Benchmark Series Boilers Pre-Installation Electrical Power Guide 

 

 

TAG-0048_Q   

•   5/16/2023          Technical Support  •  (800) 526-0288  •  Mon-Fri, 8 am - 5 pm EST          Page 

7

  of 

11

 

 

4. BOILER WIRING 

A dedicated protected circuit, 

sized for the amperage values below

, should be provided to the boiler. 

No other electrical devices should be permanently wired on the same circuit. 

 

An emergency switch (electrical shutoff) must be wired in series with power to the unit. Connecting an 
emergency  shutoff  switch  (E-stop)  to  the  main  power  terminals  of  the  boiler  is  the  safest  way  to 
disable  and  un-power  the  unit.  Use  of  the  remote  interlock,  located  on  the  I/O  board,  is  not 
recommended since it does 

not

 cutoff power within the unit, it only disables it. Under no circumstance 

should the remote interlock of the BST Manager unit be used as an emergency switch for the plant. 

Multiple Unit Wiring:

 When multiple units are installed within the same mechanical spaces, electrical 

code requirements call for a single electrical shutoff for emergency use.  It is the responsibility of the 
electrical designer to comply with local codes and regulations affecting an individual installation. 

 

 

The following table lists the input power requirements for all Benchmark boilers, including the diagram 
number of each model’s corresponding schematic diagram: 

DOMESTIC UNITS 

INTERNATIONAL UNITS 

BMK Model  Diag. Voltage/Phase/Frequency   Amps Wires  Diag. Voltage/Phase/Frequency   Amps Wires 

750 

– 1000 

1a 

120V / 1

 / 60 Hz@  

15 A 

1b 

220V / 1

 / 50- 60 Hz 

20 A 

1500 

– 2000 

20 A 

 

 

 

 

2500/3000 

208V / 3

 / 60 Hz 

20 A 

 

 

 

 

3a 

480V / 3

 / 60 Hz 

15 A 

3b 

380-415V / 3

 / 50- 60 Hz 

15 A 

4000/5000N 

208 V / 3

 / 60 Hz 

40 A 

 

 

 

 

6a 

480V / 3

 / 60 Hz 

20 A 

6b 

380-415V / 3

 / 50- 60 Hz 

20 A 

5000/6000 

208V / 3

 / 60 Hz 

30 A 

 

 

 

 

5a 

480V or 575V / 3

 / 60 Hz 

20 A 

5b 

380-415V / 3

 / 50-60 Hz 

20 A 

For applicable wiring connections, refer to the schematic diagrams below. 

 

 

 

Diagram 1a - BMK750 

– 2000:  120 V / 1

 / 60 Hz Wiring Schematic 

– 3 Wire – DOMESTIC 

 120 V / 1

 / 60 Hz 

DISCONNECT SWITCH 

1 POLE 20 AMP 

1 POLE 20 AMP 

CIRCUIT BREAKER 

Содержание AERCO Benchmark BMK750-1000 Domestic

Страница 1: ...6000 Platinum Edge Reference Manual TAG 0019 Benchmark Boiler Application Guide TAG 0022 Benchmark Vent Combustion Air Guide TAG 0047 Benchmark Gas Guide TAG 0048_Q 5 16 2023 Benchmark Boilers Models...

Страница 2: ...necessary 2 BOILER ELECTRICAL REQUIREMENTS Benchmark boilers are available with the following power options BMK Model Voltage Phase Amperage BMK750 1000 Domestic 120 V 1 60 Hz 15 BMK750 1000 Internat...

Страница 3: ...ide TAG 0048_Q 5 16 2023 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 3 of 11 Figure 2a Power Box Components BMK750 1000 DOMESTIC TERMINAL BLOCKS FUSE BLOCKS 12V POWER SUPPLY TRANSFORMER...

Страница 4: ...Figure 3a Power Box Components BMK1500 2000 DOMESTIC TERMINAL BLOCKS FUSE BLOCKS POWER BREAKER 12V POWER SUPPLY TERMINAL BLOCKS POWER BREAKER FUSE BLOCKS 12 V POWER SUPPLY TRANSFORMER FLAME ROD SIGNAL...

Страница 5: ...INTERNATIONAL Figure 4a Power Box Components BMK2500 6000 DOMESTIC POWER BREAKER FUSE BLOCKS 12V POWER SUPPLY TRANSFORMER 24 VDC POWER SUPPLY FLAME ROD SIGNAL AMPLIFIER TERMINAL BLOCKS 12 V POWER SUP...

Страница 6: ...of the boiler or where they would interfere with the removal of the side or top panels for maintenance The service disconnect switch should be mounted near the unit as illustrated in Diagram 1 Wiring...

Страница 7: ...in the same mechanical spaces electrical code requirements call for a single electrical shutoff for emergency use It is the responsibility of the electrical designer to comply with local codes and reg...

Страница 8: ...2000 220 V 1 50 60 Hz Wiring Schematic 3 Wire INTERNATIONAL Diagram 2 BMK2500 5000N 380 415 V 3 50 60 Hz Wiring Schematic 4 Wire INTERNATIONAL Diagram 3 BMK5000 6000 208 V 3 60 Hz Wiring Schematic 4 W...

Страница 9: ...ng Schematic 4 Wire DOMESTIC Diagram 4b BMK5000 6000 380 415 V 3 50 60 Hz Wiring Schematic 4 Wire INTERNATIONAL Diagram 5a BMK4000 5000N 480 V 3 60 Hz Wiring Schematic 4 Wire DOMESTIC 480 V 3 60 Hz 3...

Страница 10: ...BMK5000N information where applicable Linley Thobourne Chris Blair 5 16 2023 Rev P Added diagram and description of E Stop power shutoff switch to Section 4 Added 208 V row to BMK 4000 5000N Domestic...

Страница 11: ...Benchmark Series Boilers Pre Installation Electrical Power Guide TAG 0048_Q 5 16 2023 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 11 of 11 AERCO International Inc 2023...

Отзывы: