WattNode T-WNB-3Y-208 Скачать руководство пользователя страница 6

WattNode Pulse Output kWh Transducer Connection Instructions 

Page 6 of 7

 

For best accuracy, we recommend connecting the 

N

 (neutral) terminal to earth ground. This is not necessary on balanced 

three-phase circuits, where the ground-to-phase A, ground-to-phase B, and ground-to-phase C voltages are all roughly the 
same. This will not cause ground current to flow because the neutral terminal is not used to power the WattNode. 

 

Figure 6: Three-Phase Three-Wire Delta (No Neutral) Connection 

Recommended WattNode Models 

The following table shows the WattNode model that should be used, depending on the line to neutral voltage and line to line 
voltage (also called phase to phase voltage). 

Line to Line Voltage 

WattNode Model 

208 - 240 VAC 

WNB-3D-240-P 

480 VAC 

WNB-3D-480-P 

Grounded Leg 

In rare cases, one of the phases may be grounded. You can check for this by using a multimeter (DMM) to measure the 
voltage between each phase and ground. If you see a reading between 0 and 5 VAC, that leg is probably grounded. 

The WattNode will correctly measure circuits with a grounded leg, but the measured voltage and power for the phase will be 
zero and the status LED will not light for whichever phase is grounded, because the voltage is near zero. Also, one or both of 
the active (non-grounded) phases may show yellow or red/yellow LED flashing because the grounded leg configuration 
results in unusual power factors. 

For optimum accuracy with a grounded leg, you should also connect the 

N

 (neutral) terminal on the WattNode to the ground 

terminal; this will not cause any ground current to flow because the neutral terminal is not used to power the WattNode. If 
you have a grounded leg configuration, you can save money by removing the CT for the grounded phase, since all the power 
will be measured on the non-grounded phases. We recommend putting the grounded leg on the 

ØC

 (Phase C) input and 

attaching a note to the WattNode indicating this configuration for future reference. 

Shop for Data Logging products online at:   

www.

DataLoggerStore

.ca   

1.800.561.8187

Содержание T-WNB-3Y-208

Страница 1: ...kWh transducer to the power source and other transducer details refer to the WattNode documentation provided by Continental Control Systems Required Selected WattNode Pulse Output kWh Transducer Appr...

Страница 2: ...UX120 terminal block to P1 Output P3 P2 P1 COM Customer supplied 22 AWG twisted pair HOBO UX90 001 M Data Logger Output P3 P2 P1 COM White Black Red wire not used CABLE 2 5 STEREO Red wire not used Fi...

Страница 3: ...be used depending on the line to neutral voltage Line to Neutral Voltage WattNode Model 120 VAC WNB 3Y 208 P Single Phase Three Wire This configuration is seen in North American residential and comme...

Страница 4: ...this configuration the WattNode is powered from the A and B phase A and phase B terminals For best accuracy we recommend connecting the WattNode N neutral terminal to earth ground This will not cause...

Страница 5: ...e Models The following table shows the WattNode model that should be used depending on the line to neutral voltage and line to line voltage also called phase to phase voltage Line to Neutral Voltage L...

Страница 6: ...and ground If you see a reading between 0 and 5 VAC that leg is probably grounded The WattNode will correctly measure circuits with a grounded leg but the measured voltage and power for the phase will...

Страница 7: ...d P3 Output P3 P2 P1 COM Connect to pulse port Customer supplied 22 AWG twisted pairs HOBO H21 H22 or U30 Series Data Logger H22 001 shown HOBO UX120 Series Data Logger HOBO ZW Series Wireless Data No...

Отзывы: