Innovation Water Heaters 

– Edge [i] Controller

 

Electrical Power Design Guide 

 

 

 

  

TAG-0092   

•   GF-5066   •    9/6/2019                   Technical Support  •  (800) 526-0288  •  Mon-Fri, 8 am - 5 pm EST                  Page 

4

  of 

6

 

   

panels for maintenance.  The disconnect switch should be mounted near the unit as illustrated in 
Figure 1.  Wiring conduit, EMT, or other wiring paths should not be secured to the unit, but supported 
externally. Electricians should be instructed as to where the wiring conduit should be located, such as 
away from the relief valve discharge, drains, etc.  All electrical conduit and hardware should be 
installed so that it does not interfere with the removal of any cover, inhibit service or maintenance, or 
prevent access between the unit and walls or another unit. 

 

4

 

Unit Wiring

 

A dedicated protected circuit should be provided from the power source to the unit.  No other electrical 
devices should be permanently wired on the same circuit.  An emergency switch (electrical shutoff) 
must be in series with the power to the unit.  Refer to Figure 4 (120 VAC units) and Figure 5 (220 VAC 
units) 

for the wiring connections to the terminal block contained in the unit’s Power Box.  

 

 
 

Figure 4.  120 volt, Single Phase Wiring Schematic 

TERMINAL BLOCK IN 
POWER BOX 

DISCONNECT SWITCH 
SINGLE-POLE, 20 AMP 

12

0

 V

 1

 p

h

a

s

e

 

 

1 POLE 20 AMP 
CIRCUIT BREAKER 

GND  L2/N  L1 

120 VAC  1 PHASE 

 GND      L2/N    L1

 