wiring, wait to install the electrical 

box until after all wiring is drawn into this opening.

•  When mounting on an open wall, secure the electrical box for the control to 

the wall stud. Conduit from the electrical box to the floor is recommended 

(check local codes for requirements) for additional protection. Install one 

conduit for the floor sensor. Install another conduit for the floor heating 

system power leads.

•  Refer to the Installation Instructions supplied with the floor heating system 

for additional installation details.

Wiring

Содержание SunStat Pro II 500775

Страница 1: ... overheating and damage to the system the control floor coverings etc To prevent the risk of personal injury and or death make sure power is not applied to the product until it is fully installed and ready for final testing All work must be done with power turned off to the circuit being worked on House Wiring Pull power supply wiring to the control location Consider the following Leave about 6 to...

Страница 2: ...uch as a clothes hamper or similar could trap heat and cause improper measurement Power Leads from Heating Mat or Cable Pull the power lead wires from the floor heating system into the control location Excess power lead wire may be cut off but leave about 6 to 8 inches 15 to 20 cm of wire for connections Removing the Thermostat Front Module 1 Remove the Screw Cover at the bottom and loosen the scr...

Страница 3: ...hedule may have a WAKE start time of 6 00AM to be 82ᵒF 27 8ᵒC and SmartStart may begin pre heating at 5 30AM to reach 82ᵒF by 6 00AM It will take a couple days to learn ON OFF Default ON FACTORY RESET Use with caution This will clear all programming and settings to factory condition This is useful if there are problems or errors which cannot be corrected Hold a Setpoint Temperature 1 Press HOLD to...

Страница 4: ...o your distributor to begin the warranty process This limited warranty does not cover shipping costs Nor does it cover a product subjected to misuse or accidental damage This warranty does not cover the cost of installation diagnosis removal or reinstallation or any material costs or loss of use This limited warranty is in lieu of all other warranties obligations or liabilities expressed or implie...

Отзывы: