Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 4
– INITIAL START-UP
OMM-0137_J
• 12/20/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
41
of
167
IT IS IMPORTANT TO PERFORM THE COMBUSTION CALIBRATION PROCEDURE BELOW
TO PROVIDE OPTIMUM PERFORMANCE AND KEEP READJUSTMENTS TO A MINIMUM
.
Figure 4-3: Gas Pressure Adjustment Screw and TAC Screw Location
WARNING:
Combustion calibration and AERtrim can both alter the voltage sent to the blower, and can
thus interfere with each other. If AERtrim is enabled, and a change is made to any calibration
point during combustion calibration, you must make a corresponding change to the same
calibration point in AERtrim (see Section 9.4:
AERtrim O
2
Sensor Auto Calibration
). If you fail
to make the change in AERtrim, AERtrim may ignore the combustion calibration value and
adjust the O
2
to the AERtrim value instead.
4.5.1 NATURAL GAS Manual Combustion Calibration
These instructions apply only to units running
NATURAL GAS
.
NATURAL GAS Manual Combustion Calibration Instructions
1. Ensure
the Edge Controller’s Enable/Disable switch is set to
Disable
.
2. Open the water supply and return valves to the unit and ensure that the system pumps are
running.
3. Open the
NATURAL GAS
supply valve to the unit.
4. Turn external AC power to the unit
ON
.
5. On the Controller, go to:
Main
Menu
→
Calibration
→
Manual Combustion
. If necessary,
enter a technician level password.
6. The first
Manual Combustion Calibration
screen appears. Complete the three steps
listed before continuing with the instructions below.
In addition
, if your unit is running
AERtrim, you must turn that feature off before continuing, as AERtrim will interfere with
combustion calibration.
BRASS HEX HEAD
(Remove to access
Gas Pressure
Adjustment Screw).
TAC SCREW