Installation Instructions

Series 007 and LF007

1

2

" - 2" (15 - 50mm)

Service and Maintenance

Servicing the First and Second Check Valves

 

NOTICE

Before servicing, ensure supply water is turned off or shutoff valves

are in the closed position. 

Open test cocks #2, #3, and #4 to 

relieve pressure inside the valve prior to removing valve 

cover.

1.  Remove the cover, then remove the retainer from the body 

valve. The check valve modules can now be removed from the 

valve by hand or with a screwdriver. 

 

NOTICE

For Series 007 and LF007 sizes 

1

2

" - 2", the seats and springs of 

the first and second check modules are not interchangeable. The 

heavier spring and smaller diameter seat belong with the first check 

module. Series 007M1 sizes 

3

4

" - 1" and Series 007M2 

3

4

" (20mm) 

have interchangeable seats and springs.
2.  The check seats are attached to the cage with a bayonet type lock-

ing arrangement. Holding the cage in one hand, push the seat in-

ward and rotate clockwise against the cage. For 

3

4

" (20mm) Series 

007M2/LF007M2 and LF007 pull apart seat and cage. The seat, 

cage, spring and disc assembly are now individual components.

3.  The disc assembly may now be cleaned and reassembled or, 

depending on its condition, it may be discarded and replace with 

a new assembly from the repair kit. O-rings should be cleaned or 

replaced as necessary.

4.  Reassemble the check valve module in the reverse order. Check 

modules are installed in the valve body with the seats facing the 

valve inlet. The modules must be securely in place before the 

retainer can be replaced. On the 

3

4

" - 1" size, this retainer may 

have to be tilted slightly into place. 

Replace cover, and close 

all test cocks before returning the valve to service.

First 

Shutoff Valve

Strainer

007QT-S / LF007QT-S

WattsBox Insulated 

Enclosure

Available in Aluminum 

or Fiberglass.

For more information, 

send for ES-WB.

First 

Shutoff Valve

First Shutoff Valve

Figure 1

Figure 3

First Shutoff 

Valve

007QT-S/LF007QT-S 
Vertical flow-up installation

Strainer

007QT-S / LF007QT-S

Cover

Cover 

O-ring

Retainer

Body

First Check

Second Check

Seat

Seat 

O-ring

Disc 

Assembly

Spring

Check 

Cage

O-rings

Check 

Cage

Spring

Disc

Seat

Cover

Cover 

O-ring

Retainer

Body

Second Check

First Check

Parallel - 

Figure 3

Two or more Series 007 and LF007 smaller size valves may be 

piped in parallel (where approved) to serve a larger supply pipe 

main. This type of installation is employed whenever it is vital to 

maintain a continuous supply of water/where interruptions for test-

ing and servicing would be unacceptable. It also has the advantage 

of providing increased capacity where needed beyond that provided 

by a single valve and permits testing or servicing of an individual 

valve without shutting down the 

complete line.
For two valve installations the total capacity of the devices should 

equal or exceed that required by the system.
The quantity of valves used in parallel should be determined by 

the engineers judgement based on the operating conditions of a 

specific installation.

2

For repair kits and parts, refer to our Backflow 

Prevention Products Repair Kits & Service Parts 

price list PL-RP-BPD found on 

www.watts.com.