Installation and Maintenance Instructions
(Brackets refer to item number)

Principles of Operation

When the water supply is cut in, the valve is in wide open posi-

tion.  Water flowing to the system creates a rising delivery pres-

sure which feeds back through the control ports to the underside 

of diaphragm (8).  As the pressure on diaphragm (8) approaches 

a balance with the force exerted by adjusting spring (5), disc (20) 

is throttled to a position where just enough water flows to main-

tain the set delivery pressure.

Installation

Carefully clear inlet piping system of foreign matter and mount 

regulator with the flow arrow pointing in the direction of flow.  

Preferred position for 2300 valves is in a horizontal line with 

spring chamber up.  When so mounted, the tendency of sedi-

ment to settle in the control ports is practically eliminated.
Provide a three-valve bypass to facilitate inspection of the reduc-

ing valve without interrupting service.  Avoid damaging effects of 

foreign matter in the flow by using a strainer ahead of the valve.
This valve should be installed where it is accessible with sufficient 

clearance for cleaning, service or adjustment.

Operation

On starting up, proceed as follows:
1.  Open the inlet stop valve gradually until the reducing valve 

 

takes control as indicated by the delivery pressure gage.

2.  Turn adjusting screw (1) clockwise to increase the delivery 

 

pressure, counterclockwise to lower it.

CAUTION:

  Any time a reducing valve is adjusted, the use of a 

pressure gauge is recommended to verify correct pressure set-

ting.  Do not bottom out adjusting screw on spring chamber.

Troubleshooting

Inadequate flow or delivery pressure:
1.  Check initial pressure to see if full intended line pressure is 

 

applied at the valve inlet.

Reduced pressure builds up:
1.  Foreign matter may be lodged between disc (20) and seat ring 

(19).  Remove blind flange (24) to inspect.

2.  Diaphragm (8) may be ruptured.  Remove spring chamber (4) 

to inspect.

3.  Sealing ring (16) may be damaged.  See dismantling  

 

instructions below to replace.

Erratic Operation

Complete dismantling is recommended.
1.  Check for clogged control ports connecting body outlet with   

diaphragm chamber.

2.  Check for deposits causing sticking of sealing ring (16) or stem 

(14) in their respective guides.

Dismantling

To change or inspect composition disc or sealing ring:
1.  Remove blind flange (24).
2.  Remove stem nuts (22).  Keep stem from turning by inserting   

screw driver in slot on end of stem.

3.  Disc holder (21) will drop out.  Carefully remove balance pis-

ton (18) so as not to damage sealing ring (16) as it is pulled 

through seat ring (19).

To examine diaphragm or stem:
1.  Remove compression from spring by turning adjusting 

screw (1) counterclockwise.

2.  Remove diaphragm bolts (9) and lift off spring chamber 

(4).

3.  Lift pressure plate (7) to withdraw diaphragm and stem 

from valve.

4.  To examine diaphragm, disassemble coupling nut (6) and 

lift off pressure plate (7).

Valve Setting

Should the threaded connection between stem coupling 

(11) and stem (14) be disturbed, proceed as follows:
1.  Insert stem assembly (A) and hold disc on seat ring in 

closed position, as shown.

2.  Screw stem coupling (B) on stem until travel setting T is 

reached.

3.  Remove stem assembly (A) and lock setting by drilling 

hole drilling hole and inserting dowel pin (C).

NOTE:  Annual inspection of the rubber components 

and control parts is recommended to ensure proper 

operation.

 

Valve Size

 

3 4 

 

Dimension T

 

3

16

 

17

64

 

DIMENSION ‘T’

Содержание 2300 Series

Страница 1: ...ENTS Cv DIMENSIONS inches AND WEIGHTS pounds ENGLISH INSTRUCTIONS Local building or plumbing codes may require modifica tions to the information provided You are required to consult the local building...

Страница 2: ...ooting Inadequate flow or delivery pressure 1 Check initial pressure to see if full intended line pressure is applied at the valve inlet Reduced pressure builds up 1 Foreign matter may be lodged betwe...

Страница 3: ...te 2 Stainless Steel 12 Diaphragm Nut Steel 13 Dowel Pin Note 2 Steel 14 Stem Note 2 Stainless Steel 15 Body ANSI NPT Scr Cast Iron Body ANSI 125 Fig Cast Iron Body ANSI 250 Cast Iron 16 Sealing Ring...

Страница 4: ...SS OR IMPLIED THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURP...

Страница 5: ...108 lb 58 kg 128 lb 4 100 301 mm 117 8 pulg 318 mm 121 2 pulg 168 mm 65 8 pulg 672 mm 265 8 pulg 286 mm 111 4 pulg 90 kg 198 lb 102 kg 225 lb ADVERTENCIA Los c digos locales de construcci n o fontaner...

Страница 6: ...a indicada en la entrada de la v lvula Se acumula presi n reducida 1 Puede haber materia extra a entre el disco 20 y el anillo de asiento 19 Quite la brida ciega 24 e inspeccione 2 Puede estar roto e...

Страница 7: ...si n Nota 2 Hierro fundido 8 Diafragma Nota 1 2 Hycar 9 Pernos del diafragma Acero 10 Base Hierro fundido 11 Acoplamiento del v stago Nota 2 Acero inoxidable 12 Tuerca del diafragma Acero 13 Pasador g...

Страница 8: ...TALES APLICABLES LAS GARANT AS IMPL CITAS QUE NO PUEDAN DESCONOCERSE INCLUIDAS LAS GARANT AS IMPL CITAS DE COMERCIALIZACI N O APTITUD PARA UN FIN ESPEC FICO EST N LIMITADAS EN SU DURACI N A UN A O DES...

Страница 9: ...m 265 8 po 286 mm 111 4 po 90 kg 198 lb 102 kg 225 lb Les codes locaux du b timent ou de la plomberie peuvent n cessiter des modifications aux renseignements donn s Vous tes tenus de consulter des cod...

Страница 10: ...au niveau du robinet d admission Accumulation de r duction de pression 1 Des corps trangers peuvent tre log s entre le disque 20 et la bague de si ge du corps 19 Enlever la bride pleine 24 pour inspe...

Страница 11: ...pression Remarque 2 Fonte 8 Membrane Remarque 1 et 2 Hycar 9 Boulons de membrane Acier 10 Base Fonte 11 Raccord de tige Remarque 2 Acier inoxydable 12 crou de membrane Acier 13 Goupille Remarque 2 Aci...

Страница 12: ...FRE AUCUNE AUTRE GARANTIE EXPRESSE OU TACITE PAR LA PR SENTE LA SOCI T REJETTE SP CIFIQUEMENT TOUTE AUTRE GARANTIE EXPRESSE OU TACITE NOTAMMENT TOUTE GARANTIE TACITE DE QUALIT MARCHANDE OU D ADAPTATIO...

Отзывы: