AERCO ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX B: AERCO Equipment Monitor and Control Point Definitions
Page
48
of
108
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0107_0B
03/07/2017
Ph.: 800-526-0288
GF-150
Appendix B-2: AERCO Electronic Control System (ECS) Point Definitions
Point
Name
BAS
Modbus
Data
Address
GF-108, GF-
124, GF-114
Point Name
Reg.
Type
Modbus
Data
Address
(Hex/Dec.)
Units (Range)
Electric Valve (ECS) and SmartPlate
Cntl Output
Signal
30004
OP (Control Output
Signal)
Input
0x0003 / 3
% (0 to 100)
Setpoint
30006
w.SP (Setpoint)
Input
0x0005 / 5
°F (40 to 180)
RmSetpt
40027
Remote Input
Comms Access
parameter(Setpoint)
Holding
0x001A / 26
°F (40 to 180)
Outlet
Temp
30002
Top Value (Outlet
Temp)
Input
0x0001 / 1
°F (40 to 205)
FBk Sensor
Temp
30290
Li1 (Feedback
Sensor Temp)
Input
0x0121 / 289
°F (40 to 180)
Over Temp
Alarm
30075
AL 1 (Over Temp
Alarm)
Input
0x004A / 74
Bit 0 = Alarm 1 State (0 = Safe 1 = Alarm).
Bit 1 = Alarm 2 State (0 = Safe 1 = Alarm).
Bit 2 = Alarm 3 State (0 = Safe 1 = Alarm).
Bit 3 = Alarm 4 State (0 = Safe 1 = Alarm).
Bit 4 = Manual Mode (0 = Auto 1 = Manual).
Bit 5 = Sensor Break (0 = Good PV 1 =
Sensor Broken.
Bit 6 = Loop Break (0 = Good closed loop 1
= Open Loop).
Bit 7 = Heater Fail (0 = No Fault 1 = Load
fault detected).
Flow Rate
/Mixed
Temp
30291
Li2 (Flow)
Input
0x0122 / 290
GPM
Appendix B-3: AERCO (Modulex) BCM Point Definitions
Appendix B-3:
AERCO (Modulex) BCM Point Definitions
Point Name
BAS
Modbus
Data
Address
GF-108,
GF-124,
GF-114
Point Name
Reg.
Type
Modbus Data
Address
(Hex/Dec.)
Units (Range)
Modulex Boiler with BCM
Act Mod Lev
(Actual Modulation
Level)
41009
Global Actual
Modulation Level
Holding
0x03F0 / 1008
% (0 to 100)
Target Setpoint
41019
Target Setpoint
Holding
0x03F8 / 1016
°F (32 to 185) (Value x 10)
Req Outlet Temp
(Requested Outlet
Temp)
41005
Requested
Setpoint
Holding
0x03EC / 1004
°F (32 to 185) (Value x 10)
Net Direct Drive
40002
Direct Drive
Requested
Modulation Level
Holding
0x0001 / 1
% (0 to 100)
Mod Lev In
(Modulation Level In)
41201
Monitor Only
Global Modulation
Level
from Cascade
Manager
Holding
0x04B0 / 1200
% (0 to 100)
Flow Sens Temp
(Flow Sensor
Temperature)
41003
Flow Sensor
Temperature
Holding
0x03EA / 1002
°F (14 to 212) (Value x 10)