12
- The ambient temperature
- If external sensor is connected: the outside temperature
If Parameter “
SenS
” is set on “
Air
”, the external sensor will be used as an outside temperature sensor
5.
Parameter’s menu
Your thermostat has a parameter’s menu, in order to enter in this menu, press and maintain the edition key
( )
during 5sec. Then
parameter menu will appear and first parameter screen will be displayed:
Now you can select a parameter which must be adjusted with the navigation keys
(
◄
)
or
(
►
)
, once the parameter chosen, toggle the
value with the
(OK)
key, modify it with
(-)
or
(+)
and confirm your adjustment with
(OK)
.
To leave the parameter menu, choose the parameter «
End
» and press
(OK)
.
N°
Default value & other possibilities
00
RF INI:
Radio configuration
Sends the radio link signal in order to assign this RF Thermostat with it’s RF receiver.
You also need to set simultaneously the receiver in radio configuration mode (On a simple receiver press and
maintain button until the green light lit’s up, see receiver leaflet)
01
dEG:
Unit of the temperatures displayed
°
C
Celsius
°
F
Fahrenheit
04
AirC:
Calibration of the internal probe
The calibration must be done after 1 day working with the same setting temperature in accordance with the
following description:
Put a thermometer in the room at 1.5M distance from the floor (like the thermostat) and check the real
temperature in the room after 1 hour.
When you enter on the calibration parameter “
no
” is displayed on the right to indicate no calibration has made.
To enter the value shown on the thermometer, use the
(-)
or
(+)
keys to enter the real value. Then, press
(Ok)
to
confirm.
The message “
Yes
” should be displayed; the value will be stored in the internal memory.
If you need to erase a calibration press on the escape key
( )
.
The old value will be erased and the message “
no
” will be displayed.
* Pay attention:
Only the heating element driven by the thermostat must be used during the complete step of the calibration.
05
OutC
,
AMbC
,
FlrC:
Calibration of the external wired probe
Same calibration method as described in parameter
“04 AirC” above.
06
HG:
Anti-freeze temperature used in Holiday mode
Default value 10°C.
Use the
(-)
or
(+)
keys to change the anti-freeze setting temperature. Then press
(Ok)
to confirm.
08
Clr ALL
: Reset to Factory setting
Press and maintain
(Ok)
key during 10s to reset Set points temperatures and user parameters in this menu to
factory default settings. User programs will also be resetted.
* Pay attention:
Ensure you that you have all necessary elements to re-setup your installation before to use this function.
09
Software version
VErS ___
10
End:
Exit the parameter’s menu
Press
(OK)
key to exit installation parameter menu and return to normal operation.