USER GUIDE
GB
HUMIDITY THERMOSTAT & ZONES PROGRAMMER
o
Weekly and 12 zones programmer.
o
Permanent memory storage
o
Regulation by internal or external probe in option.
o
Heating, Cooling and humidity control.
TECHNICAL CHARACTERISTICS
Measuring accuracy
0.1°C
Operating temperature
0°C - 50°C
Ambient temperature range
5° C – 37° C in steps of 0.5° C
Regulation characteristics
Integral proportional band (PWM) or Static differential.
Electrical Protection
Class II - IP30
Feeding and autonomy
3 batteries AA LR06 1.5 V / > 2 years (alkaline batteries)
Radio frequency and
certifications
433,92MHz, < 10mW
CE. EN 300220-1, EN 301489-1
External probe in option
CTN 10K 3M
Program version
To display the software version press the
during 3sec in anti freeze
mode
.
“Crf _.__”
DISPLAY
1:
Function mode.
2:
Heating mode indicator.
3:
Cooling mode indicator.
4:
Ambient temperature indicator.
5:
Ambient temperature if “4” lit up, current zone or
temperature required.
6:
Weekly program / Radio frame.
7:
Humidity level or time.
8:
Current day of the week.
9:
Low batteries.
10:
Holiday mode.
OPERATING MODE DESCRIPTION
Use
and
keys to change operating mode.
Humidity Mode:
Use
and
to set the maximum humidity value (in relative humidity percent) of your room.
The humidity drier output will be switch on when the current humidity is above this value.
This output is controlled only in cooling mode “
Mod COOL
” or ‘
Mod AUTO
” in cooling.
PPL IMP 1305 A
INSTALLER’S PARAMETERS
To access to the installation parameters menu, press
during 10 s.
Use
and
keys to show the parameter to adjust.
Press
to toggle the parameter setting or edit the value. If the value starts to blink you can use
and
keys to adjust this value. Press
and
keys at the same time to reset this value to the factory default value.
Once you have adjusted the value press
to validate this parameter value.
When you have finished, go to «
CrF Init
» parameter and press
to go back to the main menu.
Installation parameters:
name
Description
Default setting
Other possibility
CrF Init
Use this parameter to configure the thermostat with the receiver.
J0
°C or °F temperature display selection
°C
°F
J1
12h or 24h time display
24h
12h
CH
Numbers of zones installed on your installation
12
Adjustable «
01
» to
«
12
»
H.C
Type of installation:
Menu:
The cold warm change is manually
managed by the end user. (On the thermostat)
Auto:
The cold warm change is managed by the
automatic reversible Heat pump. (Special input on
the RF Receiver)
Menu
Auto
J2
Select
Hot
or
CoLd
to adjust :
if lit up =>
adjust the heater parameters.
if lit up =>
adjust the cooler parameters.
Hot
CoLd
J5
Anti-lock-braking function of the pump
When the pump hasn’t worked on a particular day,
start it up for one minute each day.
(adjustable in
&
in
Menu
position
)
Yes
no
J6
Air or Floor temperature regulation selection.
(if no Floor sensor, regulation will use Air sensor)
Air
FLor
J7
Selection of regulation type
(adjustable in
&
in
Menu
position
)
Bp
(PWM)
«
hyst
»
static differential of 0.5°C
Cy
Selection of the proportional band duration in
minutes
(adjustable in
&
in
Menu
position
)
15 =>
Slow system
adapted to each
heating type
30 =>
adapted to Heat
pump control
Heating application :
Burner oil «
20
»
Burner gas «
10
»
Actuator «
10
»
Heat pump «
20
»
Cooling application :
Heat pump/ Air conditioning «
30
»
Ventilate convector «
10
»
On
Minimal starting time in minutes
(adjustable in
&
in
Menu
position
)
2 =>
4 =>
Adjustable,
0
to ½
Cy
OF
Minimal resting time between 2 heating cycles in
minutes
(adjustable in
&
in
Menu
position
)
3 =>
4 =>
Adjustable,
0
to
½ Cy
bP
Value of the proportional band (PWM)
(adjustable in
&
in
Menu
position
)
2.0°C =>
4.0°C =>
Adjustable
1
°C to
6
°C
A well insulated house
1.5°C
In case of your house has not a
good insulation increase this value.
Ao
Air sensor offset adjustment.
Display measured Air sensor value.
No offset
Adjustable
+
/
–
12°C
Fo
Floor sensor offset adjustment.
Display measured Floor sensor value.
No offset
Adjustable
+
/
–
12°C
FL
Floor temperature LOW limitation,
Effective only if floor sensor present.
(adjustable in
&
in
Menu
position
)
18°C =>
18°C =>
Adjustable
5,0 °C
to
FH
FH
Floor temperature HIGH limitation,
Effective only if floor sensor present.
(adjustable in
&
in
Menu
position
)
28°C =>
37°C =>
Adjustable
FL
to
37°C
GAP
Value of the dead zones (only for “
Mod Auto
”)
4,0°C
Adjustable
0,2°C
to
25 °C
dLY
Time delay between the Heat and Cold
commutation in minutes (only for “
Mod Auto
”)
60
Adjustable
1
to
240
min
CLr
Press
during 5sec to reset your thermostat, all parameter will reload with default values.