Figure 3

2

NOTICE

Shutoff Valves:

 When shutoff valves are removed and re as sem-

bly is necessary, the shutoff valve with the test cock is to be 

mount ed on the inlet side of the backflow preventer. 

A.  The assembly should always be installed in an accessible location 

to facilitate testing and servicing. 

Check the state and local 

codes to ensure that the backflow preventer is installed in 

compliance, such as the proper height above the ground.

B.   Watts recommends that a strainer be installed ahead of the 

assembly to protect the internal components from unnecessary 

fouling. 

 

CAUTION

!

   Do not add a strainer when the backflow preventer is installed on 

seldom-used water lines, such as fire sprinkler lines or other lines 

called upon only during emergencies. 

Start Up:

 The down stream shutoff should be closed. Open the 

upstream shutoff slowly and fill the valve. When the valve is filled, 

open the downstream shutoff slowly and fill the water supply sys-

tem. This is necessary to avoid water hammer or shock damage. 

C.  Water discharge from the relief valve should be vented in ac cor-

dance with code requirements. The relief valve should never be 

solidly piped into a drainage ditch, sewer, or sump. The discharge 

should be terminated approximately 12" above the ground or 

through an air gap piped to a floor drain. 

Parallel

Two or more smaller-sized assemblies can be piped in parallel (when 

approved) to serve a large supply pipe main, as shown in Figure 3. 

This type of installation is employed where in creased capacity is need-

ed beyond that provided by a single valve and permits testing or ser-

vicing of an individual valve without shutting down the complete line.
The number of assemblies used in par al lel should be determined 

by the en gi neer’s judgment based on the operating con di tions of a 

specific installation.
For parallel valve installations, the total capacity of the assemblies 

should equal or exceed that required by the system.

Outside

In an area where freezing conditions do not occur, the assembly 

can be installed outside. The most sat is fac to ry in stal la tion is above 

ground; thus, the assembly should be in stalled in this manner.
Backflow preventers should not be installed in pits unless approved 

by local codes. In such cases, a modified pit installation is preferred.

Figure 2

WattsBox

12"

NOTICE

In an area where freezing conditions can occur, the assembly 

should be installed above ground in an insulated enclosure, as 

shown in Figure 2. (For more information, download the ES-WB 

specification at watts.com.)
The assembly must be installed in an ac ces si ble location to facilitate 

testing and ser vic ing. A discharge line should be piped from the air 

gap at the relief valve con nec tion to ensure there is adequate drain-

age. Never pipe the discharge line directly into a drainage ditch, 

sewer, or sump. Never install the assembly where any part of the 

unit could become submerged in standing water. 

Annual Inspection

Annual inspection of all water system safety and control valves is 

required and necessary. Regular inspection, testing, and cleaning 

assures maximum life and proper product function.

NOTICE

Relief Valve Discharge Rates

The installation of an air gap with the drain line terminating above 

a floor drain handles any normal discharge or nuisance spitting 

through the relief valve. However, floor drain size may need to be 

designed to prevent water damage caused by a cat a stroph ic fail-

ure condition. See Figure 4 for maximum relief valve discharge 

rates, size, and capacity of typical floor drains. 

Do not

 reduce the size of the drain line from the air gap fitting. 

Pipe full line size.

D.  After initial installation, a discharge from the relief valve opening 

may occur due to inadequate initial flushing of pipe lines to elimi-

nate dirt and pipe compounds. If flush ing does not clear, remove 

the first check valve and clean thoroughly. 

NOTICE

Periodic relief valve discharge may occur on dead end service 

applications, such as boiler feed lines or cooling tower makeup 

lines due to fluctuating supply pressure during a static or no flow 

condition. To avoid this discharge, install a spring-loaded rubber 

seated check valve ahead of the backflow assembly to “lock-in

 

the downstream pressure. 

E.  Backflow preventers should never be placed in pits unless ab so-

lute ly necessary and then only when and as approved by local 

codes. In such cases, provision should be made to always vent 

above flood level or for a pit drain to ensure an adequate air gap 

below the relief port.

Содержание 009 Series

Страница 1: ...effective for the service intended Regular checking and cleaning of the product s internal components helps assure maximum life and proper product function WARNING Read this Manual BEFORE using this e...

Страница 2: ...ner Backflow preventers should not be installed in pits unless approved by local codes In such cases a modified pit installation is preferred Figure 2 WattsBox 12 NOTICE In an area where freezing cond...

Страница 3: ...erated Certified testers of backflow assemblies must conduct this confirming test F The backflow preventers must be inspected periodically for any discharge from the relief valve which provides a visu...

Страница 4: ...removed if necessary for cleaning The disc can be cleaned without disassembly of the relief valve module If it is determined that the relief valve diaphragm and or disc should be replaced the relief v...

Страница 5: ...ules are not in ter change able The heavier spring and smaller diameter seat belong with the first check module 3 The check seats are attached to the cage with a bayonet type locking arrangement Holdi...

Страница 6: ...nd wire and power adapter Use this kit to activate the integrated flood sensor and enable flood detection capabilities on the relief valve of a new installation working with a BMS controller not inclu...

Страница 7: ...munication to send alerts by email message SMS text message or voice call 88003062 FP RFK BF CFS 1 11 2 Cellular Sensor Retrofit Connection Kit Series 009 LF009 LFU009 SS009 U009 Sizes 1 to 1 Includes...

Страница 8: ...if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any othe...

Отзывы: