SAFETY DEVICE TESTING
6-5
VALVE COVER
Figure 6.6
Air/Fuel Valve Cover Location
STEPPER
MOTOR
BURNER
BLOWER
169
170
171
172
IGNITION
POSITION
SWITCH
PURGE
POSITION
SWITCH
Figure 6.7
Air/Fuel Valve Purge and Ignition Switch
Locations
6.11 IGNITION SWITCH OPEN DURING
IGNITION
1. Set the unit’s ON/OFF switch to the off
position. Place the unit in manual mode and
set the fire rate between 25% and 30%.
2. Remove the air/fuel valve cover (Fig. 6.8) by
rotating the cover counterclockwise to
unlock it then pulling it towards you.
3. Disconnect one of the two wires from the
ignition position switch (Fig. 6.7) and start
the unit.
4. The unit should begin to start then shut
down and display
IGN SWITCH OPEN
DURING IGNITION.
5. Replace the wire on the ignition switch and
depress the
CLEAR
button. The unit should
restart.
6.12 SAFETY PRESSURE RELIEF
VALVE TEST
Test the Safety Pressure Relief Valve in
accordance with ASME Boiler and Pressure
Vessel Code, Section VI.