THE WIRELESS CONTROL PANEL
STEP 13:
Verify and set automatic shut-off features
DESIRED ACTION
ON-SCREEN ACTIONS
Main Screen with Scene set to
Home (Water, Flow,
and
Scene
symbols are GREEN)
Tap the
Trip Rate
icon
Enter trip level percentage between 1 and 100
Tap top right button to select trip level setting (Factory default is10%)
Main Screen with Scene set to
Home (Water, Flow,
and
Scene
symbols are GREEN)
Tap the
Time to Alarm
icon in the bottom left
Enter the time in minutes
Tap the top-right button to confirm the programmed time
(Can be set from 1 minute to 4 hours based on customer’s preference.
Example: 1 hour = 60)
Main Screen with Scene set to
Away
(Water, Flow,
and
Scene
symbols are BLUE)
Tap the
Trip Rate
icon
Enter trip level number between 1 and 100
Tap top right button to select trip level setting (Factory default is 10%)
Main Screen with Scene set to
Away (Water, Flow, and Scene
symbols are BLUE)
Tap the
Time to Alarm
icon in the bottom left
Enter the time in minutes
Tap the top-right button to confirm the programmed time
(Can be set from 1 minute to 4 hours based on customer’s preference.
Example: 3 minutes = 3)
Setting Time to Alarm – HOME Scene
Time to Alarm = The amount of time
water is allowed to flow for before the
valve closes
Setting Trip Rate % – AWAY Scene
Setting Time to Alarm – AWAY Scene
Setting Trip Rate % – HOME Scene
Trip Rate = Sensitivity or the amount
of water flow needed to trigger time to
alarm