OWNER’S MANUAL: POINT OF LEAK DETECTORS (POLD)
Clearing POLD Alarms
Step 1: Verify which POLD is alarming
• Check which POLD is in alarm based on the Source
number shown on the Control Panel, or open the Leak
Defense mobile app to view the custom name you gave
the POLD during setup.
• Locate the Point of Leak Detector (POLD) that is in alarm
by listening to its chirp.
Step 2: Clear the alarming POLD
The unit should self-clear once the sensors are dry. If this
does not happen, open the battery compartment on the
POLD and press the reset button for 1-3 seconds until
silent (or remove and re-insert one battery).
NOTE:
For non-standard mesh style cable, if the Water
Detection Cable is still wet, you may need to remove
the batteries for 24-48 hours until it dries. If the POLD is
still going into alarm after being allowed 48 hours to dry,
please call Sentinel Hydrosolutions.
Step 3: Clear Alarm on the Control Panel
• Once the cause of the alarm is identified and handled,
you may press the Clear Alarm button on the control
panel. This should proceed to a screen indicating if the
water is off.
• If the system alarms again, check the POLD # after the
word “Source:” on the Control Panel to see if it matches
the POLD that was cleared. If it is different, repeat Step
1 & 2.
NOTE:
The alarm condition must be cleared from the
POLD before you can clear the alarm on the Control
Panel.
NOTE:
Batteries should be replaced in regular intervals
and after alarms to ensure full power.
How & When to Change POLD
Batteries
Step 1: Verify which POLD has a low battery
• When a POLD has low batteries, it will periodically chirp.
• This can be verified by tapping on the control panel to
wake it up. There will be a low battery indicator
in the top section of the panel. Tap this icon to view
details.
Step 2: Replace the batteries
• With the antenna facing away from you, the battery that
is on the left should have positive (+) facing away from
you. The battery that is on the right should have positive
(+) facing toward you and away from the reset button
NOTE:
Verify that batteries are installed properly by
tapping the reset button and ensuring the LED lights
up and is solid
Step 3: Clear alert on the Control Panel
• Press the low battery indicator on the Control
Panel and follow the on-screen steps to clear the alert
on the panel