CONTROL PANEL OPERATING PROCEDURES
3-9
8. With the unit firing properly, it will be
controlled by the temperature controller
circuitry. The
FIRE RATE
will be continu-
ously displayed on the front panel bargraph.
DIAL
(DETAIL "A")
BURNER
BLOWER
DETAIL "A"
25
Figure 3-6.
Air/Fuel Valve In Ignition Position
Once the demand for heat has been satisfied,
the Control Box will turn off the gas valve. The
blower relay will be deactivated and the Air/Fuel
Valve will be closed.
Standby
will be displayed.
3.9. START/STOP LEVELS
The start and stop levels are the fire rate
percentages that start and stop the unit, based
on load. These levels are Factory preset as
follows:
•
Start Level:
20%
•
Stop Level:
16%
Normally, these settings should not require
adjustment