background image

Innovation Water Heaters 

– Edge [i] Controller

 

Electrical Power Design Guide 

 

 

 

  

TAG-0092   

•   GF-5066   •    9/6/2019                   Technical Support  •  (800) 526-0288  •  Mon-Fri, 8 am - 5 pm EST                  Page 

3

  of 

6

 

   

 

 

           Power Box Shown With Cover Removed   

 

 

 

 

Figure 2.  Terminal Block Location 

 

2.1  220V Input Power  

Innovation-Edge units operate internally on 120 VAC power. All Innovation-Edge units that will 
connect to a 220 VAC power source must be ordered with a 220 VAC to 120 VAC transformer. This 
transformer is installed inside the unit, as shown in Figure 3. The 220 VAC electrical connection is 
made in the Power Box to the same terminals as 120 VAC connections are made (see Figure 2). The 
transformer is pre-wired to convert the power to 120 VAC. No further steps are needed. 

 

 

Figure 3.  220V Transformer 

– Front Frame & Panel and Side Panels Removed 

3

 

Provisions for Service

 

Designers must provide emergency shutoffs and other devices to satisfy electrical codes. It is also 
recommended to provide an electrical shutoff disconnect switch of suitable load carrying 
characteristics on or near each water heater. No electrical boxes or field components should be 
mounted to the surface of the unit or where they would interfere with the removal of the side or top 

POWER BOX 

TERMINAL BLOCK 
FOR 110 VAC 
UNITS 

220 VAC to 120 VAC 
TRANSFORMER 

NOTE

 

Terminal block will specify 220 
VAC for international units

 