Benchmark Series Boilers Pre-Installation Electrical Power Guide 

 

 

TAG-0048_Q   

•   5/16/2023          Technical Support  •  (800) 526-0288  •  Mon-Fri, 8 am - 5 pm EST          Page 

6

  of 

11

 

 

 

 

 

 

 

Figure 4b: Power Box Components, BMK2500 

– 6000 – INTERNATIONAL 

 

 

3. PROVISIONS FOR SERVICE 

Designers  must  provide  emergency  shutoffs  and  other  devices  to  satisfy  electrical  codes.  It  is  also 
recommended  to  provide  an  electrical  shutoff  disconnect  switch  of  suitable  load  carrying 
characteristics near each BMK boiler. No electrical boxes or field components should be mounted to 
the surface of the boiler or  where they would interfere with the removal of the side or top panels for 
maintenance.  The  service  disconnect  switch  should  be  mounted  near  the  unit,  as  illustrated  in 
Diagram 1. Wiring conduit, EMT, or other wiring paths should not be secured to the unit but supported 
externally. Electricians should be instructed as to where the wiring conduit should be located, such as 
away  from  the  relief  valve  discharge,  drains,  etc.  All  electrical  conduit  and  hardware  should  be 
installed so that it does not interfere with the removal of any covers, inhibit service or maintenance, or 
prevent access between the unit and walls or another unit.

 

 

 

TERMINAL 

BLOCKS 

POWER 

BREAKER 

FUSE 

BLOCKS 

12V 

POWER 

SUPPLY 

TRANSFORMER 

24 VDC 

POWER 

SUPPLY 

Содержание AERCO Benchmark BMK750-1000 Domestic

Страница 1: ...6000 Platinum Edge Reference Manual TAG 0019 Benchmark Boiler Application Guide TAG 0022 Benchmark Vent Combustion Air Guide TAG 0047 Benchmark Gas Guide TAG 0048_Q 5 16 2023 Benchmark Boilers Models...

Страница 2: ...necessary 2 BOILER ELECTRICAL REQUIREMENTS Benchmark boilers are available with the following power options BMK Model Voltage Phase Amperage BMK750 1000 Domestic 120 V 1 60 Hz 15 BMK750 1000 Internat...

Страница 3: ...ide TAG 0048_Q 5 16 2023 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 3 of 11 Figure 2a Power Box Components BMK750 1000 DOMESTIC TERMINAL BLOCKS FUSE BLOCKS 12V POWER SUPPLY TRANSFORMER...

Страница 4: ...Figure 3a Power Box Components BMK1500 2000 DOMESTIC TERMINAL BLOCKS FUSE BLOCKS POWER BREAKER 12V POWER SUPPLY TERMINAL BLOCKS POWER BREAKER FUSE BLOCKS 12 V POWER SUPPLY TRANSFORMER FLAME ROD SIGNAL...

Страница 5: ...INTERNATIONAL Figure 4a Power Box Components BMK2500 6000 DOMESTIC POWER BREAKER FUSE BLOCKS 12V POWER SUPPLY TRANSFORMER 24 VDC POWER SUPPLY FLAME ROD SIGNAL AMPLIFIER TERMINAL BLOCKS 12 V POWER SUP...

Страница 6: ...of the boiler or where they would interfere with the removal of the side or top panels for maintenance The service disconnect switch should be mounted near the unit as illustrated in Diagram 1 Wiring...

Страница 7: ...in the same mechanical spaces electrical code requirements call for a single electrical shutoff for emergency use It is the responsibility of the electrical designer to comply with local codes and reg...

Страница 8: ...2000 220 V 1 50 60 Hz Wiring Schematic 3 Wire INTERNATIONAL Diagram 2 BMK2500 5000N 380 415 V 3 50 60 Hz Wiring Schematic 4 Wire INTERNATIONAL Diagram 3 BMK5000 6000 208 V 3 60 Hz Wiring Schematic 4 W...

Страница 9: ...ng Schematic 4 Wire DOMESTIC Diagram 4b BMK5000 6000 380 415 V 3 50 60 Hz Wiring Schematic 4 Wire INTERNATIONAL Diagram 5a BMK4000 5000N 480 V 3 60 Hz Wiring Schematic 4 Wire DOMESTIC 480 V 3 60 Hz 3...

Страница 10: ...BMK5000N information where applicable Linley Thobourne Chris Blair 5 16 2023 Rev P Added diagram and description of E Stop power shutoff switch to Section 4 Added 208 V row to BMK 4000 5000N Domestic...

Страница 11: ...Benchmark Series Boilers Pre Installation Electrical Power Guide TAG 0048_Q 5 16 2023 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 11 of 11 AERCO International Inc 2023...

Отзывы: