background image

3

NOTICE

Do not reduce the size of the drain line from the air gap fit-

ting. The drain line must remain at full line size.

E.   After the initial installation of the assembly, a discharge from 

the relief valve may occur due to dirt and pipe compounds.  

This may be caused by inadequate initial flushing of the pipe-

lines. If flushing the valve does not clear the unit, remove the 

first check valve and clean thoroughly, using the procedures 

in “Servicing the First and Second Check Valves.” 

NOTICE

Periodic relief valve discharge may occur on dead end 

service applications, such as boiler feed lines or cooling 

tower makeup lines. This may be due to fluctuating supply 

pressure during a static or no flow condition. To avoid this 

discharge, install a spring-loaded, rubber seated check valve 

ahead of the backflow assembly. 

F.   Avoid placing the assembly in a pit or at a depth below the 

ground level, unless absolutely necessary. If an installa-

tion requires below ground level installation, a modified pit 

installation is recommended, as well as the approval of local 

codes. In such cases, provision should be made to always 

vent the drain line above the flood level. In the case of a pit 

drain, ensure an adequate air gap exists between the bottom 

of the drain line and the bottom of the pit.

G.  Periodically inspect the assembly to check for any discharge 

from the relief valve. This discharge is a visual indication that 

the valve needs cleaning or repair. Also test the valve peri-

odically in compliance with local codes to ensure its proper 

operation.

The relief vent discharges water during no-flow periods in the 

following instances:
•  The first check valve is fouled. 
•  The inlet pressure to the check valve drops sufficiently due 

to upstream pressure fluctuations. This affects the required 

operating differential between the inlet pressure and the 

reduced pressure zone. 

•  The second check is fouled during emergency backflow or 

resulting from a water hammer condition.

For more information download Troubleshooting Guide S-TSG. 

NOTICE

When installing the assembly on fire prevention systems, special 

considerations are required. 
Fire Protection System Installations: The National Fire Protection 

Agency (NFPA) Guidelines require a confirming flow test to be 

conducted by a certified tester whenever a “main line” valve is 

installed, such as a shutoff valve or a backflow preventer.

1/2"
3/4" M2
1" M2

1

2

" – 1" LF919

45
40
35
30
25
20
15
10

5
0

0 10 20 30 40 50 60  70 80 90 100 

110

Flow Rate gpm

Zone Pressure psi

  

1

2

3

4

X 1"

0 10 20 30 40 50 60  70 80 90 100 

110

Zone Pressure psi

 0   1

1

4

"–1

1

2

    

2"

Flow Rate gpm

350
300
250
200
150
100

50

0

1

1

4

" – 2" LF919

TYPICAL FLOW RATES AS SIZED BY FLOOR DRAIN MANUFACTURERS

2" 55 gpm

5" 350 gpm

3" 112 gpm

6" 450 gpm

4" 170 gpm

8" 760 gpm

installation is recommended, as well as the approval of local 

installation is recommended, as well as the approval of local 

codes. In such cases, provision should be made to always 

codes. In such cases, provision should be made to always 

vent the drain line above the flood level. In the case of a pit 

vent the drain line above the flood level. In the case of a pit 

drain, ensure an adequate air gap exists between the bottom 

drain, ensure an adequate air gap exists between the bottom 

Periodically inspect the assembly to check for any discharge 

Periodically inspect the assembly to check for any discharge 

from the relief valve. This discharge is a visual indication that 

from the relief valve. This discharge is a visual indication that 

the valve needs cleaning or repair. Also test the valve peri-

the valve needs cleaning or repair. Also test the valve peri-

odically in compliance with local codes to ensure its proper 

odically in compliance with local codes to ensure its proper 

The relief vent discharges water during no-flow periods in the 

The relief vent discharges water during no-flow periods in the 

The first check valve is fouled. 

The first check valve is fouled. 

The inlet pressure to the check valve drops sufficiently due 

The inlet pressure to the check valve drops sufficiently due 

to upstream pressure fluctuations. This affects the required 

to upstream pressure fluctuations. This affects the required 

operating differential between the inlet pressure and the 

operating differential between the inlet pressure and the 

reduced pressure zone. 

reduced pressure zone. 

The second check is fouled during emergency backflow or 

The second check is fouled during emergency backflow or 

resulting from a water hammer condition.

resulting from a water hammer condition.

For more information download Troubleshooting Guide S-TSG. 

For more information download Troubleshooting Guide S-TSG. 

DRAFT

When installing the assembly on fire prevention systems, special 

When installing the assembly on fire prevention systems, special 

considerations are required. 

considerations are required. 

Fire Protection System Installations: The National Fire Protection 

Fire Protection System Installations: The National Fire Protection 

Agency (NFPA) Guidelines require a confirming flow test to be 

Agency (NFPA) Guidelines require a confirming flow test to be 

DRAFT

DRAFT

DRAFT

0 10 20 30 40 50 60  70 80 90 100 

110

0 10 20 30 40 50 60  70 80 90 100 

110

0 10 20 30 40 50 60  70 80 90 100 

110

1

1

1

11

2

2

⁄⁄

DRAFT

DRAFT

  

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

Flow Rate gpm

Flow Rate gpm

350

350

350

300

300

300

250

250

250

200

200

200

150

150

150

100

100

100

50

0

1

1

1 4

⁄ " – 2" LF919

DRAFT

DRAFT

DRAFT

DRAFT

DRAFT

TYPICAL FLOW RATES AS SIZED BY FLOOR DRAIN MANUFACTURERS

Содержание LF919-QT-FS

Страница 1: ...e with governing authorities for local installation requirements DRAFT Need for Periodic Inspection Maintenance DRAFT Need for Periodic Inspection Maintenance This prod DRAFT This prod uct must be tested periodically in compliance with local DRAFT uct must be tested periodically in compliance with local codes but at least once per year or more as service condi DRAFT codes but at least once per yea...

Страница 2: ... avoid water hammer and or shock damage D Vent the air gap and drain line from the relief valve in accordance with code requirements Terminate discharge approximately 12 above the ground or through an air gap piped to a floor drain WARNING Do not allow the drain line to empty directly into a drainage ditch sewer system or sump NOTICE Relief Valve Discharge Rates The air gap and drain line terminat...

Страница 3: ...always DRAFT codes In such cases provision should be made to always vent the drain line above the flood level In the case of a pit DRAFT vent the drain line above the flood level In the case of a pit drain ensure an adequate air gap exists between the bottom DRAFT drain ensure an adequate air gap exists between the bottom Periodically inspect the assembly to check for any discharge DRAFT Periodica...

Страница 4: ...ts and cover realign the dia phragm assembly and place the cover back on the relief valve body 7 Reinstall the flood sensor and activation module if removal was required 8 Open the shutoff valves DRAFT 5 Remove the pressed in relief valve seat and seat O ring DRAFT 5 Remove the pressed in relief valve seat and seat O ring 1 Using a wrench loosen the diaphragm assembly by turning DRAFT 1 Using a wr...

Страница 5: ... Seat Check Seat O ring Cover Cover O ring Check Spring Check Disc Rubber Check Disc Holder Check Assembly Troubleshooting SYMPTOM CAUSE SOLUTION Check valve fails to hold 1 0 PSID minimum Debris on check disc sealing surface Disassemble and clean Leaking gate valve Disassemble and clean or repair Damaged seat disc or seat O ring Disassemble and replace Damaged guide holding check open Disassemble...

Страница 6: ...roduct does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control This warranty shall be invalidated by any abuse misuse misapplication improper installation or improper maintenance or alteration of the product Some State...

Отзывы: