If water hammer is evident, install water hammer arrestors before the system.
WARNING!
Do not attempt to remove the cartridge filter lid without relieving pressure. To open lid, close
shutoff valves before and after filter, press pressure relief button to relieve pressure. Once
pressure has been relieved, remove eyebolts and lid. To start up filter, replace lid, tighten
eyebolts, and open shutoff valves slowly to check for leaks. If lid O-ring does not seat
properly, close shutoff valves, relieve pressure, open lid, apply a small amount of non-
petroleum based lubricant to the O-ring to help it seal, reposition O-ring and close lid.
3.4.
Electrical Connections
It is the responsibility of the end user to ensure that the installation is done according to local
codes and regulations. Plug in the power cord(s) into an appropriate outlet (refer to
specifications table) that is installed and grounded in accordance with all local codes and
ordinances.
NOTE:
The system MUST be plugged into an uninterrupted power supply that matches the
rated power requirement of the system. In European installations, the appliance is to be
supplied through a residual current device (RCD) having a rated residual operating current
not exceeding 30 milliamps
WARNING!
This appliance must be grounded. In the event of a malfunction or breakdown, grounding will
reduce the risk of electric shock by providing a path of least resistance for electric current.
This appliance is equipped with a cord having an appliance-grounding conductor and a
grounding plug. The plug must be plugged into an appropriate outlet that is installed and
grounded in accordance with all local codes and ordinances.
Improper connection of the appliance-grounding conductor can result in a risk of electric
shock. Check with a qualified electrician or service representative if you are in doubt whether
the appliance is properly grounded. Do not modify the plug provided with the appliance; if it
will not fit the outlet, have a proper outlet installed by a qualified technician.
3.5.
Startup
Once the plumbing and electrical connection procedures are completed and the entire system is
verified to be free of leak, open the outlet isolation valve(s) and then slowly open the inlet
isolation valve.
NOTES:
•
DO NOT allow this system to remain ON without water in it for extended periods of time.
•
DO NOT allow the system to freeze.
•
Do not operate filter above 125psi (8.8 bar). In installations where pressure is above
100psi (6.9 bar), install a pressure release valve to release pressure at 125psi (8.8 bar)