background image

 

3

 

ES-A-ACV-LF980GD-16  2115 

© 2021 Watts

Threaded = 400psi (27.6 bar)
150# Flanged = 250psi (17.2 bar)
300# Flanged = 400psi (27.6 bar) 
Grooved End = 400psi (27.6 bar)

Operating Pressure

M Series Basic Valves

Pump Control Valve with Mechanical Check Feature

Full Port Ductile Iron Dual Chamber Basic Valve with Mechanical Check Feature

1

X

3

6

3

2

X

X

Y/FC

Y/FC

4(L)

CLOSES VALVE

OPENS VALVE

FLOW

5

X

Globe Flanged

Angle Flanged 

Globe Threaded

Globe Grooved End

Angle Threaded

Angle Grooved End

Basic Valve Body Options 

Standard Materials

Body and Cover:

        Ductile Iron ASTM A536

Coating:

  

      NSF Listed Fusion Bonded Epoxy  

 

 

   Lined 

and 

Coated

Trim:

  

      316 Stainless Steel

Elastomers:

   

      Buna-N (standard) 

 

   EPDM 

(optional) 

 

   Viton™ 

(optional)

Nut, Spring and Stem:

   Stainless Steel

Anti-Scale (Optional):

     Xylan Coated Stem and Seat

Viton™ is a trademark of The Chemours Company FC, LLC

ACV Schematic - Series LF980GD-16 

This Ames ACV is a full port, dual chamber basic valve that incor-

porates a two-piece telescoping disc and diaphragm assembly. This 

assembly is the only moving part within the valve, allowing it to open 

or close as commanded by the pilot control system. The lower por-

tion of this two-piece assembly is a mechanical check feature, which 

acts independent of diaphragm position or pilot control system, and 

provides immediate check action when flow ceases. 
When pressure is applied to the upper diaphragm chamber and 

released from the lower diaphragm chamber, the valve travels to a 

closed position. When pressure is applied to the lower diaphragm-

chamber and released from the upper diaphragm chamber the valve 

travels to a full open position.
Ames ACV Main Valves are Lead Free. The Ames ACV piloting sys-

tem contains Lead Free* components, ensuring all of our configura-

tions are Lead Free compliant.
Globe Pattern Dual Chamber Basic Valve with Mechanical Check 

Feature (

900GD-16)

Angle Pattern Dual Chamber Basic Valve with Mechanical Check 

Feature (

900AD-16)

Operating Temperature

Buna-N: 160°F (71°C) Maximum
EPDM: 300°F (140°C) Maximum
Viton™: 250°F (121°C) Maximum
Epoxy Coating**: 225°F (107°C) Maximum

** Valves can be provided without internal epoxy coating consult factory  

Содержание AMES LF980GD-16 Series

Страница 1: ...with local codes and ordinances WARNING Need for Periodic Inspection Maintenance This product must be tested periodically in compliance with local codes but at least once per year or more as service...

Страница 2: ...mp is signaled to start the 4 Way Solenoid is energized and directs fluid and pressure into the power chamber below the diaphragm and relieves fluid and pressure from the cover chamber above the diaph...

Страница 3: ...his assembly is the only moving part within the valve allowing it to open or close as commanded by the pilot control system The lower por tion of this two piece assembly is a mechanical check feature...

Страница 4: ...ure Drop psi 2 3 4 6 8 10 20 30 40 60 80 100 Flow Rate Gallons per minute Water 2 4 10 20 40 60 80 100 200 500 1000 2000 5000 10000 20000 100000 8 6 1 4 1 6 1 2 1 0 8 6 4 3 2 1 2 2 1 2 1 0 8 6 4 3 2 1...

Страница 5: ...3 and Smaller ASTM A276 302 Stainless Steel 13A Bearing Retaining Ring 4 and Larger ASTM A276 302 Stainless Steel 14 Inner Bearing ASTM A276 304 Stainless Steel 15 O ring Buna N Nitrile 16 O ring Buna...

Страница 6: ...e 300 Angle Thread Angle 150 Angle 300 Port Size NPT Port Size NPT Port Size NPT Shipping Weights A B C D E F G H I J K L M in in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in in in lbs...

Страница 7: ...EPDM optional Viton optional Voltage 24VDC 24VAC or 120VAC Enclosure General Purpose NEMA 4 standard Explosion Proof NEMA 6 6P 7 9 optional Action 4 Way Actuation Solenoid Action only Main valve actio...

Страница 8: ...ve cover This causes the main valve to close until inlet pressure is again greater than outlet Standard Material Brass Housing and Body Stainless Steel Indicating Rod Optional Material Stainless Steel...

Страница 9: ...the valve opens or closes The adjustable collar is normally set to contact the trip arm when the main valve is closed The collar can be positioned on the stem by loosening the set screw to actuate the...

Страница 10: ...on In the free flow direction the seat moves out of the flow path to all unrestricted flow Specifications Standard Flow Control Large Flow Control FLOW FLOW CLOSED Fluid Speed Controlled by Needle FLO...

Страница 11: ...ilot circuit speed controls and pilots The filter element can be accessed for cleaning by removing the clean out cap or may be cleaned by installing an optional blow down ball valve The wetted surface...

Страница 12: ...re used in pilot lines to provide a positive shutoff in any override or maintenance situation for simple trouble shooting This 2 piece full port valve features bottom loaded stems PTFE seats and packi...

Страница 13: ...r Size 1 4 3 4 NPT Model LF60 Flo Clean Strainers are used to filter the fluid pass ing through the pilot circuit and provide protection to pilot circuit speed controls and pilots It is installed in t...

Страница 14: ...vel Body Material Stainless Steel Elastomers Buna N standard EPDM optional Viton optional Enclosure NEMA 1 3 4 and 13 General Purpose standard NEMA 1 7 and 9 Explosion Proof optional Electrical Form C...

Страница 15: ...ld be kept clean and replaced exactly as removed Consult appropriate hydraulic schematic to ensure proper re assembly 6 Connect solenoid wiring leads to desired switching device using safe standard el...

Страница 16: ...not flow until pump starts Pre set pilots as noted Opening and Closing Speed Prior to pump start actuate manual operator on solenoid to enable diaphragm assembly to stroke open and closed Observing t...

Страница 17: ...ure 2B increasing the rate of closing Figure 2 Flow Control Counterclockwise to INCREASE the rate of opening Clockwise to DECREASE rate of opening 2A 2B STEP 8 At valve closure booster pump will stop...

Страница 18: ...valve specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace di...

Страница 19: ...ation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembly corroded damaged Inspect stem assembly clean replace if necessary Blo...

Страница 20: ...examine stem threads for mineral build up Remove deposits with a fine wire brush Extreme care should be taken not to damage the finish on stem guiding surfaces when disassembling Avoid applying pipe...

Страница 21: ...oes not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances o...

Отзывы: