WattNode Pulse Output kWh Transducer Connection Instructions 

Page 3 of 7 

Single-Phase Two-Wire with Neutral 

This configuration is most often seen in homes and offices. The two wires are neutral and line. For these models, the 
WattNode is powered from the 

N

 and 

ØA

 terminals. 

 

Figure 2: Single-Phase Two-Wire Connection 

Recommended WattNode Model 

The following table shows the WattNode model that should be used, depending on the line to neutral voltage.

 

Line to Neutral Voltage 

WattNode Model 

120 VAC 

WNB-3Y-208-P 

Single-Phase Three-Wire 

This configuration is seen in North American residential and commercial service with 240 VAC for large appliances. The 
three wires are neutral and two line voltage wires with AC waveforms 180° out of phase; this results in 120 VAC between 
either line wire (phase) and neutral, and 240 VAC (or sometimes 208 VAC) between the two line wires (phases). 

 

Figure 3: Single-Phase Three-Wire Connection 

Shop for Data Logging products online at:   

www.

DataLoggerStore

.ca   

1.800.561.8187

Содержание T-WNB-3Y-208

Страница 1: ...kWh transducer to the power source and other transducer details refer to the WattNode documentation provided by Continental Control Systems Required Selected WattNode Pulse Output kWh Transducer Appr...

Страница 2: ...UX120 terminal block to P1 Output P3 P2 P1 COM Customer supplied 22 AWG twisted pair HOBO UX90 001 M Data Logger Output P3 P2 P1 COM White Black Red wire not used CABLE 2 5 STEREO Red wire not used Fi...

Страница 3: ...be used depending on the line to neutral voltage Line to Neutral Voltage WattNode Model 120 VAC WNB 3Y 208 P Single Phase Three Wire This configuration is seen in North American residential and comme...

Страница 4: ...this configuration the WattNode is powered from the A and B phase A and phase B terminals For best accuracy we recommend connecting the WattNode N neutral terminal to earth ground This will not cause...

Страница 5: ...e Models The following table shows the WattNode model that should be used depending on the line to neutral voltage and line to line voltage also called phase to phase voltage Line to Neutral Voltage L...

Страница 6: ...and ground If you see a reading between 0 and 5 VAC that leg is probably grounded The WattNode will correctly measure circuits with a grounded leg but the measured voltage and power for the phase will...

Страница 7: ...d P3 Output P3 P2 P1 COM Connect to pulse port Customer supplied 22 AWG twisted pairs HOBO H21 H22 or U30 Series Data Logger H22 001 shown HOBO UX120 Series Data Logger HOBO ZW Series Wireless Data No...