Complete the following actions before starting the test procedures.
•  Ensure all needle valves are closed on the test kit.
•  Open test cock No. 4 and flush test cocks No. 1, No. 2, and No. 3 on the reduced pressure 

assembly then close test cock No. 4.

•  Attach the hoses as shown in the diagram. Bleed air from the kit then close the No. 2 shutoff.

LF909-QT-FS

No. 2 shutoff

Bleed Valve A

Bleed Valve B

High 

(red)

Bypass 

(yellow)

Low 

(blue)

Test No. 1 - Check Valve No. 2

Purpose:

 To test check valve No. 2 for tightness against reverse flow.

Requirements:

 The valve must be tight against reverse flow under 

all pressure differentials.
  1.  Slowly open the needle valves “A” high (red) and “C”  

bypass (yellow). Keep the needle valve “B” low (blue) closed.

  2. Open test cock No. 4.
  3.  Observe that the pressure differential decreases slightly. If the 

pressure differential continues to decrease (until the vent opens), 

the No. 2 check valve is reported as “leaking.”

Test No. 2 - Shutoff Valve No. 2

Purpose:

 To test shutoff valve No. 2 for tightness.

  1.  After passing Test No. 1, continue to test No. 2 by closing test 

cock No. 2.

  2.  Observe that the pressure differential decreases slightly. If pressure 

differential continues to decrease (approaching “zero”), the No. 2 

shutoff valve is reported to be “leaking.”

 

A leaking No. 2 shutoff always gives a false reading in tests  

No. 3 and 4.

Test No. 3 - Check Valve No. 1

Purpose:

 To test check valve No. 1 for tightness.

Requirements:

 The valve must be tight against reverse flow under 

all pressure differentials.
  1.  Close needle valve A high (red) and open test cock No. 2.
  2.  Close test cock No. 4. Disconnect the bypass hose (yellow) at 

test cock No. 4.

  3.  Open needle valves B low (blue) and C bypass (yellow), bleeding 

to atmosphere. Then close needle valve B (blue) to restore the 

system to a normal static condition.

  4.  Observe the pressure differential gauge. If there is a decrease in 

the indicated value, the No. 1 check valve is reported as “leaking.”

Test No. 4 - Pressure Differential Relief Valve

Purpose:

 To test operation of pressure differential relief valve.

Requirements:

 The pressure differential relief valve must operate to 

maintain the “zone” between the two check valves at least 2 psi less 

than the supply pressure.
  1. Close needle valve C bypass (yellow).
  2. Open needle valve A high (red).
  3.  Open needle valve B low (blue) very slowly until the differential 

gauge needle starts to drop.

  4.  Hold the valve at this position and observe the gauge reading  

at the moment the first discharge is noted from the relief valve. 

Record this as the opening differential pressure of the relief valve.

The differential gauge needle must drop slowly. This is important 

to maintain stability.

  5.  Close test cocks No. 2 and No. 3. Remove the hoses from test 

cocks No. 2 and No. 3.

  6.  Use the bypass hose (yellow) to relieve pressure from the test  

kit by opening needle valves A, B, and C and bleeding valves  

A and B.

  7.  Remove all test equipment and open No. 2 shutoff.

4

CAUTION

!

To prevent freezing, hold the test kit vertically to drain the differential 

gauge and hoses before placing the kit in the case. 
For additional testing information, refer to IS-TK-DL, IS-TK-9A, 

IS-TK-99E, or IS-TK-99D.

Test Procedure for Reduced Pressure Assembly

NOTICE

NOTICE

Содержание LF909-FS

Страница 1: ...ion A retrofit sensor connection kit is available for existing installations See Add on and Retrofit Sensor Connection Kits on the last page How It Operates The unique relief valve construction incorporates two channels one for air the other for water When the relief valve opens the right channel admits air to the top of the reduced pressure zone relieving the zone vacuum The left channel then dra...

Страница 2: ... or other equipment with periodic flow requirements discharge from the relief vent may occur due to water supply pressure fluctuation during static no flow conditions See Troubleshooting before installation Observe the direction of the flow arrows on the valve assembly The backflow preventer is designed so that the critical level of the relief valve is positioned below the first check This unique ...

Страница 3: ...ng A discharge line should be piped from the air gap at the relief valve connection making sure there is adequate drainage Never pipe the discharge line directly into a drainage ditch sewer or sump The assembly should never be installed where any part of the unit could become submerged in standing water Consideration should be given to the installation of external support structure as applicable I...

Страница 4: ...se needle valve A high red and open test cock No 2 2 Close test cock No 4 Disconnect the bypass hose yellow at test cock No 4 3 Open needle valves B low blue and C bypass yellow bleeding to atmosphere Then close needle valve B blue to restore the system to a normal static condition 4 Observe the pressure differential gauge If there is a decrease in the indicated value the No 1 check valve is repor...

Страница 5: ...is attached with a bayonet type locking arrangement 3 Holding the check valve module in both hands rotate the assembly quarter turn This disengages the disc assembly spring and seat cover into individual components 4 Clean and reassemble the disc assembly or depending upon its condition discard and replace it with a new assembly from the service kit O rings should be cleaned or replaced as necessa...

Страница 6: ...ver handy to reassemble the relief valve assembly Figure 2 Depress the assembly carefully guiding it against the 2 pound spring load When properly aligned the piston is in the cylinder bore Insert the screwdriver along the right channel wall positioning the screwdriver tip to the left of the relief valve O rings to hold the assembly in place Figure 3 Let go of the screwdriver and use both hands to...

Страница 7: ...ound the piping system and or electrically isolate the device with plastic pipe immediately upstream and down stream of the device Valve improperly reassembled If valve is dis as sem bled during installation exercise caution when reinstalling check springs in their proper location Valve exhibits high pressure drop Fouled strainer Clean strainer element or replace Valve too small for flows encounte...

Страница 8: ...ivation module with cable ground wire and power adapter Use this kit to activate the integrated flood sensor and enable flood detection capabilities on the relief valve of a new installation working with a BMS controller not included 88003058 FP RFK BF BMS CFS 1 11 2 BMS Sensor Retrofit Connection Kit Series LF909 Small Sizes to 1 Includes flood sensor sensor activation module with cable mounting ...

Отзывы: