Benchmark Platinum 5000-6000 Valve Proving System (VPS)
P/N 24655 rev B, 5/4/2018
Item Qty Part #
Description
Item Qty Part #
Description
1
1
24629-5
VALVE PROVING SYSTEM ASSEMBLY
6
1
97087-48
FLEXIBLE GAS TUBE (NOT SHOWN)
2
1
33261
BRACKET, VPS SUPPORT
7
1
97087-26
FLEXIBLE GAS TUBE (NOT SHOWN)
The Benchmark gas train P/N
22308-4
operates in conjunction with a Valve Proving System.
This system monitors the gas pressure on both sides of the Actuator. If the pressure difference
falls below a fixed value, indicating the failure of the Actuator or leakage in the gas line, it
triggers the shutdown of the boiler.
Once the problem has been diagnosed and corrected, the Valve Proving System must be reset
by pressing the red
Reset
switch before the unit is restarted.
RED ALARM LIGHT & RESET SWITCH
1.
OFF
during normal operation
2.
ON
indicates a leak or Actuator
failure
YELLOW RUN LIGHT
1.
OFF
during normal operation
2.
ON
during valve proving operation
3.
ON
when unit is not running
2