THERMAL FLUSH OPTION
4. Hook the Lift Lever Key onto the thermal flush activation point
located in the centre of the temperature adjustment screw on
the valve’s top cap. SEE IMAGE 9
5. Lift the lever up and over all the way until it comes to a stop.
SEE IMAGE 9
6. Turn the hot water TMV inlet valve to the ON position.
7. Turn the tapware outlet to the ON position.
Note: full temperature hot water will flow from the
tapware. Care must be taken to prevent scalding.
8. Once the required time set in the facility’s Thermal Flush
procedure has passed, turn the hot water TMV inlet valve to
the OFF position.
9. Leaving the tapware outlet in the on position, turn the cold
water TMV inlet valve to the ON position.
10. Slowly pull the Lift Lever Key back to the original position.
11. Turn the hot water TMV inlet valve to the ON position.
12. Check the outlet flow, making sure it is within the required
temperature range.
13. Turn the tapware outlet off.
13. Re-fit the red lock shield to the TMV
NOTE:
If the Red Lock Shield does not securely fit back
to the top cap this indicates the thermal flush has not been
disengaged. Repeat Steps 9-13
The Lock Shield cannot be securely replaced while the Lift
Lever Key is in place.