background image

2

•   Most field problems occur because dirt and debris are present 

in the system at the time of installation and becomes trapped 

in check #1. The system should be flushed before the back-

flow valve is installed. If the system is not flushed until after the 

backflow valve is installed, remove both check modules from 

the valve and open the inlet shutoff to allow water to flow for 

a sufficient time to flush debris from the water line. If debris in 

the water system continues to cause fouling, a strainer can be 

installed upstream of the backflow assembly.

•   Series C400-FS, C500-FS, and LFC500-FS can be installed 

in either horizontal, “N” pattern, or “Z” pattern position as long 

as the backflow assembly is installed in accordance with the 

direction of the flow arrow on the assembly and the local water 

authority approves the installation.

•   The assembly should be installed with adequate clearance 

around the valve to allow for inspection, testing, and servicing. A 

minimum clearance of 12" should be between the lower portion 

of the assembly and the floor or grade. The valve should be 

protected from freezing.

•   Installing a backflow preventer in a pit or vault is not  

recommended.

•   Normal discharge and nuisance spitting are accommodated by 

the use of an Ames air gap fitting and a fabricated indirect waste 

line. Floor drains of the same size must be provided in case of 

excessive discharge.

•   Series C400, C500, and LFC500 backflow preventers should be 

tested by a certified tester at the time of installation.

 

NOTICE

Assembly body should not be painted.

Installation Guidelines

Relief Valve Discharge Rates 2

1

2

" – 10" 

  lpm gpm

 1330 350

 1140 300

  950 250

  760 200

  570 150

  380 100

 190 50

  0 0

20 

40 

60 

80 psi

138 

276 

413 

551 kPa

Rate of Flow

Pressure

Horizontal Installation

N Pattern

Z Pattern

Содержание LFC500-FS Series

Страница 1: ...l products must be retested once maintenance has been performed Corrosive water conditions and or unauthorized adjustments or repair could render the product ineffective for the service intended Regul...

Страница 2: ...water authority approves the installation The assembly should be installed with adequate clearance around the valve to allow for inspection testing and servicing A minimum clearance of 12 should be b...

Страница 3: ...ne See Figure C 5 Remove the check 2 module with the same instructions as in step 4 For servicing 6 checks see the maintenance instructions for sizes 8 to 10 6 To clean or inspect either check module...

Страница 4: ...the service hole and thread in the service bolt by hand until it contacts the linkage See Figure A 4 Continue to thread in service bolt with the wrench until the service hole in the linkage is aligne...

Страница 5: ...ewing the relief valve from the housing 5 Remove the cover plate of the relief valve by detaching the four connecting screws 6 Remove the rubber diaphragm from the relief valve Notice how the diaphrag...

Страница 6: ...ock No 2 Close test cock No 4 Disconnect vent hose at test cock No 4 Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pressu...

Страница 7: ...Check Module O ring First Check Module Relief Valve Second Check Module Troubleshooting PROBLEM CAUSE SOLUTION Relief valve discharges water while system is not flowing Check 1 is fouled Remove and cl...

Страница 8: ...rom the date of original shipment In the event of such defects within the warranty period the Company will at its option replace or recondition the product without charge THE WARRANTY SET FORTH HEREIN...

Отзывы: