manualshive.com logo in svg
background image

DSBA3100 • Rév. 03/05/2019 

ENGLISH 

UK 

TECHNICAL DATA 

Type (1/4 turn electric actuator)  

ER20 

ER35 

ER60 

ER100 

Housing type 

Small housing (see p.13) 

large housing (see p.13) 

IP protection (EN60529) 

IP65 

Corrosion resistance (outdoor and 
indoor use) 

Housing: PA6  25% GF and cover: PA6 UL94V0  

Raw material  : 304L Stainless Steel or Steel + Zn treatment 

Temperature -10°C 

to 

+55°C 

Hygrometry 

maximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly  

to 50 % relative humidity at 40 °C 

Pollution degree 

Applicable  POLLUTION  DEGREE  of  the  intended  environment is 2 (in  most cases). 

Altitude 

altitude up to 2 000 m 

Extended environmental conditions  

Outdoor use and in WET LOCATION 

Sound level  

61 dB  

Weight 1 

Kg 2.1 

Kg 

MECHANICAL DATA 

Nominal torque 

20Nm 

35Nm 

60Nm 

100Nm 

1/4 turn travel time  

13s 

8s 

15s 

25s 

Mounting actuator base (ISO 5211) 

Star 14 

F03-F04-F05    

Star 22 

F05-F07   

Swing angle  

90° (others on request)  

Mechanical end stops 

90° +/- 5°  

Manual override 

Out axle  

Direction of rotation 

Anticlockwise to open 

Voltage  ±10% 

24V AC 50/60Hz or 100V to 240V AC 50/60Hz 

24V DC or 100V to 350V DC  

Frequency 50/60Hz 

 

Power consumption 

15W (0.08A) cos j = 0.75  

45W (0.15A) cos j = 0.75  

Overvoltage category 

 TRANSIENT OVERVOLTAGES up to the levels of OVERVOLTAGE CATEGORY ll 

TEMPORARY OVERVOLTAGES occurring on the MAINS supply 

Torque limiter 

Electric 

Duty cycle (CEI34) 

30%  

Limit switches maximal voltage 

4 to 250V AC/DC 

 (Overvoltage category II) 

Limit switches maximal current 

1mA to 5A max  

Electrical wiring 

1 ISO M20 cable gland and 1 DIN43650 3P+T connector  

Inrush current 

Circuit breaker type D, nominal current according the number of actuators (max. 4 actuators) or 

use a inrush current limiter at the output of the circuit breaker. 

ELECTRICAL DATA 

Содержание ER100

Страница 1: ...ER PREMIER Installation and Operation Manual UK 20Nm Facteur de marche 30 Duty cycle Indice de protection IP65 Enclosure protection Electric actuator ...

Страница 2: ...tion indicator 4 Emergency manual override 4 Dimensions 5 Electric wiring 6 Warnings Wiring Instructions Electric diagram Electronic boards Technical data 9 This product meets the European Directive 2012 19 UE about electrical and electronic equipment DEEE It mustn t be mixed with common waste Please recycle or dispose of them according to your country laws ...

Страница 3: ...bles batteries and adaptations are excluded from the guarantee In the case where a customer has not proceeded to pay ments within the agreed period our guarantee will be suspended until the delayed payments have been received and with the conse quence that this suspension will not prolong the guarantee period in any case All sales subject to our terms to be found on our website RETURN OF GOODS The...

Страница 4: ...uated Valve 0 180 2 way 0 close 90 open 3 way L 3 way T Ex T1 90 Emergency manual override The priority functioning mode of this actuator is electric Be sure than the power supply is switched off before using the manual override 1 Turn the knob to position MAN counter clockwise and hold it in position 2 Turn the outgoing drive shaft of the actuator with the help of an adjusting spanner 3 In order ...

Страница 5: ...4 plate Ou Or Sleeve 9 Nylon GF PA6 Housing Clutch knob 11 Square Star mm Depth mm 14 16 17 19 22 24 ISO F flange Diameter mm F03 36 F04 42 F07 70 M threaded Depth mm M5 14 2 M5 14 2 M8 16 4 Screws quantity 4 4 4 F05 50 M6 14 2 16 4 4 ER20 Star 14 mm ER35 60 100 Star 22 mm Handle for manual override ...

Страница 6: ...icated on the actuator ID label corresponds to the voltage supply Connect the wires to the connector in accordance with the required control mode see diagram p 15 To ensure the correct functioning of the anti condensation heaters the actuator must be permanently power supplied WIRING OF THE FEEDBACK SIGNAL Our actuators are equipped with two simple limit switch contacts normally set either in open...

Страница 7: ...gid feedback voltages 4 to 250V AC DC FEEDBACK COMMON FC1 FC2 FEEDBACK FC1 FEEDBACK FC2 1 2 3 ECD 1A Grey connector 9 8 7 6 5 4 1 2 3 SUGGESTED CUSTOMER WIRING N Open Close Ph N Open Ph Modulating 3 point control On off control TP PE TP PE 2 3 1 2 3 1 REP DESIGNATION FCO Open limit switch FC1 Auxiliary limit switch 1 FCF Close limit switch FC2 Auxiliary limit switch 2 POWER SUPPLY 3P T DIN43650 CO...

Страница 8: ...m torque stand by the actuator check that the actuator do not exceed the duty cycle indicated possible overheat To re start the actuator reverse the sense of rotation or switch the power off and on Electronic boards REP DESIGNATION REP DESIGNATION A Earth screw D LED 2 detected failure B Power supply and control terminal E LED 1 power supply presence C Protection fuses Power supply and Control boa...

Страница 9: ...100Nm 1 4 turn travel time 13s 8s 15s 25s Mounting actuator base ISO 5211 Star 14 F03 F04 F05 Star 22 F05 F07 Swing angle 90 others on request Mechanical end stops 90 5 Manual override Out axle Direction of rotation Anticlockwise to open Voltage 10 24V AC 50 60Hz or 100V to 240V AC 50 60Hz 24V DC or 100V to 350V DC Frequency 50 60Hz Power consumption 15W 0 08A cos j 0 75 45W 0 15A cos j 0 75 Overv...