Benchmark 750-6000 with Edge [i]: Install-Startup Manual
SECTION 2
– INSTALLATION
OMM-
144_B • GF-217 • 5/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
44
of
62
Figure 2-12a: BMK750/1000 Pump Relay Location
Figure 2-12b:
BMK1500
–
6000 Pump Relay Location (BMK2500/3000 Shown)
See Figures 2-13 and 2-14 for wiring details.
Figure 2-13: Schematic
– System Pump Start using Boiler Pump Relay
The Benchmark pump relay (SPDT) contact is rated for:
•
10 A Resistive @ 277 VAC/28 VDC
•
1/3 HP N/O @ 120/240 VAC
•
1/6 HP N/C @ 120/240 VAC
•
480 VAC Pilot Duty @ 240-277 VAC Pilot Duty
PUMP RELAY
(Orange)
– N/O
(Yellow) - COM
Heating Pump
Pump Relay Terminals
POWER BOX
PUMP RELAY
POWER BOX