3
Install the Flood Sensor and Sensor Activation Module
Attach the flood sensor and the sensor activation module to the backflow relief valve. For assemblies
with the integrated flood sensor, start at step 4.
The sensor activation module receives a signal from the flood sensor when a discharge is detected. If the
discharge meets the conditions of a qualifying event, the normally open contact is closed to provide a
signal to the Cellular Gateway input terminal.
Custom Flood Sensor Settings
The default settings on the sensor activation module for detecting discharge are
suitable for the assembly series. However, the DIP switches can customized for a
different wet threshold and time delay. Scan the QR code for more information.
1. Position the flood sensor on the relief valve.
2. For each side of the flood sensor, put the washer on the
head of the bolt, thread the bolt from the bottom, and
hand-tighten the nut to the bolt.
3. Use the two wrenches to tighten the bolts securing the
sensor to the valve.
4. Remove the dust cover from the sensor.
5. Press the sensor activation module onto the sensor.
6. Check that the module is fully seated to seal the O-ring and
to make electrical contact.
Retain the dust cover to protect the flood sensor when the
activation module needs to be removed or replaced.
NOTICE