MASTER PROGRAMMING OPTIONS
Abbreviation
Parameter
Option Abbreviation
Options
DF
Display Format
GAL
Gallons
Ltr
Liters
VT
Valve Type
dF1b
Downflow/Upflow Single Backwash
dF2b
Downflow Double Backwash
Fltr
Filter
Ufbd
Upflow Brine First
Uftr
Upflow Filter
Othr
Other
CT
Control Type
Fd
Meter (Flow) Delayed
FI
Meter (Flow) Immediate
tc
Time Clock
dAY
Day of Week
NT
Number of Tanks
1
Single Tank System
2
Two Tank System
TS
Tank in Service
U1
Tank 1 in Service
U2
Tank 2 in Service
C
Unit Capacity
Unit Capacity (Grains)
H
Feedwater Hardness
Hardness of Inlet Water
RS
Reserve Selection
SF
Percentage Safety Factor
rc
Fixed Reserve Capacity
SF
Safety Factor
Percentage of the system capacity to be used as a reserve
RC
Fixed Reserve Capacity
Fixed volume to be used as a reserve
DO
Day Override
The system’s day override setting
RT
Regen Time
The time of day the system will regenerate
BW, BD, RR, BF
Regen Cycle Step
Times
The time duration for each regeneration step. Adjustable from
OFF and 0-199 minutes.
NOTE: If “Othr” is chosen under “Valve Type”, then R1, R2,
R3, etc, will be displayed instead
D1, D2, D3, D4, D5,
D6, & D7
Day of Week Settings
Regeneration setting (On or OFF) for each day of the week on
day-of-week systems
CD
Current Day
The current day of the week
FM
Flow Meter Type: All LC-100 systems
use a 1” Plastic Turbine Meter
P0.7
3/4" Paddle Wheel Meter
Gen
Generic or Other Meter
P2.0
2" Paddle Wheel Meter
t1.5
1.5" Turbine Meter
P1.5
1.5" Paddle Wheel Meter
t1.2
1.25" Turbine Wheel Meter
t1.0
1" Turbine Meter
P1.0
1" Paddle Wheel Meter
t0.7
3/4" Turbine Meter
K
Meter Pulse Setting
Meter pulses per gallon for generic/other flow meter
NOTE: Some items may not be shown depending on controller configuration. The controller will discard any changes and exit Master
Programming Mode if any button is not pressed for sixty seconds.