Specifications

AquaSolve shall be installed on the main water ser-
vice pipe just after it enters the building, but after 
other whole building water safety devices (backflow 
preventers or pressure reducing valves), to effectively 
address water hardness con-cerns. A system may 
also be installed further downstream to protect spe-
cific equipment or areas within a plumbing system. 
The system shall be plumbed with a bypass valve to 
allow isolation of tank(s) and to allow the bypass of 
untreated water in the event that service or media 
replacement be necessary. The installation area 
should be suitable in size for the tank(s) to be ser-
viced without encumbrance and sit upright on a flat 
level surface.

The system must operate in an upflow manner and 
does not require additional water to backwash, flush, 
or regenerate once put into service. The system does 
not require any chemical additives and does not 
require electricity for operation.

Multi-tank systems shall be installed in parallel with 
PVC/CPVC manifold to meet peak flow rate require-
ments.

Spotting May Occur on External Plumbing Surfaces.

 

AquaSolve media systems perform best in single pass pota-
ble water applications with NO additional chemical additives. 
Depending on hardness, soft scale spotting may occur. Soft scale 
spots in most cases can be easily wiped down with a damp cloth 
and will not form hard scale deposits. A Point of Use (POU) Water 
Softener should be used on mandatory spot-free applications (e.g. 
glass stemware, dishware).

NOTICE

Using AquaSolve With Other Water Treatment Equipment.

Due to the unique properties of AquaSolve, there are some unique 
requirements for using AquaSolve in conjunction with other forms 
of water treatment:

1. AquaSolve must be the last stage in the treatment chain. Do 

not install any filters after AquaSolve or before any devices for 
which scale prevention is required. POU filters, e.g. carbon, 
RO or Ultraviolet (UV) are exempt from this requirement.

2. Do not apply any other antiscalants before or after AquaSolve.

3. The addition of soaps, chemicals, or cleaners, before or after 

AquaSolve treatment, may reverse its anti-scale treatment 
effects and/or create water with a heavy residue or spotting 
potential. Any adverse conditions caused by the addition of 
soaps, chemicals, or cleaners are the sole responsibility of the 
end user.

4. AquaSolve is not a water softener and does not soften the 

water - water treatment chemistry (e.g. antiscalants, seque-
trants, soaps, chemicals or cleaners etc.) will most likely have 
to be changed to be compatible with AquaSolve treated water. 
Laundry and ware-washing chemistry will likewise require 
adjustments.

WARNING

•  Not for use on closed loop systems.
•  Do not let the system freeze. Damage to the tank may result.
•  System must be operated in a vertical position. Do not lay 

it down during operation. The system may be placed in any 
position for shipping and installation but must be operated in 
the vertical position.

•  Place the system on a smooth, level surface. Because the sys-

tem operates in an upflow, fluidized bed mode, having a level 
surface is more important than with a softener or media filter.

•  A bypass valve should be installed on every system to facili-

tate installation and service.

•  Observe all local plumbing and building codes when installing 

the system.

CAUTION

Standards

Independent scientific testing has confirmed 
Template Assisted Crystallization (TAC) technology 
provides scale reduction of over 95+%. Testing was 
conducted under protocol based on DVGW W512 
test to access control of scale formation.

Operation & Maintenance Manual

Lync AquaSolve

Содержание Lync AquaSolve LM8408-COM

Страница 1: ...rth TX 76134 817 335 9531 Technical Support 800 433 5654 ext 3 Mon Fri 8 am 5 pm CST Engineered Solutions OMM LM8408_LM8410 COM_EN Important Read this Manual BEFORE using this equipment Failure to rea...

Страница 2: ...effec tive alternative technology to a water softener for the prevention of scale due to water hardness Virtually maintenance free no control valve Uses environmentally friendly technology by using no...

Страница 3: ...AquaSolve in conjunction with other forms of water treatment 1 AquaSolve must be the last stage in the treatment chain Do not install any filters after AquaSolve or before any devices for which scale...

Страница 4: ...pplying excessive flux on the inner surfaces of the pipe and use a low corrosivity water soluble flux listed under the ASTM B813 standard AquaSolve media does not reduce silica scaling While silica te...

Страница 5: ...needed for servicing The full weight of the plumbing system must be supported by pipe hangers or other means NOTICE Install Piping Connect the inlet and outlet plumbing according to your preferences a...

Страница 6: ...lue structure or appearance of these objects protect remove them or use the outlet hose to drain option 7 Connect the outlet of the AquaSolve system to the cold water supply to the building Install an...

Страница 7: ...pe hose fill with media it will plug up You need to let slugs of water flush out the pipe as you go Your AquaSolve media should be replaced every 3 years Dispose of old media and or container in accor...

Страница 8: ...F O B nearest factory at no cost excluding freight and local labor charges if any Our obligation under this warranty with respect to the Lync AquaSolve media will be limited to furnishing a replaceme...

Отзывы: