TROUBLESHOOTING

FAULT/

SYMPTOM

CAUSE

RECTIFICATION

The desired 

mixed water 

temperature 

cannot be 

obtained 

or valve is 

difficult to 

set.

• Hot and cold supplies 

are fitted to the wrong 

connections

• Valve contains debris

• Strainers contain debris

• Non-return devices are 

damaged

• Top Cap and/or Piston 

O-rings are damaged

• 

Refit the valve with Hot/

Cold supplies fitted to the 

correct connections

• 

Clean the valve ensuring 

that all debris is removed 

and components are not 

damaged

• 

Clean strainers ensuring 

debris is removed

• Check non-return device 

is not jammed.Clean it if 

necessary

• Check Top Cap & Piston 

O-rings for damage. 

Replace if necessary

The valve 

will not shut 

down

• The hot to mix temperature 

differential is not 10°C or 

greater.

• 

The piston O-ring is 

damaged.

• Valve body seat (Hot Seat) 

is damaged or fouled by 

debris

• Cold seat (bottom surface 

of Top Cap) is damaged

• Thermostatic element has 

failed

• Plastic shuttle of 

Thermostatic element has 

been damaged by debris

• Raise hot water 

temperature.

• 

Replace piston O-ring

• 

Clean seat using mild 

descaling solution

• Replace top cap

• Replace element

Mix 

temperature 

unstable

• 

Debris is fouling valve.

• Flow rate below 4L/min.

• Strainers are fouled.

• 

Clean the valve ensuring 

that all debris is removed 

and components are not 

damaged

• Rectify any pressure 

deterioration.

• Clean strainers.

Mix  

temperature 

changing 

over time

• Inlet conditions (pressures 

or temperatures) are 

fluctuating.

• Strainers contain debris

• Install suitable pressure 

control valves to ensure 

inlet conditions are within 

those stated on page

 7.

• 

Clean strainers ensuring 

debris is removed

Содержание Enware Aquablend 1500

Страница 1: ...ware Aquablend 1500 Lead Free Thermostatic Mixing Valve with Thermal Flush Lift Lever For use in Australia ATM700 15mm Inlet with 15 20mm Outlet ATM714 20mm Inlet with 20 25mm Outlet I00516_05 Apr 202...

Страница 2: ...l Flush function allows controlled thermal flush to the TMV and warm water plumbing system Enware reserves the right to change any product specification or information contained in this publication at...

Страница 3: ...d Temperatures page 7 Flow Sizing Graph page 8 Installation page 9 Commissioning of the Valve page 11 Maintenance Servicing page 14 Thermal Flush page 16 Troubleshooting page 18 Spare Parts page 20 Co...

Страница 4: ...ined as per the recommendations outlined in this manual It should be noted however that this valve should not be considered as an alternative to adequate supervision and duty of care during its use an...

Страница 5: ...ection The inlet service fittings also incorporate union type fittings enabling the thermostatic mixing valve to be removed from its installation without disturbing its pipework AQUABLEND 1500 Product...

Страница 6: ...ment will extend or contract to match the water temperature it is exposed to causing the Piston to move thereby regulating the amounts of hot and cold water entering the valve This thermostatic mechan...

Страница 7: ...loss as per flow sizing graph DYNAMIC INLET PRESSURES Hot Cold Inlet Pressures For optimum operation it is recommended that the hot and cold water supply pressures be balanced within 10 for both stati...

Страница 8: ...re the water velocity in the pipework is within the allowed limit If the valve is to be installed and operated under unequal inlet pressures the lower inlet pressure determines the outlet flow rate Ho...

Страница 9: ...the valve is not installed correctly then it will not function correctly and may put the user in danger It may also void the warranty of the valve Prior to the installation of the valve the system mu...

Страница 10: ...correctly it is necessary that the pipework is thoroughly flushed with clean water before the valve is installed This will remove any physical contaminants from the pipework ensuring trouble free oper...

Страница 11: ...that is serviced by the shortest length of pipe work between the mixing valve and outlet fixture Allow the mixed outlet to flow for at least 60 seconds to allow the temperature to stabilise before ta...

Страница 12: ...again take a temperature reading Repeat the procedure until the desired temperature has been reached 5 Tighten the temperature adjustment locking grub screw SEE IMAGE 6 6 Push the top cover firmly bac...

Страница 13: ...store the cold water supply to the valve After the mixed water temperature has stabilised note the outlet temperature ensuring the outlet temperature has re established Repeat the above test except th...

Страница 14: ...wipedown The valve and surrounding area should be inspected for leaks or water damage and action taken if required Ensure a clean dry work area is available Cleaning the Strainers Firstly isolate the...

Страница 15: ...ecured 7 Turn the isolation tap on the HOT inlet back ON 8 To check Non Return Valve on the COLD inlet side repeat steps above using the COLD inlet side Check that the test plug in the top of the inle...

Страница 16: ...g and service requirements set out in AS4032 3 Before commencing the thermal flush a site specific procedure must be implemented to control the risk of scalding Hot water will run directly to the outl...

Страница 17: ...e set in the facility s Thermal Flush procedure has passed turn the hot water TMV inlet valve to the OFF position 9 Leaving the tapware outlet in the on position turn the cold water TMV inlet valve to...

Страница 18: ...ot to mix temperature differential is not 10 C or greater The piston O ring is damaged Valve body seat Hot Seat is damaged or fouled by debris Cold seat bottom surface of Top Cap is damaged Thermostat...

Страница 19: ...within 10 Mixed water temperature too hot or cold Valve has been tampered with Valve incorrectly set Inlet temperatures are not within specified limits Readjust valve to required set temperature Read...

Страница 20: ...Element and Piston Assembly ATMS1400L Red Lock Shield Top Cap Assembly Inlet Fitting O Ring pair ATMS202 Pressure Test Point Plug with Washer Each ATMS1314 OLD STYLE 5 YEAR SERVICE KIT ATMS242L Press...

Страница 21: ...ater Pressure kPa Temp C Temp C Cold Water Supply via Pressure Reducing Valve Fitted YES NO Make of Mixing Valve Model No Size Valve Location Building Valve ID No Total No of Mixing Valves on Site Bui...

Страница 22: ...Valve commissioned by Signature Licensed Plumber Lic Cert No Business name of Plumbing Contractor Contractors Authority No Date NOTE A duplicate copy of this report is to be retained at the site for a...

Страница 23: ...All req outlets in use 1 outlet in use All req outlets in use 1 2 3 4 5 6 7 8 Give details of brand and model designation Commensurate with the design flow rate for the mixing valve NOTE An accurate d...

Страница 24: ...ls Valve installed to requirements of The drawing specification The code of TMV s The code of TMV s The local water supply authority YES NO YES NO YES NO YES NO If NO give details and action taken Any...

Страница 25: ...ontractors Authority No Date NOTE A duplicate copy of this report is to be retained at the site for any inspection by authorised persons The following information is to be provided by site manager own...

Страница 26: ...ustralia and directions and requirements of local and other statutory authorities iii any parts or components not manufactured by the Supplier or otherwise not authorised by the Supplier are installed...

Страница 27: ...AND THE SUPPLIER SHALL NOT BE RESPONSIBLE FOR ANY INCIDENTAL SPECIAL OR CONSEQUENTIAL DAMAGES OR LOST PROFITS OR THE COST OF REPAIRING OR REPLACING OTHER PROPERTY WHICH IS DAMAGED IF THE PRODUCT DOES...

Страница 28: ...1300 369 273 info enware com au enware com au...

Отзывы: