manualshive.com logo in svg
background image

3

Installation Guidelines

Series 909/LF909-FS can be installed in various way in various  

settings, as shown in Figure 3. Observance of these installation 

guidelines is important for each configuration.
•  Series 909/LF909-FS should be installed in a horizontal position 

with the relief valve port aimed downward. This positions the relief 

valve below the first check valve, enabling the zone to drain 

through the relief valve outlet. The shutoff valve with the test cock 

should be mounted on the inlet side of the backflow preventer. The 

test cock is on the inlet side of the shutoff valve.

•  Series 909/LF909-FS should always be installed in an accessible  

location to facilitate testing and servicing. Check the state and  

local codes to ensure that the backflow preventer is installed in 

compliance, such as the proper height above the ground.

•  

Water discharge from the relief valve should be vented in 

accordance with code requirements. The relief valve should 

never be solidly piped into a drainage ditch, sewer, or sump. 

The discharge should be funneled through a Watts air gap 

fitting piped to a floor drain.

•  Watts recommends installation indoors or above ground in an  

insulated enclosure.

 

NOTICE

Consult local authorities regarding acceptance of vertical installations.

•  At startup, the downstream shutoff should be closed. Open 

upstream slowly, fill the valve, and bleed the air through Test cock 

No. 2, No. 3, and No. 4. When valve is filled, open the downstream 

shutoff slowly and fill the water supply system. This is necessary to 

avoid water hammer or shock damage.

•  The installation of a Watts air gap with the drain line terminating 

above a floor drain handles any normal discharge or nuisance spit-

ting through the relief valve. However, floor drain size may need to 

be designed to prevent water damage caused by a catastrophic 

failure condition. Do not reduce the size of the drain line from the 

air gap fitting.

•  Two or more smaller size valves can be piped in parallel (when 

approved) to serve a larger supply pipe main. This type of installa-

tion is employed where increased capacity is needed beyond that 

provided by a single valve and permits testing or servicing of an 

individual valve without shutting down the complete line.

The number of assemblies used in parallel should be determined  

by the engineer’s judgment based on the operating conditions of a 

specific installation.

Indoors

Above Ground

Parallel

WattsBox Insulated Enclosures; for more information, send for ES-WB.

Min. 12" 

Strainer

Air Gap

Meter

Strainer

Main

Air 

Gap

12" 

support

Table 2. 

Total Capacity with Dual-valve Installations of Various Sizes

50 GPM

100 GPM

150 GPM

200 GPM

250 GPM

350 GPM

450 GPM

640 GPM

1000 GPM

2000 GPM

3000 GPM

5000 GPM

Two 

3

4

"

Two 1"

Two 1

1

4

"

Two 1

1

2

"

Two 1

1

2

"

Two 2"

Two 2

1

2

"

Two 3"

Two 4"

Two 6"

Two 8"

Two 10"

devices

devices

devices

devices

devices

devices

devices

devices

devices

devices

devices

devices

Figure 3. 

Series 909/LF909-FS in Different Installations,  

Sizes 2½" - 10"

Содержание 909 Series

Страница 1: ...on WARNING WARNING The installation and maintenance of backflow assemblies should be performed by a qualified licensed technician Failure to do so may result in a malfunctioning assembly Local building or plumbing codes may require modifications to the information provided You are required to consult the local building and plumbing codes prior to installa tion If the information provided here is n...

Страница 2: ... and local codes and meet the required safety provisions An air gap below the relief port must be maintained so as to avoid flooding and submersion of the assembly which may lead to a cross connection Figure 1 shows the primary components of the Series 909 LF909 FS Pipelines should be thoroughly flushed to remove foreign material before installing the unit A strainer should be installed ahead of t...

Страница 3: ...h Test cock No 2 No 3 and No 4 When valve is filled open the downstream shutoff slowly and fill the water supply system This is necessary to avoid water hammer or shock damage The installation of a Watts air gap with the drain line terminating above a floor drain handles any normal discharge or nuisance spit ting through the relief valve However floor drain size may need to be designed to prevent ...

Страница 4: ...all pressure differentials Close high valve A and open test cock No 2 Close test cock No 4 Disconnect vent hose at test cock No 4 Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pres sure differential gauge If there is a decrease in the indicated value check valve No 1 is reported as leaking Test No 4 Purpose To test oper...

Страница 5: ...e retainers Sizes 21 2 3 turn the seat by one quarter to remove it One wire is drawn out clockwise the other counterclockwise 4 Lift the seat ring straight up to remove it 5 To replace the disc on sizes 21 2 4 remove the retaining nut For sizes 6 10 remove the Allen head socket screws Reverse this procedure to install the new disc For further details contact your tech ni cal sales representative D...

Страница 6: ... assembly 5 Inspect the bottom plug and spring assembly During normal field service there is no need to remove this assembly other than inspection Unscrew the assembly with a large pipe wrench CAUTION The spring is retained on the bottom plug and is highly loaded NO attempt should be made in the field to disassemble the bottom plug and spring piston assembly For replacement a complete bottom plug ...

Страница 7: ...m and or electri cally isolate the device with plastic pipe immediately upstream and down stream of the device B 6 Valve improperly reassembled B 6 If the valve is dis as sem bled during installation exercise caution when installing check springs in their proper location C Valve exhibits high pressure drop C 1 Fouled strainer C 1 Clean strainer element or replace C 2 Valve too small for flows enco...

Страница 8: ...55 4122 0138 Watts com Part Number Add On Retrofit Kit Description Add on and Retrofit Sensor Connection Kits for BMS 88003050 BMS Sensor Connection Kit for LF909 FS Sizes 2 to 10 Includes a sensor activation module with cable power adapter and ground wire Use this kit to activate the integrated flood sensor and enable flood detection capabilities for the relief valve to work with a third party BM...

Страница 9: ...DVERTENCIA La instalación y el mantenimiento de los ensambles de reflujo deben ser realizados por un técnico calificado y autorizado El no hacerlo puede resultar en un ensamble defectuoso Las reglamentos locales de construcción o plomería pueden requerir modificaciones a la información proporcionada Debe consultar los reglamentos locales de construcción y plomería antes de realizar la instalación ...

Страница 10: ...ientos de instalación deben cumplir con todos los códigos estatales y locales y cumplir con las disposiciones de seguridad requeridas Debe mantenerse un espacio de aire debajo del puerto de alivio para evitar inundaciones e inmersiones del ensamble lo que puede provocar una conexión cruzada La Figura 1 muestra los componentes principales de la serie 909 LF909 FS Las tuberías deben lavarse a fondo ...

Страница 11: ...es necesario para evitar golpes de ariete o daños por golpes La instalación de un accesorio de espacio de aire Watts con la línea de drenaje terminando sobre un desagüe en el piso maneja cualquier descarga normal o escupida molesta a través de la válvula de alivio Sin embargo es posible que sea necesario diseñar el tamaño del desagüe del suelo para evitar daños por agua causados por una condición ...

Страница 12: ...e la válvula alta A y abra la válvula de prueba N º 2 Cierre la válvula de prueba N º 4 Desconecte la manguera de aireación en la válvula de prueba N º 4 Abra las válvulas B y C purgando al ambiente A continuación el cierre de la válvula B restaura el sistema a una condición estática normal Observe el manómetro diferencial de presión Si hay una disminución en el valor indicado la válvula de retenc...

Страница 13: ... Un alambre se extrae en el sentido de las agujas del reloj el otro en sentido antihorario 4 Levante el anillo del asiento hacia arriba para retirarlo 5 Para reemplazar el disco en tamaños de 21 2 in a 4 in 6 35 cm a 10 16 cm retire la tuerca de retención Para tamaños de 6 in a 10 in 15 24 cm a 25 4 cm retire los tornillos Allen Siga este procedimiento en orden inverso para instalar el nuevo disco...

Страница 14: ...sario retirar este ensamble más que para la inspección Desenrosque el ensamble con una llave para tubos grandes PRECAUCIÓN El resorte está retenido en el tapón inferior y está muy cargado NO se debe intentar en el campo desmontar el tapón inferior y el ensamble del pistón del resorte Para el reemplazo debe obtenerse de fábrica un ensamble del tapón inferior completo Para obtener más información pó...

Страница 15: ...sistema de tuberías y o aísle eléctricamente el dispositivo con una tubería de plástico inmediatamente aguas arriba y aguas abajo del dispositivo B 6 Válvula reensamblada incorrectamente B 6 Si la válvula se desmonta durante la instalación tenga cuidado al instalar los resortes de retención en su ubicación correcta C La válvula muestra una caída de presión alta C 1 Filtro sucio C 1 Limpie el eleme...

Страница 16: ... del sensor con cable adaptador de corriente y cable de tierra Use este kit para activar el sensor de inundación integrado y habilitar las capacidades de detección de inundaciones para que la válvula de alivio funcione con una caja de control BMS de terceros no incluida 88003051 Kit de conexión de retroadaptación del sensor BMS para tamaños LF909 de 2 in a 3 in 6 35 cm a 7 62 cm Incluye un sensor ...

Отзывы: