Benchmark 5000-6000 Boiler Installation & Startup Manual
SECTION 6:
BOILER SEQUENCING TECHNOLOGY
OMM-0123_E
• GF-207 • 12/17/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
86
of
95
OPTION 5 - Remote Setpoint With Direct Wired Header Sensor And 4-20ma
Setpoint Drive Instructions
Step 3: Configure ALL C-More Units
On ALL Boilers:
1. Go to the
Configuration
menu and set the BST Menu item to
Enabled
.
2. Go to the Boiler Sequencing Menu and set the BST Mode item to
BST Client
(for now).
On MANAGER only:
3. Go to the BST Setpoint item and enter the Failsafe Setpoint.
4. Go to the BST Setup Menu item and set to
Enabled
.
5. Go to the BST Setpoint Mode item and select
Remote Setpoint
.
6. Go to the Head Temp Source item and select
FFWD Temp
.
7. Go to the BST Remote Signal and select either
4-20ma
or
0-20ma
.
When ALL C-More units have been configured:
8. Go to the Boiler Sequencing Menu of the Manager unit and set the BST Mode item to
BST
MANAGER
.