manualshive.com logo in svg
background image

2

Outdoor Installation

•   Before installing an assembly, flush the line thoroughly to 

remove all debris, chips, and other foreign objects. Failure to 

do so may make the assembly inoperable.

•   Series 2000SS and 3000SS backflow preventers are approved 

by ASSE (American Society of Sanitation Engineers) to be 

installed in horizontal or vertical positions as long as the flow 

indicator arrow in the assembly is pointed in the direction of 

water flow. Local water authorities must approve all installation 

configurations.

•   Allow sufficient clearance around the installed assembly to 

conduct testing, servicing, and inspection. Allow a minimum of 

12" from the flood level to the bottom of the assembly.

•   If the double check valve or double check detector assembly is 

installed in a vault or pit, be sure proper drainage is available. 

If sufficient drainage is not available a cross-connection may 

occur.

•   If installing on a protection system, be sure to purge air from 

the fire system. Fill the system slowly with all inspectors test 

valves open. 

•   The control valves on the OSY-TS model have integrated 

supervisory tamper switches that require connection to a fire 

alarm control panel.

Installation Guidelines

Indoor Installation

Vertical Installation ASSE

Wiring the Tamper Switch

The supervisory tamper switch consists of two SPDT switches, 

and is designed to send a signal when the valve is closed and 

when the switch is removed from the valve. In the neutral posi-

tion, the switch indicates the valve is fully open. Closing the valve 

causes the switch rod to come out of the valve stem groove, 

activating the switch. Removing the device also activates the 

switch.
Use the schematic diagram and the wiring notes for proper  

wiring of the tamper switch to the fire alarm control panel. (For 

more information refer to Tamper Switch Wiring Instructions at 

watts.com.)

CAUTION

!

Before wiring supervisory switches in fire protection systems, 

refer to the following standards:
NFPA 13: Standard for the Installation of Sprinkler Systems
NFPA 25: Inspection, Testing, Maintenance of Water-based Fire 

Protection Systems
NFPA 70: National Electrical Code
NFPA 72: National Fire Alarm Code
CSA C22.1 NO.1 Canadian Electrical Code, Part 1, Safety 

Standard for Electrical Installations Section 32
CAN/ULC-S524, Standard for Installation of Fire Alarm Systems

Wiring Notes

•  Connection to power limited circuitry is required.
•  The auxiliary switch is for supplemental use only and shall not 

be used for fire alarm signaling applications.

•  Switch functions are checked at the factory. Checking the 

switch after field installation is strongly advised. Check conti-

nuity with the valve fully open. Switch functions activate within 

two (2) turns from open.

WARNING

!

Metallic conduit required by NEC for proper grounding conduit 

joint must be sealed with a conductive sealant.
Install switch in accordance with National Electrical Code and/or 

local ordinances.
Wiring methods shall be in accordance with CSA C22.1, 

Canadian Electrical Code, Part 1, Safety Standard for Electrical 

Installations, Section 32 and CAN/ULC-S524, Standard for 

Installation of Fire Alarm Systems Assure All Devices Are Properly 

Grounded.

Отзывы: