background image

3

Solenoid Operation 

(For Existing LFF113RFP Installations Only)

The Solenoid is prewired to the existing Junction Box, and must 

be rewired by a certified electrician. The solenoid is equipped 

with a Solenoid Bypass valve (normally closed) which manually 

closes the Main Valve when engaged.
Opening the Solenoid Bypass Valve pressurizes the Main Valve 

cover as indicated by Pressure Gauge, closing the Main Valve.
Closing Solenoid Bypass Valve and opening the Manual Reset 

Ball Valve returns the Main Valve to the full open position.
Pressure Gauge returns to zero when the Main Valve is fully 

open.

NOTE:  

Manual Reset Ball Valve must be closed for normal 

operation.

Installing the Flow Sensor 

(Backfl ow Upgrade Kit Only)

The Flow Sensor is installed in the discharge piping from the 

RPZ relief valve. If the Flow Sensor senses water in the dis-

charge piping, it will signal the Junction Box to close the valve.

Installation Notes

1.  Install the supplied tee for the Flow Sensor in the RPZ dis-

charge line in the HORIZONTAL position as shown below.

2.  Cut Sensor Probes to length. The ends of the Sensor Probes 

should be located between 

1

3

 and 

1

2

 of the pipe’s inner diam-

eter from the pipe bottom. The probes MUST NOT BE less 

than ¼" from the pipe wall.

3.  Install Flow Sensor in tee, again ensuring that it is in the 

HORIZONTAL position as shown below.

To Floor Drain

From RPZ Relief 

Valve (with Air Gap)

Sensor Probes 

Installed

Front View

Top View with 

Cover Removed

2" NPT

WARNING

!

Certified electrician to connect main power and Flow Sensor to 

Junction Box.

Ensure Sensor Probes do not contact pipe bottom or sides.

CAUTION

!

Installation and Operation

Содержание SentryPlus 113RFP

Страница 1: ... Required Tools and Materials for Installation 2 Installation and Operation 3 ISolenoid Operation For Existing LFF113RFP Installations Only 3 Installing the Flow Sensor Backflow Upgrade Kit Only 3 Wiring Retrofitting the junction box 4 Installing the Wireless Node 6 Registering Your Device and Alert Configuration 7 Start up Instructions 8 Warranty 8 Read this Manual BEFORE using this equipment Fai...

Страница 2: ...ctorial and or safety mes sage to identify hazards and alert you to the potential for death or serious personal injury Identifies hazards which if not avoided will result in death or serious injury Identifies hazards which if not avoided could result in death or serious injury Identifies hazards which if not avoided could result in minor or moderate injury Identifies practices actions or failure t...

Страница 3: ... Flow Sensor is installed in the discharge piping from the RPZ relief valve If the Flow Sensor senses water in the dis charge piping it will signal the Junction Box to close the valve Installation Notes 1 Install the supplied tee for the Flow Sensor in the RPZ dis charge line in the HORIZONTAL position as shown below 2 Cut Sensor Probes to length The ends of the Sensor Probes should be located bet...

Страница 4: ...tection or protection NOTICE Wiring the Junction Box For Existing LFF113RFP Installations Only After removal of power from the circuit disengage the wiring from o Main terminals inside Junction Box o Terminals 1 and 2 Flow Sensor o Terminals 3 and 4 Solenoid o Terminals 5 and 6 remote trip indicator if wired Remove the Junction Box from the ACV or wall mount Replace the Junction Box with the new u...

Страница 5: ...is adjust able from 0 seconds to over 1 hour Adjust the time delay by using the delay adjustment dial in the Junction Box Use a small Phillips head screwdriver to adjust either the range selector 0 6 0 12 0 30 0 60 on the left side or the unit selector 0 1 sec sec min hr on the right side Increase the time delay by adjusting the dial clockwise decrease the time delay by adjusting the time delay co...

Страница 6: ...oles 13 Screws are not included 5 Route wires from terminals 7 and 8 of the Junction Box through the wiring gland 12 and connect to the Wireless Node at the Flood screw terminal 2 Polarity does not matter Six feet of wire is supplied with the unit but the Wireless Node can be located up to 100 feet away from the Junction Box If additional wire is used it must meet the required rating for the Junct...

Страница 7: ...ess Node is connecting to the Cloud Once a Cloud connection is established the Program button light will blink rapidly for a few seconds and then shut off The Cellular LED 8 and IoT LED 9 should both be a solid blue 2 Cellular Connection Once the start up sequence is completed the Cellular LED will be a steady blue if there is a good connection It will blink if there is a poor connection There wil...

Страница 8: ... have other rights that vary from State to State You should consult applicable state laws to determine your rights SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT IOM UPGRADEKIT SentryPlus...

Отзывы: